R. STAHL 9176 Series Loop-Powered Binary Output Isolator Barriers

Product: Loop-powered binary output

Application: Ex i field circuit

Model Numbers: 9176/10-16-00s

Article Number: 222182

Brand: STAHL

Key Features

The 9176 series binary outputs issue binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps, or horns. These devices are powered by the control circuit and do not require a separate auxiliary power supply. The intrinsically safe outputs are galvanically separated from the inputs. Two-channel variants feature galvanically separated channels.

Technical Data

Explosion Protection

Application range (zones) 2
Ex interface zone 0, 1, 2, 20, 21, 22
IECEx gas certificate IECEx BVS 13.0012 X
IECEx gas explosion protection Ex nA [ia Ga] IIC T4 Gc
IECEx dust certificate IECEx BVS 13.0012 X
IECEx dust explosion protection [Ex ia Da] IIIC
ATEX gas certificate BVS 04 ATEX E 075 X
ATEX gas explosion protection II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
ATEX dust certificate BVS 04 ATEX E 075 X
ATEX dust explosion protection II (1) D [Ex ia Da] IIIC
FM certificate FM16US0122X
CFM certificate FM16CA0067X
Marking cFMus Class I, Div. 2, Groups A,B,C,D;
Class I, Zone 2, Group IIC
AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G;
Class I, Zone 0, [AEx ia]/[Ex ia] IIC
Certificates T4 Mounting vert. at Ta = 70°C, or horizontal Ta = 60°C
See Doc. 91 766 01 31 1
ATEX (BVS), Brazil (ULB), Canada (FM), China (NEPSI), IECEx (BVS), Korea (KTL), SIL (exida), USA (FM)
Ship approval CCS, EU RO MR (DNV)
Declaration of conformity ATEX (EUK), China (CCC)

Safety Data

Max. voltage U₀/V₀c 27.6 V
Max. current I₀ (Ex ia) 110 mA
Max. current Ib (Ex ib) 50 mA
Max. power P₀ 760 mW
Max. permissible external capacitance C/Ca for IIC 0.085 μF
Max. permissible external inductance L/La for IIC 1.2 mH
Max. permissible external capacitance C/Ca for IIB 0.667 μF
Max. permissible external inductance L/La for IIB 9 mH
Internal capacitance 1.1 nF
Internal inductance Negligible
Max. voltage U₀ parallel 27.6 V
Max. current I₀ (Ex ia) paral. 220 mA
Safety-related max. voltage 253 V

Electrical Data

Number of channels 1
Auxiliary Power without
Auxiliary power consumption 0.5 W + (I x 37 mW/mA)
Polarity reversal protection Yes

Galvanic Isolation

Test voltage as per standard EN IEC 60079-11
Test voltage as per standard EN 50178
Input to input 350 V AC

Input

Input In accordance with EN 61131-2
Input voltage for ON 18 – 31.2 V
Input voltage for OFF 0 – 5 V
Control Power PE 0.5 W+ (IA x 37 mW/mA) (with IA = max. required output current)

Output

Output open-circuit voltage U₂ 25 V
Max. output current IA max 35 mA
Output internal resistance Ri 250 Ω
Output residual ripple < 100 mV
Output switching frequency ≤ 10 Hz
Switching delay ON/OFF ≤ 50 ms
Switching delay OFF/ON ≤ 18 ms
Switching state indication Yellow "OUT" LED

Output Characteristic Diagram

A graph shows the output characteristic for the 9175/.0-16-11 and 9176/.0-16-00 models. The X-axis represents current in mA (0-45 mA) and the Y-axis represents voltage in V (0-25 V). Two curves are shown:

The graph is valid for UN; -20 to +60 °C.

Ambient Conditions

Ambient temperature °C -20 °C ... 70 °C (Single device)
-20 °C ... 60 °C (Group assembly)
Ambient temperature °F -4 °F ... +158 °F (Single device)
-4 °F ... +140 °F (Group assembly)
Note The installation conditions affect the ambient temperature. Observe the "Cabinet installation guide".
Storage temperature °C -40 °C ... 80 °C
Storage temperature °F -40 °F ... +176 °F
Max. relative humidity 95%
Use at the height of < 2000 m
Electromagnetic compatibility Tested to the following standards and regulations: EN 61326-1 For use in industrial areas; NAMUR NE 21

Mechanical Data

Degree of protection (IP) IP30
Degree of protection (IP) terminals IP20
Fire resistance (UL 94) V0
Enclosure material Polyamide
Grid dimension 17.6 mm
Width 17.6 mm (0.69 in)
Height 114.5 mm (4.51 in)
Length 108 mm (4.25 in)
Weight 170 g (0.37 lb)

