Beghelli Completa LED CT Emergency Luminaire
Model: Completa LED CT
Manufacturer: Beghelli S.p.A.
Article Number: 334.902.174 B
Product Overview and Ratings
The Beghelli Completa LED CT is an emergency luminaire designed for reliable lighting during power outages. It is available in various IP ratings for different environmental conditions:
- IP40: Suitable for indoor general use.
- IP42: Offers protection against vertically falling water drops.
- IP66: Designed for dust-tight and protection against strong jets of water.
Operating Temperature Range: -10°C to 45°C
Power Supply: 230V - 50Hz
Certifications: CE, IP40, IP66, ISO 14001, ISO 9001
Installation and Wiring
The luminaire can be installed in different configurations. Refer to the diagrams for specific wiring instructions.
The basic autonomy setting can be adjusted by cutting or leaving the wire intact:
- 1h Autonomy (wire intact): For 1 hour of emergency lighting.
- 3h Autonomy (wire cut): For 3 hours of emergency lighting.
Note: The autonomy setting made via the App takes priority over circuit settings.
Diagram shows wiring for standard operation when Infinity Mode is off.
Diagram shows wiring for operation when Infinity Mode is on. Terminals N2 and L2 must be connected as shown in schemes 2.1 or 2.2.
- 1.1 SA (Maintained): Standard wiring for maintained operation.
- 1.2 SE (Non-Maintained): Standard wiring for non-maintained operation.
- 2.1 SA-SE: Wiring for emergency operation due to mains failure (general emergency or local lighting).
- 2.2 SA-SE: Wiring for emergency operation due to general emergency mains failure (CableCom network).
Caution: Do not invert phase and neutral polarity. Maximum 32 lamps can be connected. Do not connect other devices on the L+ N- power cable/BUS.
Advanced Features and Configuration
The Completa LED CT can be configured and controlled using the Beghelli B.connect App or the CableCom Connect central unit (cod. 20151).
The luminaire supports various configurations and functions:
- Autonomy Duration (1h, 1.5h, 2h, 3h, 8h)
- SE/SA Setting (Non-maintained/Maintained - only on SA luminaires)
- AT Setting (even/odd)
- Test Duration (1h or set autonomy)
- Infinity Mode Setting
- Rest Mode
- Factory Reset
- Functional Test Start/Stop
- Autonomy Test Start/Stop
- Automatic Test Sync
- Automatic Test Scheduling
- Failure Report from Remote
- Luminaire Tracking
- Luminaire Type Identification
- AT (Without App and Central): Basic settings can be configured using jumpers or QR code. Default test duration is 1h, Infinity mode is disabled by default.
- AT + App B.connect: Use the B.connect App (available on App Store and Google Play) to access luminaire configuration via the "luminaire" menu.
- AT + CableCom Connect Central Unit (cod. 20151) + App: Centralized control and configuration. Settings can be managed remotely via the "nuBe" cloud.
- 1 high brightness flash: Function performed.
- 5 low light flashes: Function NOT enabled.
- No flashing: Command NOT received.
Note: With CableCom Connect control unit cod. 20151, all configurations and commands can be sent remotely via the "nuBe" cloud.
- Functional Test (30 sec): Every 28 days.
- Autonomy Test (1h): Every 26 weeks.
Even lamps perform the autonomy test 1 week after odd lamps. (0,2,...,8,A,C,E)=even; (1,3,...,9,B,D,F)=odd.
- Fixed Green: Battery Charged.
- Flashing Green: Battery Charging.
- One Red Flash: Battery Error Duration.
- Two Red Flashes: Lighting LED Error.
- Three Red Flashes: Battery Disconnected.
Communication remains possible for 2 hours, and the LED flashes orange for 1 minute to signal communication opening.
Functional Test and Functional STOP Test can be controlled by the B.Connect App at any time without needing to open communication with the device.
Expansion Modules
The luminaire can be expanded with the following modules:
- LG Module (Cod. 15036)
- LG FM Module (Cod. 15037)
- DALI Module (Cod. 15038)
These modules are SELV compliant.
Technical Specifications Table
Model | Current (mA) | Power Factor (COS φ) | LEDs | Battery Type |
---|---|---|---|---|
4200 SE | 180 | 0.047 | 24 | LTO 4,8V 0,5Ah |
4201 SE | 180 | 0.047 | 24 | LTO 4,8V 0,5Ah |
4202 SE | 180 | 0.047 | 24 | 2x LTO 4,8V 0,5Ah |
4203 SA | 180 | 0.095 | 24 | LTO 4,8V 0,5Ah |
4204 SA | 180 | 0.095 | 24 | 2x LTO 4,8V 0,5Ah |
4205 SE | 180 | 0.047 | 24 | 3x LTO 4,8V 0,5Ah |
4206 SA | 180 | 0.095 | 24 | 3x LTO 4,8V 0,5Ah |
* For autonomy management, refer to the table.
** With Infinity mode activated and lamp wired as scheme 2.1, the autonomy is infinite with Cablecom network present (N-L+).
Warnings and Guarantee
Caution: Electric Shock.
This device is intended for its designed purpose only. Any other use is considered improper and dangerous.
The rechargeable battery and LED source are non-replaceable. For repairs, contact an authorized technical service center and request original spare parts. Failure to comply may compromise the safety of the device.