Pambuka

Tripp Lite S3MT-30KWR480V lan S3MT-60KWR480V minangka model bungkus 480V sing kalebu rong trafo ing siji kandang: trafo step-down isolasi input 480V (Delta) nganti 208V (Wye) lan 208V (Wye) (Wye) nganti 480V. output otomatis step-up trafo.
Transformer isolasi input nyuda lonjakan lan lonjakan saluran sarana nalika nglindhungi UPS. Autotransformer output dirancang kanggo ndhukung beban IT 480V (Wye). Model kasebut duwe pemutus sirkuit sing dibangun kanggo nyegah kakehan sirkuit sing mbebayani. Papat penggemar bal-prewangan kanggo S3MT-30KWR480V lan wolung penggemar bal-prewangan kanggo S3MT- 60KWR480V njaga operasi sepi lan bantuan kanggo dissipate panas trafo. Relay sensor panas lan saklar termal, digabungake karo lampu LED ing panel ngarep, nyedhiyakake bebaya suhu lan proteksi overheating. Jejak cilik sistem UPS lan pro akustik sing sepifile mbisakake panginstalan kanthi ruang minimal lan pengaruh gangguan. Kabeh model trafo duwe omah stainless steel kanthi panel ngarep sing padha karo garis UPS S3M-Series 208V 3-Phase.

Model UPS Nomer Seri Kapasitas Katrangan
S3MT-30KWR480V
(Ora kompatibel karo
SUT2OK utawa SUT3OK UPS)
AG-0511 30 kW input Transformer: 480V kanggo 208V Isolasi Step-Down Transformer
Transformer Output: 208V kanggo 480V Auto Step-Up Transformer
S3MT-60KWR480V
(Ora kompatibel karo
SUT4OK utawa SUT6OK UPS)
AG-0512 60 kW input Transformer: 480V kanggo 208V Isolasi Step-Down Transformer
Transformer Output: 208V kanggo 480V Auto Step-Up Transformer

Aplikasi khas
4-Wire (3Ph+N+PE) ngemot peralatan IT ing pamaréntahan, manufaktur, rumah sakit, setelan industri, lan setelan perusahaan sing duwe 480V listrik lan 480V IT.

Fitur Utama

  • Transformator step-down input nyedhiyakake proteksi isolasi 480V (Delta) nganti 208V/120V (Wye) menyang input UPS
  • Autotransformer output nyedhiyakake 208V (Wye) nganti 480V (Wye) step-up kanggo ndhukung beban IT 480V
  • Circuit Breakers ing output saka trafo input lan input saka trafo output
  • Bebaya lan pangayoman overheating
  • 95.2% nganti 97.5% efisiensi
  • Lebokake input voltage lan frekuensi operasi sawetara: Voltage: -20% nganti + 25% @ 100% mbukak lan 40-70 Hz
  • Kelas insulasi: bahan 180 ° C
  • Diuji keandalan miturut ISTA-3B kanggo geter, shock, drop (tes tip)
  • Sertifikasi UL lan CSA TUV
  • Omah stainless steel kasar dikirim siap dipasang
  • garansi 2 taun

Konfigurasi Khas
Transformer 480V Wrap-Around (WR) kalebu trafo input (T-in) lan output (T-out) ing siji enclosure.TRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - tokoh 2 Transformer 480V iki bisa dituku kanthi kapisah utawa minangka bagéan saka model kit karo UPS Tripp Lite S3M Series 3-Phase:

Model Transformer Bungkus maksimal
Beban pancet
Kompatibel karo
UPS 208V 3 Ph
Model Kit: UPS + Transformer
Model Kit Model Kit Klebu
480V S3MT-30KWR480V 30 kW UPS 20-30 kW
(Ora kompatibel karo
SUT2OK utawa SUT30K)
S3M30K-30KWR4T S3M3OK UPS +
S3MT-30KWR480V
S3MT-60KWR480V 60 kW 50 60kW UPS
(Ora kompatibel karo
SUT4OK utawa SUT60K)
S3M50K-60KWR4T S3M5OK UPS +
S3MT-60KWR480V
S3M60K-60KWR4T S3M6OK UPS +
S3MT-60KWR480V

