R. STAHL 9176/20-15-00s Loop-Powered Binary Output Isolator

Product Type: Ex i field circuit Isolator

Article Number: 222180

Product Overview

The R. STAHL Series 9176 binary outputs are designed for the intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns. These devices are powered by the control circuit, eliminating the need for a separate auxiliary power supply. The intrinsically safe outputs are galvanically separated from the inputs. Two-channel variants offer galvanically separated channels, reducing the required space.

Technical Data

Explosion Protection

Application range (zones) 2, 0, 1, 20, 21, 22
Ex interface zone IECEx BVS 13.0012 X
IECEx gas explosion protection Ex nA [ia Ga] IIC T4 Gc
IECEx dust certificate IECEx BVS 13.0012 X
IECEx dust explosion protection [Ex ia Da] IIIC
ATEX gas certificate BVS 04 ATEX E 075 X
ATEX gas explosion protection II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
ATEX dust certificate BVS 04 ATEX E 075 X
ATEX dust explosion protection II (1) D [Ex ia Da] IIIC
FMUS certificate FM16US0122X
CFM certificate FM16CA0067X
Marking cFMus Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, Group IIC; AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC
Certificates ATEX (BVS), Brazil (ULB), Canada (FM), China (NEPSI), IECEx (BVS), Korea (KTL), SIL (exida), USA (FM)
Ship approval CCS, EU RO MR (DNV)
Declaration of conformity ATEX (EUK), China (CCC)

Safety Data

Max. permissible external capacity C. for IIC 0.085 µF
Max. permissible external inductance L. for IIC 1.8 mH
Max. permissible external capacity C. for IIB 0.667 µF
Max. permissible external inductance L. for IIB 17 mH
Internal capacitance 1.1 nF
Internal inductance Negligible
Max. voltage Uo parallel 27.6 V
Max. power Po parallel 1192 mW
Max. current Io (Ex ia) parallel 173 mA
Max. current Io (Ex ib) parallel 88 mA
Internal capacitance parallel 2.2 nF
Internal inductance parallel negligible
Safety-related max. voltage 253 V
Intrinsically safe limiting values inductance L/capacitance C. Max. connectable inductance L/capacitance C. 2 parallel channels
IIC L. [mH]: 2.5 mH, C. [µF]: 2.500 µF
IIB L. [mH]: 2.5 mH, C. [µF]: 0.665 µF
IIIC L. [mH]: 2.500 mH, C. [µF]: 0.665 µF

Electrical Data

Number of channels 2
Internal resistance R 320 Ω
Auxiliary power without
Auxiliary power consumption 0.5 W + (I x 37 mW/mA)
Polarity reversal protection Yes
Galvanic Isolation
Test voltage as per standard (Ex i input to Ex i input) EN IEC 60079-11, 500 V AC
Test voltage as per standard (Input to input) EN 50178, 350 V AC

Input

In accordance with EN 61131-2
Input voltage for ON 18 – 31.2 V
Input voltage for OFF 0 – 5 V
Control Power PE 0.5 W + (IA x 37 mW/mA) (with IA = max. required output current)

Output

Output open-circuit voltage U₂ 25 V
Max. output current Ia max 29 mA
Max. output current I note Parallel channels: 58 mA
Internal resistance R₁ note 320 Ω/parallel: 160 Ω
Output residual ripple < 100 mV
Output switching frequency ≤ 10 Hz
Switching delay ON/OFF ≤ 50 ms
Switching delay OFF/ON ≤ 18 ms
Switching state indication Yellow "OUT" LED

Output Characteristic

A graph shows the output characteristic for the 9176/.0-15-00. The X-axis represents current [mA] and the Y-axis represents voltage. Two curves are shown: Curve A for a single channel and Curve B for parallel channels. The graph indicates operating conditions at UN; -20 to +60 °C.

Ambient Conditions

Ambient temperature (Single device) -20 °C ... 70 °C
Ambient temperature (Group assembly) -20 °C ... 60 °C
Ambient temperature (Single device, Fahrenheit) -4 °F ... +158 °F
Ambient temperature (Group assembly, Fahrenheit) -4 °F ... +140 °F
Storage temperature -40 °C ... 80 °C
Storage temperature (Fahrenheit) -40 °F ... +176 °F
Maximum relative humidity 95%
Use at the height of < 2000 m
Electromagnetic compatibility Tested to EN 61326-1 for industrial areas; NAMUR NE 21

Note: Installation conditions influence the ambient temperature. Please observe the "Cabinet installation guide".

