R. STAHL 9176/20-16-00s Loop-Powered Binary Output Isolator

For Ex i field circuits

Art. No. 222184

Product Overview

The R. STAHL Series 9176 binary outputs transmit binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns. These devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs. The two-channel variants feature galvanically separated channels.

Technical Data

Explosion Protection

Application range (zones) ?, 0, 1, 2, 20, 21, 22
Ex interface zone IECEx BVS 13.0012 X
IECEx gas explosion protection Ex nA [ia Ga] IIC T4 Gc
IECEx dust certificate IECEx BVS 13.0012 X
IECEx dust explosion protection [Ex ia Da] IIIC
ATEX gas certificate BVS 04 ATEX E 075 X
ATEX gas explosion protection II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
ATEX dust certificate BVS 04 ATEX E 075 X
ATEX dust explosion protection II (1) D [Ex ia Da] IIIC
FMUS certificate FM16US0122X
CFM certificate FM16CA0067X
Marking cFMus Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, Group IIC; AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC; T4 Mounting vert. at Ta = 70°C, or horizontal Ta = 60°C (See Doc. 91 76601 31 1)

Certificates

Certificates ATEX (BVS), Brazil (ULB), Canada (FM), China (NEPSI), IECEx (BVS), Korea (KTL), SIL (exida), USA (FM)
Ship approval CCS, EU RO MR (DNV)
Declaration of conformity ATEX (EUK), China (CCC)

Safety Data

Max. voltage Uo 27.6 V
Max. current Io (Ex ia) 110 mA
Max. current Io (Ex ib) 50 mA
Max. power Po 760 mW
Max. permissible external capacity Co for IIC 0.085 µF
Max. permissible external inductance Lo for IIC 1.2 mH
Max. permissible external capacity Co for IIB 0.667 µF
Max. permissible external inductance Lo for IIB 9 mH
Internal capacitance 1.1 nF
Internal inductance Negligible
Max. voltage Uo parallel 27.6 V
Max. power Po parallel 1520 mW
Max. current Io (Ex ia) parallel 220 mA
Max. current Io (Ex ib) parallel 100 mA
Internal capacitance parallel 2.2 nF
Internal inductance parallel negligible
Safety-related max. voltage 253 V
Intrinsically safe limiting values inductance L/capacitance C Max. connectable inductance L/capacitance Co, 2 parallel channels
IIC L [mH]: 1.8 mH, C [µF]: 0.665 µF
IIB L [mH]: 1.800 mH, C [µF]: 0.665 µF
IIIC L [mH]: 1.800 mH, C [µF]: 0.665 µF

Electrical Data

Number of channels 2
Internal resistance R 250 Ω

Auxiliary Power

Auxiliary power without
Auxiliary power consumption 0.5 W + (I x 37 mW/mA)
Polarity reversal protection Yes

Galvanic Isolation

Test voltage as per standard EN IEC 60079-11
Ex i input to Ex i input 500 V AC
Test voltage as per standard EN 50178
Input to input 350 V AC

Input

Input In accordance with EN 61131-2
Input voltage for ON 18 – 31.2 V
Input voltage for OFF 0 – 5 V
Control Power PE 0.5 W + (IA x 37 mW/mA) (with IA = max. required output current)

Output

Output open-circuit voltage U₂ 25 V
Max. output current Ia max 35 mA
Max. output current I note Parallel channels: 70 mA
Internal resistance R₁ note 250 Ω/parallel: 125 Ω
Output residual ripple < 100 mV
Output switching frequency ≤ 10 Hz
Switching delay ON/OFF ≤ 50 ms
Switching delay OFF/ON ≤ 18 ms
Switching state indication Yellow "OUT" LED

Output Characteristic

The diagram shows the output characteristic for the 9175/.0-16-11 and 9176/.0-16-00 models. The X-axis represents the current in mA, and the Y-axis represents the voltage in V.

Curve A: Characteristic curve for each channel at UN; -20 to +60 °C.

Curve B: Characteristic curve for channel 1, parallel channel 2 (only types 9176/20-..-..-..).

Ambient Conditions

Ambient temperature -20 °C ... 70 °C (Single device)
-20 °C ... 60 °C (Group assembly)
Ambient temperature -4 °F ... +158 °F (Single device)
-4 °F ... +140 °F (Group assembly)
Storage temperature -40 °C ... 80 °C
-40 °F ... +176 °F
Maximum relative humidity 95%
Use at the height of < 2000 m
Electromagnetic compatibility Tested to the following standards and regulations: EN 61326-1 For use in industrial areas; NAMUR NE 21

Note: Installation conditions influence the ambient temperature. Please observe the "Cabinet installation guide".