Bebaya Safety Penting

SIMPAN INSTRUCTIONS IKI
Manual iki ngemot instruksi penting kanggo model S3MT-30KWR480V lan S3MT-60KWR480V sing kudu ditindakake sajrone instalasi lan pangopènan trafo lan UPS.
AWAS! Resiko kejut listrik! Bagean urip sing mbebayani ing unit iki diuripake saka trafo sanajan pemutus dipateni.
WARNING! Unit iki dimaksudake kanggo instalasi ing lingkungan sing dikontrol.
AWAS! Transformator bisa nyebabake risiko kejut listrik lan arus arus pendek sing dhuwur. Pancegahan ing ngisor iki kudu diamati nalika nggarap trafo:

  • Copot jam tangan, dering, utawa barang logam liyane.
  • Gunakake alat kanthi gagang terisolasi.

Kanggo nyuda resiko kejut listrik, copot trafo lan UPS saka sumber utama sadurunge nindakake pangopènan utawa layanan.
Pelayanan trafo 3 tahap lan UPS kudu ditindakake dening personel tripp Lite sing nduweni sertifikasi babagan trafo 3 tahap lan UPS lan kabeh pancegahan sing dibutuhake.
Transformer kasebut abot banget. Ati-ati kudu ditrapake kanggo mindhah lan posisi posisi. Pandhuan sing ana ing njero manual iki penting lan kudu ditindakake kanthi cepet sawayah-wayah sajrone instalasi lan pangopènan tindakake trafo 3 phase lan UPS.

AWAS!
Transformer duwe tingkat panas sing mbebayani. Yen indikator LED abang panel depan saka trafo aktif, outlet unit kasebut bisa uga duwe panas sing mbebayani.
Kabeh layanan kanggo peralatan iki kudu ditindakake dening personel layanan sing wis disertifikasi Tripp Lite.
Sadurunge nindakake pangopènan, ndandani, utawa ngirim, luwih dhisik, priksa manawa kabeh dipateni lan pedhot.

Simbol Khusus - Simbol ing ngisor iki digunakake ing trafo kanggo ngelingake sampeyan babagan pancegahan:
Ikon ati-atiRISIKO KEJUTAN ELEKTRIK - Mirsani bebaya yen ana risiko kejut listrik.
AWAS – REFER MANUAL OWNER kanggo informasi babagan instruksi operasi lan pangopènan sing penting.
TRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - lambang 1TERMINAL GROUNDING SAFE - Nuduhake lemah aman utama.

Instalasi

Data MekanikTRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - tokoh 3

Syarat Fisik
Ninggalake papan ing kabinet kanggo operasi lan ventilasi (Gambar 3-1):

  1. Ninggalake paling ora 23.6 ing. (600 mm) ruangan ing ngarep kanggo ventilasi
  2. Ninggalake paling ora 20 ing. (500 mm) papan ing sisih tengen lan kiwa kanggo operasi
  3. Ninggalake paling ora 20 ing (500 mm) ruangan ing mburi kanggo ventilasi

TRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - tokoh 4

Inspeksi Paket

  1. Aja ngeculake kabinet trafo nalika nyopot saka bungkus.
  2. Priksa tampilan kanggo ndeleng manawa kabinet trafo rusak nalika transportasi. Aja listrik ing kabinet trafo yen ana karusakan sing ditemokake. Hubungi langsung dealer.
  3. Priksa aksesoris ing dhaptar kemasan lan hubungi dealer yen ana bagean sing ilang.

