R. STAHL 9176A Series: Loop-Powered Binary Output Ex i Field Circuit Isolators

Article Number: 222182

Model: MY R. STAHL 9176A

Product Overview

The R. STAHL 9176A series isolators provide binary outputs without auxiliary power for Ex i field circuits. They are suitable for operating solenoid valves, signaling devices, beacons, or horns in hazardous areas. These devices are powered by the control circuit, eliminating the need for separate power supplies. The two-channel variants offer galvanically separated channels, reducing space requirements.

Technical Data

Explosion Protection

Applications (Zones) Interface Ex Zone Approvals
2, 0, 1, 20, 21, 22 IECEx BVS 13.0012 X IECEx gas, IECEx protection against gas explosions: Ex nA [ia Ga] IIC T4 Gc
IECEx BVS 13.0012 X IECEx dust, IECEx protection against dust explosions: [Ex ia Da] IIIC
BVS 04 ATEX E 075 X ATEX gas, ATEX protection against gas explosions: II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
BVS 04 ATEX E 075 X ATEX dust, ATEX protection against dust explosions: II (1) D [Ex ia Da] IIIC
FM16US0122X FM Approvals (FM)
FM16CA0067X FM Approvals (FM)
Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, Group IIC; AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC; T4 Mounting vert. at Ta = 70°C, or horizontal Ta = 60°C CFMus Marked

Certifications

Safety Data

Parameter Value
Maximum Voltage (U) 27.6 V
Maximum Current (Ex ia) 110 mA
Maximum Current (Ex ib) 50 mA
Maximum Power (P) 760 mW
Max. external capacitance (C) for IIC 0.085 µF
Max. external inductance (L) for IIC 1.2 mH
Max. external capacitance (C) for IIB 0.667 µF
Max. external inductance (L) for IIB 9 mH
Internal Capacitance 1.1 nF
Internal Inductance Irrelevant
Max. voltage Uo parallel 27.6 V
Max. current lo (Ex ia) parallel 220 mA
Maximum safety technical voltage 253 V

Electrical Data

Parameter Value
Number of channels 1
Auxiliary Power None
Power consumption auxiliary power 0.5 W + (I x 37 mW/mA)
Reverse polarity protection Yes

Galvanic Separation

Parameter Value
Test voltage according to standard EN IEC 60079-11
Test voltage according to standard EN 50178
Input to Input 350 V AC

Input

Parameter Value
Input voltage for ON 18 - 31.2 V (according to EN 61131-2)
Input voltage for OFF 0 - 5 V
Control power PE 0.5 W + (IA x 37 mW/mA) (with IA = required max. output current)

Output

Parameter Value
Output voltage in open circuit (U₂) 25 V
Max. output current (Ia max) 35 mA
Output internal resistance (R) 250 Ω
Output ripple residual < 100 mV
Output switching frequency <= 10 Hz
Switching delay ON/OFF <= 50 ms
Switching delay OFF/ON <= 18 ms
Status indication Yellow LED "OUT"

Environmental Conditions

Parameter Value
Ambient Temperature (single device) -20 °C ... +70 °C
Ambient Temperature (group mounting) -20 °C ... +60 °C
Ambient Temperature (single device, Fahrenheit) -4 °F ... +158 °F
Ambient Temperature (group mounting, Fahrenheit) -4 °F ... +140 °F
Storage Temperature -40 °C ... +80 °C
Storage Temperature (Fahrenheit) -40 °F ... +176 °F
Maximum relative humidity 95%
Utilization at altitude < 2000 m

Note: Mounting conditions influence ambient temperature. Refer to "Control Cabinet Installation Instructions".

Electromagnetic Compatibility

Tested according to the following standards and regulations: EN 61326-1 for industrial use; NAMUR NE 21.

Mechanical Data

Parameter Value
Degree of protection (IP) IP30
Degree of protection (IP) terminals IP20
Fire resistance (UL 94) V0
Enclosure material Polyamide
Grid dimension 17.6 mm
Width 17.6 mm
Mounting width in inches 0.69 in
Height 114.5 mm
Height in inches 4.51 in
Length 108 mm
Length in inches 4.25 in
Weight 170 g
Weight in pounds 0.37 lb

Mounting / Installation

Parameter Value
Mounting type NS 35/15, NS 35/7.5 DIN rail
Mounting position Horizontal, Vertical
Connection type Screw terminal
Minimum solid conductor cross-section 0.2 mm²
Maximum flexible conductor cross-section 2.5 mm²
Minimum flexible conductor cross-section 0.2 mm²
Maximum flexible conductor cross-section 2.5 mm²
AWG ambient temperature 24 - 14

Technical Drawings and Diagrams

Characteristic Curve

The document includes a characteristic output curve (U/I) for the 9175/.0-16-11 and 9176/.0-16-00 series. Curve A represents the characteristic per channel, and Curve B represents the characteristic for channel 1 parallel to channel 2 (for 9176/20-..-... types).

