R. STAHL Isolators: Loop-powered binary output

Ex i field circuit

Model: 9176/20-15-00k | Art. No. 222181

The R. STAHL Series 9176 binary outputs transmit binary signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns. These devices are powered by the control circuit, eliminating the need for a separate auxiliary power supply. The intrinsically safe outputs are galvanically separated from the inputs. Two-channel variants offer space savings and feature galvanically separated channels.

Technical Data

Explosion Protection

Application range (zones) 2, 0, 1, 2, 20, 21, 22
Ex interface zone IECEx BVS 13.0012 X
IECEx gas explosion protection Ex nA [ia Ga] IIC T4 Gc
IECEx dust certificate IECEx BVS 13.0012 X
IECEx dust explosion protection [Ex ia Da] IIIC
ATEX gas certificate BVS 04 ATEX E 075 X
ATEX gas explosion protection II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
ATEX dust certificate BVS 04 ATEX E 075 X
ATEX dust explosion protection II (1) D [Ex ia Da] IIIC
FMUS certificate FM16US0122X
CFM certificate FM16CA0067X
Marking cFMus Class I, Div. 2, Groups A,B,C,D;
Class I, Zone 2, Group IIC
AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G;
Class I, Zone 0, [AEx ia]/[Ex ia] IIC
Certificates ATEX (BVS), Brazil (ULB), Canada (FM), China (NEPSI), IECEx (BVS), Korea (KTL), SIL (exida), USA (FM)
Ship approval CCS, EU RO MR (DNV)
Declaration of conformity ATEX (EUK), China (CCC)

Safety Data

Max. voltage Uo 27.6 V
Max. current I (Ex ia) 86.5 mA
Max. current I (Ex ib) 44 mA
Max. power Po 596 mW
Max. permissible external capacity Co for IIC 0.085 µF
Max. permissible external inductance Lo for IIC 1.8 mH
Max. permissible external capacity Co for IIB 0.667 µF
Max. permissible external inductance Lo for IIB 17 mH
Internal capacitance 1.1 nF
Internal inductance Negligible
Max. voltage Uo parallel 27.6 V
Max. power Po parallel 1192 mW
Max. current Io (Ex ia) paral. 173 mA
Max. current Io (Ex ib) paral. 88 mA
Internal capacitance parallel 2.2 nF
Internal inductance parallel negligible
Safety-related max. voltage 253 V
Intrinsically safe limiting values inductance L / capacitance C Max. connectable inductance L / capacitance Co: 2 parallel channels
IIC L: 2.5 mH, C: 2.500 mF
IIB L: 2.5 mH, C: 0.665 µF
IIIC L: 2.500 mH, C: 0.665 µF

Electrical Data

Number of channels 2
Internal resistance R 320 Ω
Auxiliary power without
Auxiliary power consumption 0.5 W + (I x 37 mW/mA)
Polarity reversal protection Yes

Galvanic Isolation

Test voltage as per standard EN IEC 60079-11
Ex i input to Ex i input 500 V AC
Test voltage as per standard EN 50178
Input to input 350 V AC

Input

Input In accordance with EN 61131-2
Input voltage for ON 18 - 31.2 V
Input voltage for OFF 0 - 5 V
Control Power PE 0.5 W + (IA x 37 mW/mA) (with IA = max. required output current)

Output

Output open-circuit voltage U₂ 25 V
Max. output current Iₐ max 29 mA
Max. output current I note Parallel channels: 58 mA
Internal resistance R₁ note 320 Ω/parallel: 160 Ω
Output residual ripple < 100 mV
Output switching frequency ≤ 10 Hz
Switching delay ON/OFF ≤ 50 ms
Switching delay OFF/ON ≤ 18 ms
Switching state indication Yellow "OUT" LED

Output Characteristic Diagram

The diagram shows the output characteristic curve for the 9176/.0-15-00. Curve A represents the characteristic for each channel, while Curve B represents the characteristic for channel 1 in parallel channel 2 configurations (for types 9176/20-...). The x-axis represents current in mA, and the y-axis represents voltage in V. The curves are shown for an ambient temperature of -20 to +60 °C.