Mbongkar UPS

  1. Tahan piring geser tetep stabil. Cut lan copot taline sing naleni (Gambar 3-2).
    TRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - tokoh 5
  2. Copot tas plastik lan karton njaba (Gambar 3-3).
    TRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - tokoh 6
  3. Copot bahan pengepakan busa lan palet beveled (Gambar 3-4).
    TRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - tokoh 7
  4. Copot ngawut-awut ngamanake kabinèt kanggo pallet (Figure 3-5).
    TRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - tokoh 8
  5. Angkat kabinet nganggo forklift lan copot palet pengepakan (Gambar 3-6).
    TRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - tokoh 9

Isi Paket

Isine TL P / N S3MT-30KWR480V S3MT-60KWR480V
Transfer Input lan Output ing Siji Kabinet 1 1
Manual Pamilik 933D04 1 1
Rok ngisor 103922A 2 2
Rok ngisor 103923A 2 2
Ngawut-awut kanggo Rok 3011C3 24 24

Kabinet LiwatviewTRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - tokoh 10

1 Output Transformer Over-Temperature Weker LED 6 Output Transformer Breaker karo Trip
2 Input Transformer Over-Temperature Weker LED 7 Input Transformator Kabel Terminal
3 Output Transformer Cooling Fans 8 Terminal Kabel Transformator Output
4 Input Transformer Cooling Fans 9 Knockout Entri Ngisor (kanggo Entri lan Metu Kabel Daya)
5 Input Transformer Breaker karo Trip

TRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - tokoh 11

TRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - tokoh 12

Kabel Daya
Desain kabel bakal sesuai karo voltages lan arus sing diwenehake ing bagean iki, lan sesuai karo kode listrik lokal.

WARNING!
Sawise miwiti, priksa manawa sampeyan ngerti lokasi lan operasi saka isolator njaba sing disambungake menyang input / bypass UPS saka panel distribusi utilitas.
Priksa manawa persediaan iki diisolasi kanthi ELEKTRIK lan ngirim tandha-tandha peringatan sing dibutuhake kanggo nyegah operasi sing ora sengaja.

Ukuran Kabel

Model UPS Ukuran Kabel (kabel THHW ing 75 ° C)
Input AC Output AC Netral Grounding
Gauge Torsi Gauge Torsi Gauge Torsi Gauge Torsi
S3MT- 30KWR480V Transformer input
6AWG
Maks.
3 AWG
6.5N•m 3 AWG
Maks.
3 AWG
6.5N•m 3 AWG
Maks.
3 AWG
6.5N • m 3 AWG
Maks.
3 AWG
6.5 N
Trafo output
6AWG
Maks.
3 AWG
6.5N•m 3 AWG
Maks.
3 AWG
6.5 N 3 AWG
Maks.
3 AWG
6.5 N 3 AWG
Maks.
3 AWG
6.5N•m
Model UPS Ukuran Kabel (kabel THHW ing 75 ° C)
Input AC Output AC Netral Grounding Lug
Gauge Torsi Gauge Torsi Gauge Torsi Gauge Torsi
S3MT- 60KWR480V Transformer input
50mm2
Maks.
50mm2x2
25N•m 50mm2x2
Maks.
50mm2x2
25N•m 70mm2x2
Maks.
70mm2x2
25N•m 50mm2
Maks.
50mm2x2
25 N M8
Trafo output
50mm2
Maks.
50mm2x2
25N•m 50mm2x2
Maks.
50mm2x2
25N•m 70mm2x2
Maks.
70mm2x2
25 N 50mm2
Maks. 50
mm2x2
25 N M8

Diagram Jalur Sambungan Input lan Output Transformer-to-UPS
Sambungan kapacak ing ngisor iki kanggo kabinèt karo trafo isolator input dibangun ing, autotransformer output, lan breaker karo trip lan fault LED.TRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - tokoh 13

Multiple Transformer Sambungan

WARNING:
Transformator input (T-in) output netral ora kaiket ing lemah sasis. Mangga nyedhiyakake sarana kanggo nyambungake lemah sasis trafo menyang netral output trafo.
Cathetan: Tanah sasis trafo kudu disambungake menyang lemah bumi.
PENTING: Sampeyan bisa view lan / utawa download manual iki saka tripplite.com websitus kanggo view sambungan kabel ing warna.

