Altronix AL1024NKA8 lan AL1024NKA8D nyebarake lan ngalih daya kanggo ngakses sistem kontrol lan aksesoris. Dheweke ngowahi input 115VAC 60Hz dadi wolung (8) output sing dilindhungi 12VDC utawa 24VDC sing dikontrol kanthi mandiri. Desain input dual Akses Power Controller ngidini daya setir saka loro (2) pabrik-diinstal vol kurang independentage 12 utawa 24VDC Altronix daya Penyetor kanggo wolung (8) sekring kontrol independen (AL1024NKA8) utawa PTC (AL1024NKA8D) output dilindhungi. Output daya bisa diowahi dadi kontak "C" garing. Output diaktifake dening sink kolektor mbukak, biasane mbukak (NO), biasane ditutup (NC) input pemicu garing, utawa output udan saka Sistem Kontrol Akses, Card Reader, Keypad, Push Button, PIR, etc. AL1024NKA8(D) bakal daya rute kanggo macem-macem piranti hardware kontrol akses kalebu Mag Locks, Electric Strikes, Magnetik Door Holders, etc Output bakal operate ing loro mode Gagal-Aman lan / utawa Gagal-Aman. Antarmuka FACP mbisakake Egress Darurat, Pemantauan Alarm, utawa bisa digunakake kanggo micu piranti tambahan liyane. Fitur pedhot weker geni bisa dipilih kanthi individu kanggo saben utawa kabeh wolung (8) output. Konektor spade ngijini sampeyan kanggo daya chain daisy kanggo sawetara ACMS8 (CB) modul. Fitur iki ngidini sampeyan nyebarake daya liwat output liyane kanggo sistem sing luwih gedhe.
Spesifikasi Stand-by (arus total ditampilake)
Output | 15 min. saka Stand-by lan 5 min. saka Weker | 4 jam. saka Stand-by lan 5 min. saka Weker | 24 jam. saka Stand-by
lan 5 min. saka Weker |
60 jam. saka Stand-by
lan 5 min. saka Weker |
24VDC/12AH
Baterei |
Stand-By = 8A Weker = 10A | Stand-By = 1.5A Weker = 10A | Stand-By = 200mA Weker = 10A | Stand-By = 100mA Weker = 10A |
Output | 15 min. saka Stand-by lan 5 min. saka Weker | 4 jam. saka Stand-by lan 5 min. saka Weker | 24 jam. saka Stand-by lan 15 min. saka Weker | 60 jam. saka Stand-by lan 15 min. saka Weker |
24VDC/65AH
Baterei |
– | Stand-By = 8.0A Weker = 10A | Stand-By = 1.5A Weker = 10A | Stand-By = 500mA Weker = 10A |
Kanggo aplikasi Kontrol Akses, kapasitas baterei kanggo arus suplai 10A - 1 jam. kanggo baterei 24VDC / 12AH, 6.5 hrs. kanggo baterei 24VDC / 65AH. Deleng lembar kerja pitungan ukuran baterei ing ngisor iki kanggo baterei liyane.
- A. AL1024NKA8(D) konsumsi arus internal (stand-by) ________________ 0.05 A
- B. Konsumsi arus beban (stand-by) ________________ A
- C. Wektu siyaga dibutuhake (jam) ________________ H
- D. Kapasitas baterei dibutuhake kanggo siyaga (A+B)*C ________________ AH
- E. AL1024NKA8(D) konsumsi daya internal (Alarm) ________________ 0.05 A
- F. Konsumsi arus beban (Alarm) ________________ A
- G. Durasi weker (Jam; 15 Min. = 0.25 Jam) (Weker) ________________ H
- H. Kapasitas baterei dibutuhake kanggo Weker (E+F)*G ________________ AH
- I. Total kapasitas baterei sing diwilang D+H ________________ AH
- J. Kapasitas baterei dibutuhake I*1.8 (faktor safety) ________________ AH
Cathetan: Sumber daya AL1024NKA8(D) dirancang kanggo nggarap baterei nganti 65AH. Wigati dicathet: baris [I] ora kudu ngluwihi 36AH.
Sampeyan kudu nyuda konsumsi saiki utawa wektu siyaga supaya bisa tundhuk karo syarat. Kanggo nemtokake ukuran baterei nyata, mangga garis bunder [J] menyang ukuran baterei standar sing paling cedhak (contone 3.5 AH = 4.0 AH).
Spesifikasi
Input:
- AL1024ULXB2:
- 115VAC, 60Hz, 4.2A.