Mechanical Data

Degree of protection (IP) IP30
Degree of protection (IP) terminals IP20
Fire resistance (UL 94) V0
Enclosure material Polyamide
Grid dimension 17.6 mm
Width 17.6 mm
Width, inches 0.69 in
Height 114.5 mm
Height in inches 4.51 in
Length 108 mm
Length in inches 4.25 in
Weight 185 g
Weight 0.41 lb

Mounting / Installation

Mounting orientation Vertical, Horizontal
Connection type Screw terminal
Min. rigid conductor cross section 0.2 mm²
Max. rigid conductor cross section 2.5 mm²
Min. flex conductor cross section 0.2 mm²
Max. flex conductor cross section 2.5 mm²
Connection cross-section AWG 24 ... 14

Technical Drawings

A connection diagram illustrates the setup for the ISpac Isolator within hazardous and safe areas. It shows the Field Device connected to the ISpac Isolator, which is then connected to the Control System. The diagram indicates hazardous area zones (Division 1, Zone 0/1) and safe area zones (Division 2, Zone 2).

Accessories

Accessory Description Article No.
Transparent cover For 91xx ISpac modules, Yellow, transparent. Clear identification of the device for SIL applications. (Packaging unit: 10 pieces) 200914

Spare Parts

Screw terminal

Description Article No.
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, colour: green 112817
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, colour: black 112816
3-pole plug, screw connector, thread: M3, stripping length: 7 mm, colour: blue 112818

Screw terminal with test tap

Description Article No.
3-pole plug with test tap, screw connector, thread: M3, stripping length: 7 mm, colour: black 113005
3-pole plug with test tap, screw connector, thread: M3, stripping length: 7 mm, colour: blue 113004

Spring clamp terminal

Description Article No.
3-pole plug with test tap, spring clamp connection, stripping length: 10 mm, colour: green 112825
3-pole plug with test tap, spring clamp connection, stripping length: 10 mm, colour: black 112824
3-pole plug with test tap, spring clamp connection, stripping length: 10 mm, colour: blue 112826

R. STAHL Schaltgeräte GmbH reserves the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.

PDF preview unavailable. Download the PDF instead.

ex-single-data-sheet-loop-powered-binary-output-ex-i-field-circuit-9176-20-15-00s-222180-en-gb-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 9176/20-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical specifications and data for the R. STAHL 9176/20-16-00s loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous areas.
Preview R. STAHL 9176 Series Loop-Powered Binary Output Isolator Barriers for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176 series loop-powered binary output isolator barriers, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous locations.
Preview R. STAHL 9176/10-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical data sheet for the R. STAHL 9176/10-16-00s loop-powered binary output isolator. This device is designed for the intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns, requiring no separate auxiliary power supply. It features galvanically separated inputs and outputs, with two-channel variants offering separated channels. The isolator is suitable for various hazardous area classifications including ATEX, IECEx, and cFMus.
Preview R. STAHL Series 9276 Loop-Powered Binary Output Isolator - Technical Data
Detailed technical specifications for the R. STAHL Series 9276 loop-powered binary output isolator (Ex i field circuit), including explosion protection, safety data, electrical data, ambient conditions, and mechanical dimensions.
Preview R. STAHL 9176A Isolator Barrier: Loop-Powered Binary Output for Ex i Field Circuits
Detailed technical specifications and data for the R. STAHL 9176A Isolator Barrier, a loop-powered binary output device designed for intrinsically safe operation in Ex i field circuits. Learn about its explosion protection, technical data, safety features, and accessories.
Preview R. STAHL 9276/10-21-40-00s Loop-Powered Binary Output Isolator - Technical Data
Detailed technical specifications for the R. STAHL 9276/10-21-40-00s loop-powered binary output isolator, designed for Ex i field circuits. Includes explosion protection, safety data, electrical specifications, ambient conditions, and mechanical data.
Preview R. STAHL 9176/20-15-00s Binary Output Isolator for Ex i Field Circuits
Technical specifications and details for the R. STAHL 9176/20-15-00s loop-powered binary output isolator, designed for Ex i field circuits. This document covers safety data, electrical characteristics, environmental conditions, mechanical data, and accessories.
Preview R. STAHL 9276/10-24-48-00s Loop-Powered Binary Output Isolator - Technical Data
Detailed technical specifications for the R. STAHL 9276/10-24-48-00s loop-powered binary output isolator, including explosion protection, safety data, electrical characteristics, and mechanical dimensions. Suitable for intrinsically safe operation of Ex i solenoid valves.