Mounting / Installation

Mounting type DIN rail NS35/15, NS35/7.5
Mounting orientation Horizontal / Vertical
Connection type Screw terminal
Min. rigid conductor cross section 0.2 mm²
Max. rigid conductor cross section 2.5 mm²
Min. flex conductor cross section 0.2 mm²
Max. flex conductor cross section 2.5 mm²
Connection cross-section AWG 24 ... 14

Technical Drawings

Output Characteristic Diagram: (See section above for description)

Connection Diagram: A diagram shows the connection of the 9176/10-..-.. model, illustrating the flow from Field Device to ISpac Isolator, then to the Control System, with connections for Hazardous Location and Nonhazardous Location.

Dimensional Drawings: The document includes diagrams showing the overall dimensions of the unit in mm and inches. Key dimensions include height (114.5 mm / 4.51 in), width (17.6 mm / 0.69 in), and length (108 mm / 4.25 in). It also lists compatible ISpac and ISbus series.

Accessories

Item Description Art. No.
Transparent cover For 91xx ISpac modules
Yellow, transparent
Clear identification of the device for SIL applications.
(Packaging unit: 10 pieces)
200914

Spare Parts

Screw terminal

Description Art. No.
3-pole plug, screw connector
thread: M3
stripping length: 7 mm
color: green
112817
3-pole plug, screw connector
thread: M3
stripping length: 7 mm
color: black
112816
3-pole plug, screw connector
thread: M3
stripping length: 7 mm
color: blue
112818

Screw terminal with test tap

Description Art. No.
3-pole plug with test tap, screw connector
thread: M3
stripping length: 7 mm
colour: black
113005
3-pole plug with test tap, screw connector
thread: M3
stripping length: 7 mm
colour: blue
113004

Spring clamp terminal

Description Art. No.
3-pole plug with test tap, spring clamp connection
stripping length: 10 mm
color: green
112825
3-pole plug with test tap, spring clamp connection
stripping length: 10 mm
color: black
112824
3-pole plug with test tap, spring clamp connection
stripping length: 10 mm
color: blue
112826

PDF preview unavailable. Download the PDF instead.

ex-single-data-sheet-loop-powered-binary-output-ex-i-field-circuit-9176-10-16-00s-222182-en-us-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 9176/20-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical specifications and data for the R. STAHL 9176/20-16-00s loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous areas.
Preview R. STAHL 9176/10-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical data sheet for the R. STAHL 9176/10-16-00s loop-powered binary output isolator. This device is designed for the intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns, requiring no separate auxiliary power supply. It features galvanically separated inputs and outputs, with two-channel variants offering separated channels. The isolator is suitable for various hazardous area classifications including ATEX, IECEx, and cFMus.
Preview R. STAHL 9176/20-15-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical specifications and details for the R. STAHL 9176/20-15-00s loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous areas.
Preview R. STAHL 9176A Isolator Barrier: Loop-Powered Binary Output for Ex i Field Circuits
Detailed technical specifications and data for the R. STAHL 9176A Isolator Barrier, a loop-powered binary output device designed for intrinsically safe operation in Ex i field circuits. Learn about its explosion protection, technical data, safety features, and accessories.
Preview R. STAHL 9176/10-16-00s: Loop-Powered Binary Output for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176/10-16-00s loop-powered binary output module, designed for intrinsically safe operation of Ex i solenoid valves, signaling devices, and horns. Features include no separate auxiliary power requirement, galvanic isolation, and various safety certifications.
Preview R. STAHL Series 9276 Loop-Powered Binary Output Isolator - Technical Data
Detailed technical specifications for the R. STAHL Series 9276 loop-powered binary output isolator (Ex i field circuit), including explosion protection, safety data, electrical data, ambient conditions, and mechanical dimensions.
Preview R. STAHL 9176A Series: Loop-Powered Binary Output Ex i Field Circuit Isolators
Technical data and specifications for the R. STAHL 9176A series of loop-powered binary output isolators for Ex i field circuits. Details include safety data, electrical characteristics, environmental conditions, mechanical data, and accessories.
Preview R. STAHL 9176A Galvanic Isolator: Technical Specifications and Features
Detailed technical specifications, safety features, and application information for the R. STAHL 9176A loop-powered binary output galvanic isolator for Ex i field circuits. Includes ATEX, IECEx, and cFM certifications.