X-axis: I [mA]

Y-axis: U [V]

Measurement Diagram

A measurement diagram showing dimensions in millimeters and inches is provided for the device.

Overall dimensions: 108 mm [4.25 in] (Length), 114.5 mm [4.51 in] (Height), 17.6 mm [0.69 in] (Width).

The diagram also indicates compatibility with ISpac series 9143, 9146, 9147, 9160, 9162, 9163, 9165, 9167, 9170, 9172, 9175, 9176, 9180, 9182, 9193, and ISbus series 9412 with screw terminals.

Accessories

Description Article Number
Transparent cover for ISpac 91xx modules (yellow, transparent). Unambiguous device marking for SIL applications. (Sales unit: 10 pieces) 200914

Spare Parts

Screw Terminal with Test Socket

Description Article Number
Tripolar plug, screw connection. Screw thread: M3. Stripping length: 7 mm. Color: green. 112817
Tripolar plug, screw connection. Screw thread: M3. Stripping length: 7 mm. Color: black. 112818
Tripolar plug, screw connection. Screw thread: M3. Stripping length: 7 mm. Color: blue. 113005
Tripolar plug, screw connection. Screw thread: M3. Stripping length: 7 mm. Color: black. 113004

Spring Terminal with Test Socket

Description Article Number
Tripolar plug, spring connection. Stripping length: 10 mm. Color: green. 112825
Tripolar plug, spring connection. Stripping length: 10 mm. Color: black. 112824
Tripolar plug, spring connection. Stripping length: 10 mm. Color: blue. 112826

R. STAHL reserves the right to modify technical data, dimensions, weights, designs, and delivery options.

PDF preview unavailable. Download the PDF instead.

ex-single-data-sheet-loop-powered-binary-output-ex-i-field-circuit-9176-10-16-00s-222182-es-es-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 9176A Galvanic Isolator: Technical Specifications and Features
Detailed technical specifications, safety features, and application information for the R. STAHL 9176A loop-powered binary output galvanic isolator for Ex i field circuits. Includes ATEX, IECEx, and cFM certifications.
Preview R. STAHL 9176/10-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical data sheet for the R. STAHL 9176/10-16-00s loop-powered binary output isolator. This device is designed for the intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns, requiring no separate auxiliary power supply. It features galvanically separated inputs and outputs, with two-channel variants offering separated channels. The isolator is suitable for various hazardous area classifications including ATEX, IECEx, and cFMus.
Preview R. STAHL 9176 Series Loop-Powered Binary Output Isolator Barriers for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176 series loop-powered binary output isolator barriers, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous locations.
Preview R. STAHL 9176/10-16-00s: Loop-Powered Binary Output for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176/10-16-00s loop-powered binary output module, designed for intrinsically safe operation of Ex i solenoid valves, signaling devices, and horns. Features include no separate auxiliary power requirement, galvanic isolation, and various safety certifications.
Preview R. STAHL 9176/20-15-00s Binary Output Isolator for Ex i Field Circuits
Technical specifications and details for the R. STAHL 9176/20-15-00s loop-powered binary output isolator, designed for Ex i field circuits. This document covers safety data, electrical characteristics, environmental conditions, mechanical data, and accessories.
Preview R. STAHL 9176A Isolator Barrier: Loop-Powered Binary Output for Ex i Field Circuits
Detailed technical specifications and data for the R. STAHL 9176A Isolator Barrier, a loop-powered binary output device designed for intrinsically safe operation in Ex i field circuits. Learn about its explosion protection, technical data, safety features, and accessories.
Preview R. STAHL 9176/20-16-00k Ex i Binary Output Isolator - Technical Data
Detailed technical specifications and data for the R. STAHL 9176/20-16-00k loop-powered binary output isolator for Ex i field circuits, including safety, electrical, environmental, and mechanical data.
Preview R. STAHL 9176/20-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical specifications and data for the R. STAHL 9176/20-16-00s loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous areas.