- ACMS8/ACMS8CB:
- Wolung (8) input pemicu:
- a) Biasane mbukak input (NO) (kontak garing).
- b) Input Normally Close (NC) (kontak kering).
- c) Bukak input sink kolektor.
- d) Input Wet (5VDC - 24VDC) kanthi resistor 10K
- e) Sembarang kombinasi saka ndhuwur.
- Wolung (8) input pemicu:
Output:
- daya:
- 12VDC utawa 5VDC nganti 6A, 24VDC nganti 10A (daya total 240W).
- Overvoltage pangayoman.
- ACMS8:
- Output sing dilindhungi sekring dirating @ 2.5A saben output, ora winates daya. Total output 6A maks. Aja ngluwihi rating sumber daya individu.
- ACMS8CB:
- Output sing dilindhungi PTC dirating @ 2A saben output, Kelas 2 winates daya. Total output 6A maks. Aja ngluwihi rating sumber daya individu.
- Wolung (8) output sing bisa dikontrol kanthi mandiri utawa wolung (8) output relay Formulir "C" sing dikontrol kanthi mandiri (pirsani ing ngisor iki kanggo rating):
- a) Output daya Gagal-Aman lan/utawa Gagal-Aman.
- b) Formulir "C" relay dirating @ 2.5A. 12, 24VDC, 0.6 Faktor Daya (ACMS8 mung).
- c) Output daya tambahan (unswitched).
- d) Sembarang kombinasi saka ndhuwur.
- Output individu bisa disetel menyang posisi OFF kanggo servis (jumper output disetel menyang posisi tengah). Ora ditrapake kanggo aplikasi Kontak Kering.
- Sembarang saka wolung (8) output daya sekring/dilindungi PTC bisa dipilih kanggo ngetutake daya Input 1 utawa Input 2. Output voltage saben output padha karo vol inputtage saka input sing dipilih.
- Penindasan mundhak.
Fuse/PTC Rating:
- AL1024ULXB2:
- Sekring input dirating 5A / 250V.
- Sekring baterei 15A/32V.
- ACMS8:
- Sekring input utama dirating 15A/32V.
- Sekring output dirating 3A / 32V.
- ACMS8CB:
- Input utama PTC dirating 9A.
- Output PTC dirating 2A.
Gawe serep baterei:
- Pangisi daya internal kanggo batere asam timbal utawa gel sing ditutup.
- Ganti otomatis batere siyap nalika AC gagal.
- Pangisian daya maksimum saiki 3.6A.
- Zero voltage drop nalika ngalih menyang serep baterei.
Pengawasan:
- Pengawasan gagal AC (bentuk kontak "C").
- Pengawasan baterei sithik (kontak "C").
- Pengawasan ngarsane baterei (kontak wangun "C").
Putus Alarm Kebakaran:
- Pedhot Alarm Kebakaran (latching utawa non-latching) bisa dipilih kanthi individu kanggo kabeh utawa wolung (8) output. Opsi input pedhot Alarm Kebakaran:
- a) Biasane mbukak [NO] utawa biasane ditutup [NC] input kontak garing. Input pembalikan polaritas saka sirkuit sinyal FACP.
- Input FACP WET dirating 5-30VDC 7mA.
- FACP input EOL mbutuhake 10K end of line resistor.
- Relay output FACP [NC]:
Salah siji Garing 1A / 28VDC, 0.6 Power Factor utawa 10K resistance karo [EOL JMP] utuh.
Indikator Visual:
- AL1024ULXB2:
- LED AC Hijau: Nuduhake 115VAC saiki.
- Red DC LED: Nuduhake output DC.
- ACMS8(CB):
- LED abang: Nuduhake output sing dipicu.
- LED Biru: Nuduhake pedhot FACP dipicu.
- Individu Voltage LED: Nuduhake 12VDC (Ijo) utawa 24VDC (Abang).
lingkungan:
- Suhu operasi: 0ºC nganti 49ºC lingkungan.
- Kelembapan: 20 nganti 85%, non-kondensasi.
Ukuran Enclosure (kira-kira H x W x D): 15.5" x 12" x 4.5" (393.7mm x 304.8mm x 114.3mm).
Pandhuan Instalasi
Cara kabel kudu sesuai karo Kode Listrik Nasional / NFPA 70 / NFPA 72 / ANSI, Kode Listrik Kanada lan kabeh kode lan panguwasa lokal sing duwe yurisdiksi. Produk dimaksudake mung kanggo panggunaan njero ruangan.
