R. STAHL 9176/10-16-00s: Loop-Powered Binary Output for Ex i Field Circuits

Art. Nr. 222182

Product Overview

The R. STAHL 9176/10-16-00s is a loop-powered binary output module designed for intrinsically safe operation of Ex i solenoid valves, signaling devices, and horns. It requires no separate auxiliary power, as it is supplied via the control current circuit. The intrinsically safe outputs are galvanically isolated from the input circuits. Two-channel variants offer galvanically isolated channels, reducing space requirements.

Technical Data

Explosionsschutz

Explosion protection (Zones) 0, 1, 2, 20, 21, 22
Ex Interface Zone IECEx BVS 13.0012 X
IECEx Gas Explosion Protection Ex nA [ia Ga] IIC T4 Gc
IECEx Dust Explosion Protection [Ex ia Da] IIIC
ATEX Gas Explosion Protection II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
ATEX Dust Explosion Protection II (1) D [Ex ia Da] IIIC
FM16US0122X
FM16CA0067X
cFM Marking Class I, Div. 2, Groups A,B,C,D;
Class I, Zone 2, Group IIC
AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G;
Class I, Zone 0, [AEx ia]/[Ex ia] IIC
Certifications ATEX (BVS), Brazil (ULB), IECEx (BVS), Canada (FM), Korea (KTL), SIL (exida), USA (FM), People's Republic of China (NEPSI)
Marine Approval CCS, EU RO MR (DNV)
Conformity Declarations ATEX (EUK), People's Republic of China (CCC)

Safety-Related Data

Max. Voltage Uo 27.6 V
Max. Current Io (Ex ia) 220 mA
Max. Current Io (Ex ib) 50 mA
Maximum Power P. 760 mW
Max. permissible external capacitance C. for IIC 0.085 μF
Max. permissible external inductance L. for IIC 1.2 mH
Max. permissible external capacitance C. for IIB 0.667 μF
Max. permissible external inductance L. for IIB 9 mH
Internal Capacitance C 1.1 nF
Internal Inductance L negligible
Max. Voltage Uo parallel 27.6 V
Max. Current Io (Ex ia) parallel 220 mA
Safety-related voltage max. 253 V

Electrical Data

Number of channels 1
Auxiliary Power None
Auxiliary Power Power Consumption 0.5 W + (Ia x 37 mW / mA)
Reverse Polarity Protection Yes ✔️

Galvanic Isolation

Test Voltage per Norm EN IEC 60079-11
Test Voltage per Norm EN 50178
Input to Input 350 V AC

Input

Input per EN 61131-2
Input Voltage for ON 18 - 31.2 V
Input Voltage for OFF 0 - 5 V
Control Power P 0.5 W + (IA x 37 mW / mA) (with I = max. required output current)

Output

Output Open Circuit Voltage U 25 V
Max. Output Current Ia max 35 mA
Output Internal Resistance R 250 Ω
Output Residual Ripple < 100 mV
Output Switching Frequency ≤ 10 Hz
Switching Delay ON/OFF ≤ 50 ms
Switching Delay OFF/ON ≤ 18 ms
Output Status Indicator Yellow LED "OUT"

Output Characteristic Curve

The output characteristic curve for 9175/.0-16-11 and 9176/.0-16-00 is provided, showing the relationship between current (I [mA]) and voltage (U [V]).

Note:

Environmental and Mechanical Data

Environmental Conditions

Ambient Temperature -20 °C ... 70 °C (Single Device)
Ambient Temperature -20 °C ... 60 °C (Group Assembly)
Ambient Temperature (°F) -4 °F ... +158 °F (Single Device)
Ambient Temperature (°F) -4 °F ... +140 °F (Group Assembly)
Note Installation conditions influence ambient temperature. Refer to "Installation Manual Control Cabinet".
Storage Temperature -40 °C ... 80 °C
Storage Temperature (°F) -40 °F ... +176 °F
Maximum Relative Humidity 95%
Usage at Altitude < 2000 m
Electromagnetic Compatibility Tested according to the following standards and regulations: EN 61326-1 for industrial use; NAMUR NE 21

