R. STAHL 9176/20-16-00s Loop-Powered Binary Output Isolator Barrier

The R. STAHL 9176/20-16-00s is a loop-powered binary output isolator barrier designed for Ex i field circuits. It is suitable for intrinsically safe operation of Ex i solenoid valves, indicator lamps, or horns.

Key Features

Technical Data

Explosion Protection

ParameterValue
Application range (zones)0, 1, 2, 20, 21, 22
Ex interface zone0, 1, 2, 20, 21, 22
IECEX gas certificateIECEx BVS 13.0012 X
IECEx gas explosion protectionEx nA [ia Ga] IIC T4 Gc
IECEx dust certificateIECEx BVS 13.0012 X
IECEx dust explosion protection[Ex ia Da] IIIC
ATEX gas certificateBVS 04 ATEX E 075 X
ATEX gas explosion protectionII 3 (1) G Ex nA [ia Ga] IIC T4 Gc
ATEX dust certificateBVS 04 ATEX E 075 X
ATEX dust explosion protectionII (1) D [Ex ia Da] IIIC
FM certificateFM16US0122X
CFM certificateFM16CA0067X
Marking cFMusClass I, Div. 2, Groups A,B,C,D; Class I, Zone 2, Group IIC; AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC
CertificatesT4 Mounting vert. at Ta = 70°C, or horizontal Ta = 60°C; See Doc. 91 766 01 31 1
Ship approvalCCS, EU RO MR (DNV)
Declaration of conformityATEX (EUK), China (CCC)

Safety Data

ParameterValue
Max. voltage Uo parallel27.6 V
Max. current Io (Ex ia)110 mA
Max. current Io (Ex ib)50 mA
Max. power Po760 mW
Max. permissible external capacitance C/C for IIC0.085 μF
Max. permissible external inductance L/La for IIC1.2 mH
Max. permissible external capacitance C/C for IIB0.667 μF
Max. permissible external inductance L/La for IIB9 mH
Internal capacitance1.1 nF
Internal inductanceNegligible
Max. voltage Uo parallel27.6 V
Max. power Po parallel1520 mW
Max. current Io (Ex ia) paral.220 mA
Max. current Io (Ex ib) paral.100 mA
Internal capacitance parallel2.2 nF
Internal inductance parallelnegligible
Safety-related max. voltage253 V
Intrinsically safe limiting values inductance L/capacitance C.Max. connectable inductance L/capacitance C₀: 2 parallel channels
IICL₀ [mH]: 1.8 mH; C₀ [µF]: 0.665 μF
IIBL₀ [mH]: 1.800 mH; C₀ [µF]: 0.665 μF

Electrical Data

ParameterValue
Number of channels2
Internal resistance R250 Ω
Auxiliary Powerwithout
Auxiliary power consumption0.5 W + (I x 37 mW/mA)
Polarity reversal protectionYes
Galvanic Isolation
Test voltage as per standardEN IEC 60079-11
Ex i input to Ex i input500 V AC
Test voltage as per standardEN 50178
Input to input350 V AC

Input

ParameterValue
InputIn accordance with EN 61131-2
Input voltage for ON18 – 31.2 V
Input voltage for OFF0 – 5 V
Control Power PE0.5 W + (IA x 37 mW/mA) (with IA = max. required output current)

Output

ParameterValue
Output open-circuit voltage U₂25 V
Max. output current Ia max35 mA
Max. output current I noteParallel channels: 70 mA
Internal resistance R₁ note250 Ω/parallel: 125 Ω
Output residual ripple< 100 mV
Output switching frequency≤ 10 Hz
Switching delay ON/OFF≤ 50 ms
Switching delay OFF/ON≤ 18 ms
Switching state indicationYellow "OUT" LED

Output Characteristic Curve

A graphical representation shows the output characteristic for the 9175/.0-16-11; 9176/.0-16-00 series. The X-axis represents current in mA (0-45 mA), and the Y-axis represents voltage in V (0-25 V). Curve A illustrates the characteristic for each channel, while Curve B shows the characteristic for channel 1 and parallel channel 2 for types 9176/20-..-....

Ambient Conditions

ParameterValue
Ambient temperature °C-20 °C ... 70 °C (Single device); -20 °C ... 60 °C (Group assembly)
Ambient temperature °F-4 °F ... +158 °F (Single device); -4 °F ... +140 °F (Group assembly)
Storage temperature °C-40 °C ... 80 °C
Storage temperature °F-40 °F ... +176 °F
Max. relative humidity95%
Use at the height of< 2000 m
Electromagnetic compatibilityTested to the following standards and regulations: EN 61326-1 For use in industrial areas; NAMUR NE 21

Note: Installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".