Sambungan S3MT-30KWR480V kanggo Sistem UPS 20kVA nganti 30kVA 208V
Cathetan: Trafo iki ora kompatibel karo model UPS SUT20K lan SUT30K. TRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - tokoh 14

Kabinet Transformer Kab
Cathetan: Input trafo yaiku Delta 3-Wire (3Ph + Ground) lan trafo output yaiku Wye 4-Wire (3Ph + N + Ground).

Sambungan S3MT-60KWR480V kanggo Sistem UPS 50kVA utawa 60kVA
Cathetan: Trafo iki ora kompatibel karo model UPS SUT40K lan SUT60K.

WARNING:
Transformator input (T-in) output netral ora kaiket ing lemah sasis. Mangga nyedhiyakake sarana kanggo nyambungake lemah sasis trafo menyang netral output trafo.
Cathetan: Tanah sasis trafo kudu disambungake menyang lemah bumi.
PENTING: Sampeyan bisa view lan / utawa download manual iki saka tripplite.com websitus kanggo view sambungan kabel ing warna.TRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - tokoh 15

Kabinet Transformer Kab
Cathetan: Input trafo yaiku Delta 3-Wire (3Ph + Ground) lan trafo output yaiku Wye 4-Wire (3Ph + N + Ground).

Operasi

Swara-Suhu Proteksi
Peringatan Lampu LED Suhu Suhu Tinggi (Abang)
Trafo kalebu loro lampu LED peringatan ing sisih ndhuwur panel ngarep: siji lampu kanggo trafo input lan siji lampu kanggo trafo output. Lampu peringatan sing cocog bakal diuripake nalika sisih sekunder input (T-in) utawa nalika sisih utama trafo output (T-out) tekan suhu 160 ° C ± 5 ° C, yaiku sawetara 155 °C nganti 165°C (311°F nganti 329°F). Lampu peringatan mati nalika trafo adhem nganti suhu 125°C ± 5°C, yaiku kisaran 120°C nganti 130°C (248°F nganti 266°F).

Relay Perlindhungan Suhu lan Saklar Thermal
Transformer kalebu relay proteksi over-temperatur lan switch termal ing sisih sekunder input (T-in) lan ing sisih utama trafo output (T-out) kanggo nglindhungi trafo saka overheating.

  • Transformer Input (T-in): Yen sisih sekunder trafo input (T-in) tekan suhu 160°C ± 5°C, yaiku kisaran 155°C nganti 165°C (311°F nganti 329°F), lan proteksi suhu sing luwih dhuwur. relay lan ngalih termal bakal ngaktifake lan bakal mbukak breaker ing sisih secondary trafo. Sawise suhu trafo wis adhem nganti 125°C ± 5°C, yaiku kisaran 120°C nganti 130°C (248°F nganti 266°F), lampu LED peringatan bakal dipateni, lan sampeyan bisa ngaktifake maneh kanthi manual ( nutup) breaker output ing trafo kanggo miwiti maneh operasi normal.
  • Transformers Output (T-out): Yen sisih utami trafo output (T-out) tekan suhu 160°C ± 5°C, yaiku kisaran 155°C nganti 165°C (311°F nganti 329°F), lan proteksi suhu dhuwur. relay lan ngalih termal bakal ngaktifake lan bakal mbukak breaker ing sisih utami trafo. Sawise suhu trafo wis adhem nganti 125°C ± 5°C, yaiku kisaran 120°C nganti 130°C (248°F nganti 266°F), lampu LED bebaya bakal dipateni, lan sampeyan bisa maneh kanthi manual. -aktif (nutup) mbobol input ing trafo kanggo miwiti maneh operasi normal.