Mechanical Data

Housing Protection (IP) IP30
Terminal Protection (IP) IP20
Flame Resistance (UL 94) VO
Housing Material Polyamide
Pitch 17.6 mm
Width 17.6 mm (0.69 in)
Height 114.5 mm (4.51 in)
Length 108 mm (4.25 in)
Weight 170 g (0.37 lb)

Mounting / Installation

Mounting Type DIN rail NS35/15, NS35/7.5
Installation Position Horizontal, Vertical
Connection Type Screw terminal
Conductor Cross-section, solid, min. 0.2 mm²
Conductor Cross-section, solid, max. 2.5 mm²
Conductor Cross-section, flexible, min. 0.2 mm²
Conductor Cross-section, flexible, max. 2.5 mm²
Connection Cross-section AWG 24 ... 14

Accessories and Spare Parts

Technical Drawing

A technical drawing illustrating the dimensions and connection diagram is provided. It shows the device in relation to Ex-zones and safe areas, with connections to field devices and PLC/PLS.

Accessories

Clear Cover For ISpac Modules 91xx, yellow, transparent. For unique device identification for SIL applications. (Packaging unit: 10 pieces) Art. Nr. 200914

Spare Parts

Screw Terminal Blocks
3-pole plug, screw connection, Screw thread: M3, Stripping length: 7 mm, Color: green Art. Nr. 112817
3-pole plug, screw connection, Screw thread: M3, Stripping length: 7 mm, Color: black Art. Nr. 112816
3-pole plug, screw connection, Screw thread: M3, Stripping length: 7 mm, Color: blue Art. Nr. 112818
Screw Terminal Blocks with Test Access
3-pole plug with test access, screw connection, Screw thread: M3, Stripping length: 7 mm, Color: black Art. Nr. 113005
3-pole plug with test access, screw connection, Screw thread: M3, Stripping length: 7 mm, Color: blue Art. Nr. 113004
Spring Clamp Terminal Blocks
3-pole plug with test access, spring clamp connection, Stripping length: 10 mm, Color: green Art. Nr. 112825
3-pole plug with test access, spring clamp connection, Stripping length: 10 mm, Color: black Art. Nr. 112824
3-pole plug with test access, spring clamp connection, Stripping length: 10 mm, Color: blue Art. Nr. 112826

PDF preview unavailable. Download the PDF instead.

ex-single-data-sheet-loop-powered-binary-output-ex-i-field-circuit-9176-10-16-00s-222182-de-de-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 9176 Series Loop-Powered Binary Output Isolator Barriers for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176 series loop-powered binary output isolator barriers, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous locations.
Preview R. STAHL 9176/10-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical data sheet for the R. STAHL 9176/10-16-00s loop-powered binary output isolator. This device is designed for the intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns, requiring no separate auxiliary power supply. It features galvanically separated inputs and outputs, with two-channel variants offering separated channels. The isolator is suitable for various hazardous area classifications including ATEX, IECEx, and cFMus.
Preview R. STAHL 9176/20-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical specifications and data for the R. STAHL 9176/20-16-00s loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous areas.
Preview R. STAHL 9176A Series: Loop-Powered Binary Output Ex i Field Circuit Isolators
Technical data and specifications for the R. STAHL 9176A series of loop-powered binary output isolators for Ex i field circuits. Details include safety data, electrical characteristics, environmental conditions, mechanical data, and accessories.
Preview R. STAHL 9176A Isolator Barrier: Loop-Powered Binary Output for Ex i Field Circuits
Detailed technical specifications and data for the R. STAHL 9176A Isolator Barrier, a loop-powered binary output device designed for intrinsically safe operation in Ex i field circuits. Learn about its explosion protection, technical data, safety features, and accessories.
Preview R. STAHL 9176A Galvanic Isolator: Technical Specifications and Features
Detailed technical specifications, safety features, and application information for the R. STAHL 9176A loop-powered binary output galvanic isolator for Ex i field circuits. Includes ATEX, IECEx, and cFM certifications.
Preview R. STAHL 9176/20-15-00k Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical specifications and data for the R. STAHL 9176/20-15-00k loop-powered binary output isolator, designed for intrinsically safe operation in Ex i field circuits. Features include suitability for solenoid valves and signaling devices, two-channel variants, and no need for separate auxiliary power.
Preview R. STAHL 9176/20-15-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical specifications and details for the R. STAHL 9176/20-15-00s loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous areas.