Ambient Conditions

Ambient temperature -20 °C ... 70 °C (Single device)
-20 °C ... 60 °C (Group assembly)
Ambient temperature -4 °F ... +158 °F (Single device)
-4 °F ... +140 °F (Group assembly)
Storage temperature -40 °C ... 80 °C
-40 °F ... +176 °F
Maximum relative humidity 95%
Use at the height of < 2000 m
Electromagnetic compatibility Tested to the following standards and regulations: EN 61326-1 For use in industrial areas; NAMUR NE 21

Mechanical Data

Degree of protection (IP) IP30
Degree of protection (IP) terminals IP20
Fire resistance (UL 94) VO
Enclosure material Polyamide
Grid dimension 17.6 mm
Width 17.6 mm
Width, inches 0.69 in
Height 114.5 mm
Height in inches 4.51 in
Length 128 mm
Length in inches 5.04 in
Weight 180 g
Weight 0.4 lb

Mounting / Installation

Mounting orientation Horizontal
Vertical
Connection type Spring clamp terminal
Min. rigid conductor cross section 0.2 mm²
Max. rigid conductor cross section 2.5 mm²
Min. flex conductor cross section 0.2 mm²
Max. flex conductor cross section 2.5 mm²
Connection cross-section AWG 24 ... 14

Technical Drawings - Subject to Alterations

The diagram illustrates the hazardous and safe area classifications, showing Division 1, Zone 0/1 in the hazardous area and Division 2, Zone 2 in the safe area. It depicts the connection between a Field Device, an ISpac Isolator, and a Control System.

The dimensional drawings provide overall dimensions in millimeters and inches for the device, including length, width, and height.

Accessories

Description Art. No.
Transparent cover for 91xx ISpac modules. Yellow, transparent. Clear identification of the device for SIL applications. (Packaging unit: 10 pieces) 200914

Spare Parts

Screw terminal

Description Art. No.
3-pole plug, screw connector
thread: M3
stripping length: 7 mm
colour: green
112817
3-pole plug, screw connector
thread: M3
stripping length: 7 mm
colour: black
112816
3-pole plug, screw connector
thread: M3
stripping length: 7 mm
colour: blue
112818

Screw terminal with test tap

Description Art. No.
3-pole plug with test tap, screw connector
thread: M3
stripping length: 7 mm
colour: black
113005
3-pole plug with test tap, screw connector
thread: M3
stripping length: 7 mm
colour: blue
113004

Spring clamp terminal

Description Art. No.
3-pole plug with test tap, spring clamp connection
stripping length: 10 mm
colour: green
112825
3-pole plug with test tap, spring clamp connection
stripping length: 10 mm
colour: black
112824
3-pole plug with test tap, spring clamp connection
stripping length: 10 mm
colour: blue
112826

R. STAHL reserves the right to make alterations to the technical data, dimensions, weights, designs, and products available without notice. The illustrations cannot be considered binding.

PDF preview unavailable. Download the PDF instead.

ex-single-data-sheet-loop-powered-binary-output-ex-i-field-circuit-9176-20-15-00k-222181-en-gb-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 9176A Isolator Barriers: Loop-Powered Binary Output for Ex i Field Circuits
Technical specifications and details for the R. STAHL 9176A series isolator barriers, designed for loop-powered binary outputs in Ex i field circuits. Features include intrinsic safety, galvanic separation, and suitability for solenoid valves and signaling devices.
Preview R. STAHL 9176/20-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical specifications and data for the R. STAHL 9176/20-16-00s loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous areas.
Preview R. STAHL 9176A Isolator Barrier: Loop-Powered Binary Output for Ex i Field Circuits
Detailed technical specifications and data for the R. STAHL 9176A Isolator Barrier, a loop-powered binary output device designed for intrinsically safe operation in Ex i field circuits. Learn about its explosion protection, technical data, safety features, and accessories.
Preview R. STAHL 9176 Series Loop-Powered Binary Output Isolator Barriers for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176 series loop-powered binary output isolator barriers, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous locations.
Preview R. STAHL 9176/10-16-00s: Loop-Powered Binary Output for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176/10-16-00s loop-powered binary output module, designed for intrinsically safe operation of Ex i solenoid valves, signaling devices, and horns. Features include no separate auxiliary power requirement, galvanic isolation, and various safety certifications.
Preview R. STAHL 9176/20-15-00k Isolator Barrier: Technical Specifications and Features
Detailed technical data, safety information, and specifications for the R. STAHL 9176/20-15-00k loop-powered binary output isolator barrier for Ex i field circuits. Includes explosion protection, electrical data, ambient conditions, and mechanical data.
Preview R. STAHL 9176/20-15-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical specifications and details for the R. STAHL 9176/20-15-00s loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous areas.
Preview R. STAHL 9176/10-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical data sheet for the R. STAHL 9176/10-16-00s loop-powered binary output isolator. This device is designed for the intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns, requiring no separate auxiliary power supply. It features galvanically separated inputs and outputs, with two-channel variants offering separated channels. The isolator is suitable for various hazardous area classifications including ATEX, IECEx, and cFMus.