Spesifikasi

Model S3MT-30KWR480V S3MT-60KWR480V
Katrangan Loro Transformator 30kW ing siji Kabinet:
Transformator Isolasi Input (T-In)
480V Input (Delta) kanggo 208V Output
(Wye) Transformer, lan Output Auto
Transformator (T-Out) 208V (Wye) Input
kanggo 480V (Wye) output
Loro Transformator 60kW ing siji Kabinet:
Input IsolasiTransformer (T-In)
480V Input (Delta) kanggo 208V Output
(Wye) Transformer, lan Output Auto
Transformator (T-Out) 208V (Wye) Input
kanggo 480V (Wye) output
KVA/kW Ratings kanggo Input (T ing) lan Output (T-metu) Transformers 30 kVA/30 kW 60 kVA/30 kW
Jinis Transformer Jinis garing
SPESIFIKASI INPUT saka loro TRANSFORMERS
Transformator Input (T-In) T-in Input Voltage 480V 480V
T-in Input Voltage Range -45% + 25%) kanggo 40 % mbukak
(-20%+25%) kanggo 100 % mbukak
(-45%+25%) kanggo 40 % mbukak
(-20%+25%) kanggo 100 % mbukak
Input T-in Amp(s) 51A 101A
T-in Input Nomer Fase 3PH 3 HCP
Sambungan Input T-in 3-Kawat (L1, L2, L3 + PE) 3-Kawat (L1, L2, L3 + PE)
Konfigurasi Input AC T-in Delta Delta
Tipe Sambungan T-in !put Tembaga Bar Tembaga Bar
T-in AC Frekuensi Input 50/60 50/60
T-in Range Frekuensi 40/70 Hz 40/70 Hz
T-in Voltage Pemilihan N/A WA
Voltage Drop Ratio: Output tanpa beban kanggo output kanthi Full Load 3%
Isolasi Input T-In ya wis
T-in Input Inrush Saiki d010A (10 ms) Aku 920A (10 ms)
Transformator Output (T-Out) T-metu Input Voltage Range (-45%+25%) kanggo beban 40% (-20%+25%) kanggo beban 100%
T-metu Input Voltage 208V
Input T-metu Amp(s) 87A 173A
T-metu No Fase 3PH 3PH
Sambungan Input T-out 4-Kawat (L1, L2 L3 + N + PE)
Konfigurasi Input AC T-out WYE
Tipe sambungan Input T-out Tembaga Bar Tembaga Bar
Frekuensi Input AC T-out 50/60 50/60
Rentang Frekuensi T-metu 40/70 Hz 40-70 Hz
T-metu Voltage Pemilihan N/A WA
Isolasi Input T-out Ora
T-metu Input Inrush Saiki 1010A (10 ms) 2020A (10 ms)
Model S3MT-30KWR480V S3MT-60KWR480V
Isolasi Input T-out
Transformator Input (T-In) T-in AC Output Voltage (V) 208V 208V
Output AC T-in Amps 113A 225A
T-in Output No Fase 3PH 3PH
Sambungan Output T-in 4-Kawat (L1, L2, L3 + N + PE)
Konfigurasi Output AC T-in Me Me
Tipe Sambungan T-in Tembaga Bar Tembaga Bar
T-in Output Breaker Rating 125A 250A
Transformator Output (T-Out) Output AC T-out Amps 36A 72A
Output T-metu No Fase 3PH 3PH
Sambungan Output T-Out 4-Kawat (L1, L2, L3 + N + PE)
Konfigurasi Output AC T-out Me Me
Tipe Sambungan T-out Tembaga Bar Tembaga Bar
