R. STAHL 9176/20-16-00k: Loop-Powered Binary Output for Ex i Field Circuits

Article Number: 222185

Product Overview

The R. STAHL 9176/20-16-00k is a loop-powered binary output device designed for intrinsically safe (Ex i) operation of Ex i solenoid valves, signal lamps, or horns. It requires no separate auxiliary power supply, as it is powered via the control current. The intrinsically safe outputs are galvanically isolated from the inputs. Two-channel variants offer galvanically isolated channels, reducing space requirements.

Technical Data

Explosion Protection

Parameter Value
Area of Operation (Zones) 0, 1, 2, 20, 21, 22
Ex Interface Zone IECEx BVS 13.0012 X
IECEx Gas Explosion Protection Ex nA [ia Ga] IIC T4 Gc
IECEx Dust Explosion Protection [Ex ia Da] IIIC
ATEX Gas Explosion Protection II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
ATEX Dust Explosion Protection II (1) D [Ex ia Da] IIIC
FM Approval FM16US0122X
cFM Approval FM16CA0067X
cFM Marking Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, Group IIC; AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC
Temperature Rating T4 Mounting vert. at Ta = 70°C, or horizontal Ta = 60°C
Certifications ATEX (BVS), Brasilien (ULB), IECEx (BVS), Kanada (FM), Korea (KTL), SIL (exida), USA (FM), Volksrepublik China (NEPSI)
Marine Approval CCS, EU RO MR (DNV)
Conformity Declarations ATEX (EUK), Volksrepublik China (CCC)

Safety-Related Data

Parameter Value
Maximum Voltage Ui 27.6 V
Max. Current Io (Ex ia) 110 mA
Max. Current Io (Ex ib) 50 mA
Maximum Power Po 760 mW
Max. External Capacitance Cext for IIC 0.085 μF
Max. External Inductance Lext for IIC 1.2 mH
Max. External Capacitance Cext for IIB 0.667 μF
Max. External Inductance Lext for IIB 9 mH
Internal Capacitance Ci 1.1 nF
Internal Inductance Li Negligible
Max. Voltage Uo parallel 27.6 V
Max. Power Po parallel 1520 mW
Max. Current Io (Ex ia) parallel 220 mA
Max. Current Io (Ex ib) parallel 100 mA
Internal Capacitance parallel 2.2 nF
Internal Inductance parallel Negligible
Max. Safety Voltage 253 V
Max. Connectable Inductance Lext/Capacitance Cext (2 Channels parallel) L: 1.8 mH, C: 0.665 μF (IIC); L: 1800 mH, C: 0.665 μF (IIIC)

Electrical Data

Parameter Value
Number of Channels 2
Internal Resistance R 250 Ω
Auxiliary Power None
Auxiliary Power Consumption 0.5 W + (Ia x 37 mW / mA)
Reverse Polarity Protection Yes ✔️
Galvanic Isolation Test Voltage (Ex i Input to Ex i Input) 500 V AC (per EN IEC 60079-11)
Galvanic Isolation Test Voltage (Input to Input) 350 V AC (per EN 50178)
Input Voltage for ON 18–31.2 V (per EN 61131-2)
Input Voltage for OFF 0–5 V
Drive Power PE 0.5 W + (Ia x 37 mW / mA)
Output Open-Circuit Voltage Uo 25 V
Max. Output Current Ia 35 mA

Output Characteristics

Parameter Value
Max. Output Current Ia (Parallel Channels) 70 mA
Internal Resistance R (Parallel Channels) 125 Ω
Output Residual Ripple < 100 mV
Output Switching Frequency ≤ 10 Hz
Switching Delay ON/OFF ≤ 50 ms
Switching Delay OFF/ON ≤ 18 ms
Output Status Indicator Yellow LED "OUT"

Output Characteristic Curve:

The document includes a graph illustrating the output characteristic curve for models 9175/.0-16-11 and 9176/.0-16-00. The graph plots current (I [mA]) on the X-axis against voltage (U [V]) on the Y-axis. Curve A represents a single channel, while Curve B represents channel 1 in parallel with channel 2 (for types 9176/20-...). The curves show the operational limits under different temperature conditions.