Mechanical Data

Degree of protection (IP) IP30
Degree of protection (IP) terminals IP20
Fire resistance (UL 94) V0
Enclosure material Polyamide
Grid dimension 17.6 mm
Width 17.6 mm
Width, inches 0.69 in
Height 114.5 mm
Height in inches 4.51 in
Length 108 mm
Length in inches 4.25 in
Weight 185 g
Weight 0.41 lb

Mounting / Installation

Mounting type DIN rail NS35/15, NS35/7.5
Mounting orientation Vertical, Horizontal
Connection type Screw terminal
Min. rigid conductor cross section 0.2 mm²
Max. rigid conductor cross section 2.5 mm²
Min. flex conductor cross section 0.2 mm²
Max. flex conductor cross section 2.5 mm²
Connection cross-section AWG 24 ... 14

Technical Drawings

Connection Diagram Type 9176/20-..-..-..

The diagram illustrates the connection between a Field Device, an ISpac Isolator, and a Control System in both hazardous and safe areas. It shows the intrinsic safety barriers and signal paths.

Accessories

Accessory Description Art. No.
Transparent cover For 91xx ISpac modules
Yellow, transparent
Clear identification of the device for SIL applications.
(Packaging unit: 10 pieces)
200914

Spare Parts

Screw terminal

Description Art. No.
3-pole plug, screw connector
thread: M3
stripping length: 7 mm
colour: green
112817
3-pole plug, screw connector
thread: M3
stripping length: 7 mm
colour: black
112816
3-pole plug, screw connector
thread: M3
stripping length: 7 mm
colour: blue
112818

Screw terminal with test tap

Description Art. No.
3-pole plug with test tap, screw connector
thread: M3
stripping length: 7 mm
colour: black
113005
3-pole plug with test tap, screw connector
thread: M3
stripping length: 7 mm
colour: blue
113004

Spring clamp terminal

Description Art. No.
3-pole plug with test tap, spring clamp connection
stripping length: 10 mm
colour: green
112825
3-pole plug with test tap, spring clamp connection
stripping length: 10 mm
colour: black
112824
3-pole plug with test tap, spring clamp connection
stripping length: 10 mm
colour: blue
112826

R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG

Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com

PDF preview unavailable. Download the PDF instead.

ex-single-data-sheet-loop-powered-binary-output-ex-i-field-circuit-9176-20-16-00s-222184-en-gb-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 9176 Series Loop-Powered Binary Output Isolator Barriers for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176 series loop-powered binary output isolator barriers, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous locations.
Preview R. STAHL 9176/20-15-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical specifications and details for the R. STAHL 9176/20-15-00s loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous areas.
Preview R. STAHL 9176/10-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical data sheet for the R. STAHL 9176/10-16-00s loop-powered binary output isolator. This device is designed for the intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns, requiring no separate auxiliary power supply. It features galvanically separated inputs and outputs, with two-channel variants offering separated channels. The isolator is suitable for various hazardous area classifications including ATEX, IECEx, and cFMus.
Preview R. STAHL 9176A Isolator Barrier: Loop-Powered Binary Output for Ex i Field Circuits
Detailed technical specifications and data for the R. STAHL 9176A Isolator Barrier, a loop-powered binary output device designed for intrinsically safe operation in Ex i field circuits. Learn about its explosion protection, technical data, safety features, and accessories.
Preview R. STAHL Series 9276 Loop-Powered Binary Output Isolator - Technical Data
Detailed technical specifications for the R. STAHL Series 9276 loop-powered binary output isolator (Ex i field circuit), including explosion protection, safety data, electrical data, ambient conditions, and mechanical dimensions.
Preview R. STAHL 9176/10-16-00s: Loop-Powered Binary Output for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176/10-16-00s loop-powered binary output module, designed for intrinsically safe operation of Ex i solenoid valves, signaling devices, and horns. Features include no separate auxiliary power requirement, galvanic isolation, and various safety certifications.
Preview R. STAHL 9276/10-21-40-00s Loop-Powered Binary Output Isolator - Technical Data
Detailed technical specifications for the R. STAHL 9276/10-21-40-00s loop-powered binary output isolator, designed for Ex i field circuits. Includes explosion protection, safety data, electrical specifications, ambient conditions, and mechanical data.
Preview R. STAHL 9176/20-16-00s Loop-Powered Binary Output Isolator Barrier
Technical data and specifications for the R. STAHL 9176/20-16-00s loop-powered binary output isolator barrier for Ex i field circuits. Features include intrinsic safety, galvanic separation, and suitability for solenoid valves and signaling devices.