Beghelli Formula 65 LED AT Emergency Lighting
Product Overview
The Beghelli Formula 65 LED AT is an emergency lighting fixture designed for reliable operation in various environments. It offers features such as adjustable autonomy, app-based control, and clear LED status indicators.
Installation and Setup
Mounting and Wiring
Refer to the diagrams for mounting instructions. Ensure correct wiring according to local regulations. The fixture is rated IP65.
Autonomy Setting (1h-3h) without App:
To set the autonomy duration (1 hour or 3 hours), connect the battery after cutting the wire for the desired autonomy. A cut wire typically signifies 3-hour autonomy, while an intact wire signifies 1-hour autonomy.
Autonomy Setting with App:
The autonomy setting via the B.connect app takes priority over the physical wire cutting method.
Battery Connection
Connect the battery connector as shown in the diagrams. The battery should be connected after cutting the wire for autonomy selection.
Technical Specifications
Model | Power | Frequency | Cos φ | LED | Battery Type |
R0818 SE | 180mA | 230V 50Hz | 0.047 | 32 LED | LiFe 3.2V 0.5Ah |
R1124 SE | 180mA | 230V 50Hz | 0.047 | 32 LED | LiFe 3.2V 1.5Ah |
R2436 SE | 180mA | 230V 50Hz | 0.047 | 32 LED | LiFe 3.2V 3Ah |
R1124SA (SA) | 180mA | 230V 50Hz | 0.095 | 32 LED | LiFe 3.2V 1.5Ah |
R2436SA (SA) | 180mA | 230V 50Hz | 0.095 | 32 LED | LiFe 3.2V 3Ah |
Autonomy Options: 1h, 1.5h, 2h, 3h, 8h
Configuration and Commands
Without App
- Autonomy: 1h, 1.5h, 2h, 3h, 8h (set by wire cutting)
- SE/SA Setting: (Only on SA luminaires)
- Even/Odd AT Setting
- Test Duration: 1h or selected autonomy
- Factory Reset
With App (B.connect)
The B.connect app (available on App Store and Google Play) allows for advanced configuration:
- Autonomy time setting
- Mode setting (SE/SA)
- Even/odd setting
- Test duration setting
- Luminaire synchronization
- Factory reset
- Emergency Test: Start/Stop Functional Test
Lamp Response:
- 1 high brightness flash: function performed
- 5 low light flashes: function NOT enabled
- No flashing: command NOT received
LED Signals
- Fixed Green: Battery Charged
- Flashing Green: Battery Charging
- One Red Flash: Battery Duration Error
- Two Red Flashes: Lighting LED Error
- Three Red Flashes: Battery Disconnected
Automatic Test Periodicity
- Functional Test (30 sec): Every 28 days
- Autonomy Test (1h): Every 26 weeks
Even-numbered lamps perform the autonomy test one week after odd-numbered lamps.
Optional Accessories
An optional accessory and the Inibit remote control (code 2730) can be used to put the appliance into "rest mode".
Warnings and Guarantee
- This device is intended for its designed purpose only. Any other use is considered improper and dangerous.
- The rechargeable battery and LED source are non-replaceable. For repairs, contact an authorized technical service center and request original spare parts. Failure to comply may compromise safety.
- Caution: Electric Shock
Manufacturer Information
BEGHELLI S.p.A. - Via Mozzeghine 13/15 - località Monteveglio 40053 Valsamoggia (BO) ITALY - Tel. +39 051 9660411 - Fax +39 051 9660444 - N° Verde 800 626626