Environmental Conditions

Parameter Value
Ambient Temperature (Single Device) -20 °C ... 70 °C (-4 °F ... +158 °F)
Ambient Temperature (Group Mounting) -20 °C ... 60 °C (-4 °F ... +140 °F)
Storage Temperature -40 °C ... 80 °C (-40 °F ... +176 °F)
Max. Relative Humidity 95%
Usage at Altitude < 2000 m
Electromagnetic Compatibility Tested according to EN 61326-1, industrial area; NAMUR NE 21

Mechanical Data

Parameter Value
Enclosure Protection (IP) IP30
Terminal Enclosure Protection (IP) IP20
Flammability Rating (UL 94) V0
Housing Material Polyamide
Module Width 17.6 mm (0.69 in)
Height 114.5 mm (4.51 in)
Length 128 mm (5.04 in)
Weight 180 g (0.4 lb)

Mounting and Installation

Wiring Diagram: The document shows a wiring diagram illustrating the connection between an Ex field device, the ISpac isolating transducer, and the PLC/PLS in a safe area. It depicts the Ex area (Division 1, Zone 0/1) and the safe area (Division 2, Zone 2).

Dimensional Drawing: A dimensional drawing provides the overall dimensions of the unit in millimeters and inches.

Accessories

Clear Cover

Available for ISpac Modules 91xx. Yellow, transparent. Provides clear device identification for SIL applications. (Packaging unit: 10 pieces). Article Number: 200914

Spare Parts

Screw Terminals

Description Article Number
3-pole connector, screw terminal, M3 thread, 7 mm stripping length, green 112817
3-pole connector, screw terminal, M3 thread, 7 mm stripping length, black 112816
3-pole connector, screw terminal, M3 thread, 7 mm stripping length, blue 112818

Screw Terminals with Test Socket

Description Article Number
3-pole connector with test socket, screw terminal, M3 thread, 7 mm stripping length, black 113005
3-pole connector with test socket, screw terminal, M3 thread, 7 mm stripping length, blue 113004

Spring Clamp Terminals

Description Article Number
3-pole connector with test socket, spring clamp terminal, 10 mm stripping length, green 112825
3-pole connector with test socket, spring clamp terminal, 10 mm stripping length, black 112824
3-pole connector with test socket, spring clamp terminal, 10 mm stripping length, blue 112826

Note: Technical data, dimensions, weights, constructions, and delivery options are subject to change without notice. Illustrations are non-binding.

Manufacturer: R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG

Contact: Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com

PDF preview unavailable. Download the PDF instead.

ex-single-data-sheet-loop-powered-binary-output-ex-i-field-circuit-9176-20-16-00k-222185-de-de-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 9176A Isolator Barriers: Loop-Powered Binary Output for Ex i Field Circuits
Technical specifications and details for the R. STAHL 9176A series isolator barriers, designed for loop-powered binary outputs in Ex i field circuits. Features include intrinsic safety, galvanic separation, and suitability for solenoid valves and signaling devices.
Preview R. STAHL 9176 Series: Loop-Powered Binary Output for Ex i Field Circuits
Technical data sheet for the R. STAHL 9176 series of loop-powered binary outputs for Ex i field circuits. This document details technical specifications, safety data, certifications, and accessories for the 9176/20-15-00s model.
Preview R. STAHL 9176/20-16-00k Galvanic Isolator: Technical Specifications and Features
Detailed technical specifications, safety features, and electrical characteristics of the R. STAHL 9176/20-16-00k loop-powered binary output Ex i field circuit galvanic isolator. Includes ATEX and IECEx certifications, environmental conditions, and mechanical data.
Preview R. STAHL 9176/20-16-00k Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176/20-16-00k loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns. Features include two-channel variants, no auxiliary power requirement, and galvanic separation.
Preview R. STAHL 9176/20-16-00s Loop-Powered Binary Output Isolator Barrier
Technical data and specifications for the R. STAHL 9176/20-16-00s loop-powered binary output isolator barrier for Ex i field circuits. Features include intrinsic safety, galvanic separation, and suitability for solenoid valves and signaling devices.
Preview R. STAHL 9176/20-16-00k Ex i Binary Output Isolator - Technical Data
Detailed technical specifications and data for the R. STAHL 9176/20-16-00k loop-powered binary output isolator for Ex i field circuits, including safety, electrical, environmental, and mechanical data.
Preview R. STAHL 9176/10-16-00k: Loop-Powered Binary Output for Ex i Field Circuits
Technical data sheet for the R. STAHL 9176/10-16-00k loop-powered binary output module for Ex i field circuits. Details include explosion protection, technical specifications, electrical data, and mechanical data.
Preview R. STAHL 9176A Isolator Barrier: Loop-Powered Binary Output for Ex i Field Circuits
Detailed technical specifications and data for the R. STAHL 9176A Isolator Barrier, a loop-powered binary output device designed for intrinsically safe operation in Ex i field circuits. Learn about its explosion protection, technical data, safety features, and accessories.