INVERTER UNIVERSALE AT
Brand: Beghelli
Certifications: UK CA, IP40, CE, IMO IMQ CERTIFIED, IQNET CERTIFIED
Product Overview and Dimensions
Installation Types
For installation inside luminaires (Versione da incorporare):
For ceiling installation in technical spaces outside the luminaire (Versione indipendente):
Dimensions
Length: 227mm
Height: 30mm
Width: 46mm
Technical Specifications
Power Supply: 230V-50Hz
Temperature Ratings: Tc 70°C, ta 0÷50°C
Cable Specification: H07VV-F 0.5~1.5 mm²
WEEE Disposal Symbol: ♺ (Directive 2012/19/UE)
Wiring Configurations
Maintained Configuration with Driver (Configurazione SA con driver)
This configuration connects the EMERGENCY LED MODULE, Signal LED, and Booster Battery to the driver. Connections include RM+, RM-, LED+, LED-, L, N, BAT 2, BAT 1, SA, SE. The system supports REST MODE (cod.2730) and requires LINE SE and LINE SA connections.
Not Maintained Configuration without Driver (Configurazione SE senza driver)
This configuration is similar to the maintained mode but does not include a direct connection for the DRIVER LED. It connects the EMERGENCY LED MODULE, Signal LED, and Booster Battery. Connections include RM+, RM-, LED+, LED-, L, N, BAT 2, BAT 1, SE. The system supports REST MODE (cod.2730) and requires LINE SE and LINE SA connections.
Jumper Settings for Autonomy and Power Output
Jumper Emergency Duration | Autonomy | Pout (W) - Battery Included | Pout (W) - +1 Booster | Pout (W) - +2 Booster |
---|---|---|---|---|
1h | 1h | 5 | 10 | 15 |
1.5h | 1.5h | 3.3 | 6.6 | 10 |
2h | 2h | 2.5 | 5 | 7.5 |
3h | 3h | 1.7 | 3.4 | 5 |
8h | 8h | 0.7 | 1.4 | 2 |
Booster Battery Type: RA13 LiFe 6,4V 1,5Ah
Settings and Operation
General Settings
Settings configured via the B.connect App have priority over settings made directly on the circuit.
Reset and Test Functions
Reset: Pressing the button for 15 seconds restores the circuit settings to their default values.
Test: A brief press of the button activates the lamp for one second, confirming correct emergency operation.
Power Output vs. LED Voltage Graph
The electronic driver provides constant power output, delivering a maximum current of 250mA. If the LED strip voltage is insufficient to achieve the set power, the actual power delivered will be lower, limited by the maximum output current (250mA).
Graph Description: A graph illustrates the relationship between Power Output (Pout W) and LED Voltage (Vled V). It shows distinct curves for 1, 2, and 3 batteries, all referencing a 1-hour autonomy. For example, with 2 batteries and 1-hour autonomy, a Vled of 40V results in a Pmax of 10W at the maximum output current of 250mA.
Maximum LED Current: 250mA.
Note: 10W output is achieved with 2 batteries only when LED voltages are 40V or higher.
Setting with B.connect App
The B.connect App (available on the App Store and Google Play) allows for advanced configuration and testing.
Bluetooth Communication Opening:
- Mode 1 (Inverter NOT POWERED): Press the RESET button to open a 15-minute programming window.
- Mode 2 (First Power-Up): A 2-hour programming window is automatically activated. Note: Bluetooth turns off after 2 hours, but this setting can be modified via the App.
Configuration Options (with/without App)
Configuration/Command | Without App | With App |
---|---|---|
Autonomy - Duration 1h | • Default | • Default |
Autonomy - Duration 1.5h | • With jumper | • |
Autonomy - Duration 2h | • With jumper | • |
Autonomy - Duration 3h | • With jumper | • |
Autonomy - Duration 8h | • With jumper | • |
Setting Even/Odd AT | • | • |
Test Duration 1h / or chosen autonomy | • Test duration 1h | • Test duration 1h |
Reset | • With RESET button | • |
Start/Stop Functional Test | • | • |
Sync Automatic Test | • | • |
Local Action on Single Device: The system allows for local control and testing of individual units.
Unique Device Identification: Each device is identified by a unique QR code.
Technical Details and Safety
Product Identification
Order Code: 19398
Technical Data: 230V 50Hz, 30mA, COS ϕ 0.57, P out 3.6W
Battery Type: LiFe 6,4V 1,5Ah
Supported Autonomies: 1h, 1.5h, 2h, 3h, 8h
Installation Instructions
General: Place the battery pack as far as possible from heat sources, such as the ballast.
Automatic Tests Periodicity
Functional Test: Performed every 28 days.
Autonomy Test: Performed every 26 weeks. Even-numbered lamps conduct their autonomy test one week after odd-numbered lamps.
For operation modes of the centralized diagnosis system, refer to the Control Unit manual (cod. 12100).
LED Signals
- Solid Green: Battery Charged
- Flashing Green: Battery Charging
- One Red Flash: Battery Error - Duration
- Two Red Flashes: Lighting LED Error
- Three Red Flashes: Battery Disconnected
Technical Characteristics
- I OUT MAX: 250mA
- V OUT: 20÷240V
- Recharging Time: 12 hours
- Frequency Band: 2.4GHz-2.4835GHz
- RF Power: <100mW e.i.r.p.
Warnings and Guarantee
This device is intended solely for its designed purpose. Any other use is considered improper and dangerous.
The rechargeable battery is non-replaceable. For any required repairs, contact an authorized technical service center and insist on the use of original spare parts. Failure to comply with these conditions may compromise the safety of the device.
Beghelli S.p.A. declares that the radio transceiver complies with Directive 2014/53/EU. The full text of the EU Declaration of Conformity is available at: www.beghelli.it/en/technical-area/tools/download.
This radio device may be used under "free use" conditions.