T-in Output Breaker Rating 125A 250A
Operasi
Peringatan Lampu LED Suhu Suhu Tinggi (Abang) AKTIF ing 160°C±-5°C (155°C/311°F nganti 165°C/329°F) lan
mateni ing 125°C ±5°C (120°C/248°F nganti 130°C/266°F)
Piranti Reset Proteksi Over-Suhu T-in: Transfomer Input
• Output Transfomer/sekunder bakal OFF (Breaker mbukak) ing 160°C ±5°C (155°C/311°F nganti 165°C/329°F).
•Sampeyan bisa ngaktifake (nutup) pemutus output kanthi manual nalika Lampu LED dipateni.
•Lampu peringatan bakal dipateni ing suhu 125°C ±5°C (120°C/248°F nganti 130°C/266°F), ing wektu iku sampeyan bisa nutup pemutus kanthi manual kanggo miwiti maneh operasi.
T-metu: Output Transformer
•Input transformator/utama bakal OFF (Breaker mbukak) ing suhu 160°C ±5°C (155°C/311°F nganti 165°C/329°F).
•Sampeyan bisa ngaktifake (nutup) pemutus input kanthi manual nalika lampu LED dipateni.
•Lampu LED Warning bakal dipateni ing suhu 125°C ±5°C (120°C/248°F nganti 130°C/266°F), nalika sampeyan bisa nutup pemutus kanthi manual kanggo miwiti maneh operasi.
Kelas Isolasi 180°C
Munggah Suhu 125°C
T-in Efficiency @ Full Load 95% 97%
T-in Efficiency @ Setengah Load 98% 98%
T-metu Efficiency @ Full Load 95% 97%
T-metu Efficiency @ Setengah Load 98% 98%
Model S3MT-30KWR480V Aku S3MT-60KWR480V
Informasi Fisik
Dhuwur Unit (Inci/cm) 63/160
Jembar Unit (Inci/cm) 23.6/60
Ambane Unit (Inci/cm) 33.5/85.1
Bobot Unit (Lbs./Kg) 961/436 1398/634
Ngunggahake Lantai 855 kg/m2 1243 kg/m2
Unit Karton Dhuwur (Inci/cm) 70.9/180.1
Jembar Karton Unit (Inci/cm) 27.6/70.1
Ambane Karton Unit (Inci/cm) 37.8/96
Bobot Karton Unit (Lbs./Kg) 1058/479.9 1510/684.9
Label Tip-n-Tell Dibutuhake (Y/N) ya wis
Audible Noise (ENG) Maks. 65dB
RH Kelembapan, Non-Kondensasi 95%
Disipasi Termal Online kanthi Muatan Penuh, (Btu/Hr) 9829 7167
Suhu Panyimpenan (ENG) -15 - 60C
Suhu Operasi (ENG) 0°C — 40°C
Elevasi Operasi <1000 meter kanggo daya nominal (luwih saka 100 m,
daya de-rating 1% saben 100 m)
Mekanik
Transformer Winding alumunium
Bahan Kabinet Kab Baja Galvanis Gulung Dingin (SGCC)
Warna Kabinet RAL 9011
Kipas Angin (Jenis / Jumlah) 4 x Ball Bearing,
120 mm (576 total CFM)
8 x Ball Bearing,
120 mm (1152 total CFM)
linuwih
Getaran ISTA-3B
Kejut ISTA-3B
Nyelehake ISTA-3B (Tip Test)
Persetujuan Agensi
Agensi sing nyetujoni cTUVs
Diuji Standar Badan UL 1778 5th Edition
Persetujuan Kanada CSA 22.2-107.3-14
Persetujuan CE N/A
Persetujuan EMI N/A
RoHS/REACH ya wis