Mechanical Data

ParameterValue
Degree of protection (IP)IP30
Degree of protection (IP) terminalsIP20
Fire resistance (UL 94)V0
Enclosure materialPolyamide
Grid dimension17.6 mm
Width17.6 mm
Width, inches0.69 in
Height114.5 mm
Height in inches4.51 in
Length108 mm
Length in inches4.25 in
Weight185 g
Weight0.41 lb

Mounting / Installation

ParameterValue
Mounting orientationVertical, Horizontal
Connection typeScrew terminal
Min. rigid conductor cross section0.2 mm²
Max. rigid conductor cross section2.5 mm²
Min. flex conductor cross section0.2 mm²
Max. flex conductor cross section2.5 mm²
Connection cross-section AWG24 ... 14

Technical Drawings

Diagrams illustrate connection configurations for hazardous and non-hazardous locations. The first diagram shows a connection for 9176/10-..-.., and the second for 9176/20-..-..-.., depicting the field device, ISpac Isolator, and control system connections.

Accessories

AccessoryArt. No.
Transparent cover for 91xx ISpac modules (Yellow, transparent). Clear identification of the device for SIL applications. (Packaging unit: 10 pieces)200914

Spare Parts

Screw terminal

DescriptionArt. No.
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, color: green112817
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, color: black112816
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, color: blue112818

Screw terminal with test tap

DescriptionArt. No.
3-pole plug with test tap, screw connector, thread: M3, stripping length: 7 mm, colour: black113005
3-pole plug with test tap, screw connector, thread: M3, stripping length: 7 mm, colour: blue113004

Spring clamp terminal

DescriptionArt. No.
3-pole plug with test tap, spring clamp connection, stripping length: 10 mm, color: green112825
3-pole plug with test tap, spring clamp connection, stripping length: 10 mm, color: black112824
3-pole plug with test tap, spring clamp connection, stripping length: 10 mm, color: blue112826

R. STAHL, INC. | 13259 N. Promenade Blvd. | Stafford, TX 77477 | Tel. +1 800 782 4357

PDF preview unavailable. Download the PDF instead.

ex-single-data-sheet-loop-powered-binary-output-ex-i-field-circuit-9176-20-16-00s-222184-en-us-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 9176 Series: Loop-Powered Binary Output for Ex i Field Circuits
Technical data sheet for the R. STAHL 9176 series of loop-powered binary outputs for Ex i field circuits. This document details technical specifications, safety data, certifications, and accessories for the 9176/20-15-00s model.
Preview R. STAHL 9176/20-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical specifications and data for the R. STAHL 9176/20-16-00s loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous areas.
Preview R. STAHL 9176A Galvanic Isolator: Ex i Field Circuit Output
Technical specifications and features of the R. STAHL 9176A galvanic isolator, a binary output for Ex i field circuits. Details include safety values, electrical characteristics, environmental conditions, and mechanical specifications.
Preview R. STAHL 9176/20-16-00k Loop-Powered Binary Output Ex i Field Circuit
Technical datasheet for the R. STAHL 9176/20-16-00k, a loop-powered binary output for Ex i field circuits. Details technical specifications, safety data, certifications, and dimensions.
Preview R. STAHL 9176/20-15-00s Binary Output Isolator for Ex i Field Circuits
Technical specifications and details for the R. STAHL 9176/20-15-00s loop-powered binary output isolator, designed for Ex i field circuits. This document covers safety data, electrical characteristics, environmental conditions, mechanical data, and accessories.
Preview R. STAHL 9176/10-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical data sheet for the R. STAHL 9176/10-16-00s loop-powered binary output isolator. This device is designed for the intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns, requiring no separate auxiliary power supply. It features galvanically separated inputs and outputs, with two-channel variants offering separated channels. The isolator is suitable for various hazardous area classifications including ATEX, IECEx, and cFMus.
Preview R. STAHL 9176A Series: Loop-Powered Binary Output Ex i Field Circuit Isolators
Technical data and specifications for the R. STAHL 9176A series of loop-powered binary output isolators for Ex i field circuits. Details include safety data, electrical characteristics, environmental conditions, mechanical data, and accessories.
Preview R. STAHL 9176 Series Loop-Powered Binary Output Isolator Barriers for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176 series loop-powered binary output isolator barriers, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous locations.