Panyimpenan

Sadurunge nyimpen trafo isolasi, priksa manawa kabeh sambungan wis pedhot lan kabeh pemutus dipateni.
Ganti kabeh tutup akses input utawa output supaya ora ngrusak kontak.
Transformer kudu disimpen ing lingkungan sing resik lan aman kanthi suhu antara 5 ° F nganti 140 ° F (-15 ° C nganti 60 ° C) lan asor relatif kurang saka 90% (ora kondensasi).
Simpen trafo ing wadhah pengiriman asli, yen bisa.
WARNING: Trafo (s) iku abot banget. Sadurunge nyimpen trafo, priksa manawa sampeyan kudu nggatekake syarat beban lantai (kg / m²) sing kadhaptar ing bagean 5. Spesifikasi ing "Info Fisik" kanggo nyimpen kanthi aman.

Warranty lan Kepatuhan Regulasi

Warranty winates
Penjual njamin prodhuk iki, yen digunakake miturut kabeh instruksi sing ditrapake, bebas saka cacat asli ing materi lan workmanship sajrone 2 taun wiwit tanggal tuku awal. Yen prodhuk kudu mbuktekaken risak ing materi utawa workmanship ing wektu sing, Bakul bakal ndandani utawa ngganti produk, ing sawijine discretion. Layanan ing Garansi iki mung kalebu bagean. Pelanggan internasional kudu ngubungi dhukungan Tripp Lite ing intlservice@tripplite.com. Pelanggan Continental USA kudu ngubungi Layanan Pelanggan Tripp Lite ing 773-869-1234 utawa ngunjungi tripplite.com/support/help JAMINAN IKI Ora ditrapake kanggo nyandhang normal utawa ngrusak asil saka kacilakan, nyalahi panggunaan, penyalahgunaan utawa nguciwakake. SELLER ora menehi JAMINAN EXPRESS LAIN JAMINAN sing ditulis kanthi nyata ing kene. Kajaba nganti larang dening hukum ditrapake, ALL JAMINAN diwenehake, kalebu ALL JAMINAN MERCHANTABILITY UTAWA FITNESS, diwatesi ing DURATION TO THE JAMINAN JAMINAN ndhuwur; LAN JAMINAN IKI SING TATA-KATA SING KALIAN KERUSAKAN INSIDENTAL LAN KONSEQUENTIAL. (Sawetara negara ora ngidini watesan babagan suwene garansi sing diwenehake, lan sawetara negara ora ngidini pengecualian utawa watesan kerusakan insidental utawa konsekuensial, mula watesan utawa pengecualian ing ndhuwur bisa uga ora ditrapake kanggo sampeyan. Jaminan iki menehi hak legal tartamtu. , lan sampeyan bisa uga duwe hak liyane, sing beda-beda saka yurisdiksi menyang yurisdiksi.)
Tripp Lite; 1111 W. dalan 35th; Chicago IL 60609; USA
WARNING: Pangguna individu kudu ati-ati kanggo nemtokake sadurunge nggunakake apa piranti iki cocok, cukup utawa aman kanggo panggunaan sing dimaksud. Amarga aplikasi individu tundhuk variasi gedhe, pabrikan ora menehi perwakilan utawa garansi babagan kesesuaian utawa kesesuaian piranti kasebut kanggo aplikasi tartamtu.

Registrasi produk
Dolan maring tripplite.com/warranty dina iki kanggo ndhaftar produk Tripp Lite anyar. Sampeyan bakal kanthi otomatis mlebu menyang gambar kanggo kasempatan menang produk Tripp Lite GRATIS!*
* Ora perlu tuku. Void ngendi dilarang. Sawetara watesan ditrapake. Ndeleng ing websitus kanggo rincian.

Informasi Kepatuhan WEEE kanggo Pelanggan lan Daur Ulang Tripp Lite (Uni Eropa)
Haier HWO60S4LMB2 Oven Tembok 60cm - lambang 11Miturut Peraturan Limbah Listrik lan Elektronik (WEEE), nalika pelanggan tuku peralatan listrik lan elektronik anyar saka Tripp Lite, dheweke duwe hak:

  • Kirimi peralatan lawas kanggo daur ulang kanthi basis siji-kanggo-siji, kaya-kanggo-kaya (iki beda-beda gumantung saka negara)
  • Kirimi peralatan anyar maneh kanggo daur ulang nalika pungkasane dadi sampah

Panggunaan peralatan iki ing aplikasi dhukungan urip ing endi kegagalan peralatan iki bisa uga bisa nyebabake kegagalan peralatan dhukungan urip utawa mengaruhi safety utawa efektifitase ora dianjurake.
Tripp Lite duwe kabijakan perbaikan terus-terusan. Spesifikasi bisa diganti tanpa kabar. Foto lan ilustrasi bisa uga rada beda karo produk nyata.

TRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - logoTRIPP LITE S3MT 60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers - warramty1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support

Dokumen / Sumber Daya

TRIPP-LITE S3MT-60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers [pdf] Manual Pamilik
S3MT-30KWR480V, S3MT-60KWR480V, S3MT-60KWR480V S3MT-Seri 3-Phase Input lan Output Transformers, S3MT-60KWR480V, S3MT-Seri 3-Phase Input lan Output Transformers

Referensi

Ninggalake komentar

Alamat email sampeyan ora bakal diterbitake. Kolom sing dibutuhake ditandhani *