- Pasang unit ing lokasi sing dikarepake. Tandhani lan predrill bolongan ing tembok kanggo baris munggah karo loro keyholes ndhuwur ing pager. Pasang rong fasteners ndhuwur lan ngawut-awut ing tembok karo kepala meneng protruding. Selehake bolongan tombol ndhuwur pager ing rong sekrup ndhuwur, tingkat lan aman. Tandhani posisi rong bolongan ngisor. Copot pager. Pengeboran bolongan ngisor lan pasang rong pengikat. Selehake bolongan tombol ndhuwur pager ing rong sekrup ndhuwur. Pasang loro ngawut-awut ngisor lan priksa manawa kanggo ngencengi kabeh ngawut-awut (Dimensi Enclosure, pg. 12). Kandang aman ing lemah bumi.
- Priksa manawa kabeh jumper output [PWR1] - [PWR8] diselehake ing posisi OFF (tengah) (Fig. 1, pg. 3).
- Sambungake daya AC unswitched (115VAC 60Hz) kanggo terminal ditandhani [L, N] (Fig. 4a, pg. 5). LED "AC" ijo ing papan sumber daya bakal urip. Cahya iki bisa dideleng liwat lensa LED ing lawang pager. Gunakake 14 AWG utawa luwih gedhe kanggo kabeh sambungan daya. Kabel ijo sing aman timbal menyang lemah. Tetep kabel winates daya kapisah saka kabel non daya winates (115VAC 60Hz Input, Kabel Baterei). Jarak minimal 0.25" kudu diwenehake.
AWAS: Aja ndemek bagean logam sing katon. Mateni daya sirkuit cabang sadurunge nginstal utawa nglayani peralatan. Ora ana bagean sing bisa digunakake pangguna ing njero. Rujuk instalasi lan servis menyang personel layanan sing mumpuni. - Setel saben output [OUT1] – [OUT8] kanggo daya rute saka Input 1 utawa 2 (Fig. 1, pg. 3).
Cathetan: Ukur output voltage sadurunge nyambungake piranti. Iki mbantu nyegah karusakan potensial. - Pateni daya sadurunge nyambungake piranti.
- Opsi output: AL1024NKA8(D) bakal nyedhiyakake nganti wolung (8) output daya sing diuripake utawa wolung (8) output "C" sing garing, utawa kombinasi apa wae saka output daya sing diuripake lan output "C", ditambah wolung (8) sing ora ngalih. output daya tambahan.
- Output Daya Ngalih:
Sambungake input negatif (-) piranti sing didhukung menyang terminal sing ditandhani [COM].- Kanggo operasi Gagal-Aman, sambungake input positif (+) piranti sing didhukung menyang terminal sing ditandhani [NC].
- Kanggo operasi Fail-Secure, sambungake input positif (+) piranti sing didhukung menyang terminal sing ditandhani [NO].
- Formulir "C" output:
Nalika wangun "C" output dikarepake, jumper cocog (1-8) kudu diselehake ing posisi OFF (Fig. 7, pg. 9). Utawa, sekring output sing cocog (1-8) bisa dicopot (mung AL1024NKA8). Sambungake negatif (-) saka sumber daya langsung menyang piranti ngunci. Sambungake positif (+) catu daya menyang terminal sing ditandhani [C].- Kanggo operasi Gagal-Aman, sambungake positif (+) piranti sing didhukung menyang terminal sing ditandhani [NC].
- Kanggo operasi Fail-Secure sambungake positif (+) piranti sing didhukung menyang terminal sing ditandhani [NO]. Kontak kering rating @ 2.5A, 28VDC.
- Output Daya Tambahan (ora ngalih):
Sambungake input positif (+) piranti sing didhukung menyang terminal sing ditandhani [C] lan negatif (-) saka piranti sing didhukung menyang terminal sing ditandhani [COM]. Output bisa digunakake kanggo nyedhiyani daya kanggo maca kertu, keypads etc.
- Output Daya Ngalih:
- Uripake daya utama sawise kabeh piranti disambungake.
- Pilihan pemicu input:
Cathetan: Yen pedhot Fire Alarm ora digunakake, sambungake resistor 10K ohm menyang terminal sing ditandhani [GND lan EOL], plus sambungake jumper menyang terminal sing ditandhani [GND, RST].
Input Normally Open (NO):
Geser logika kontrol input DIP ngalih menyang posisi OFF kanggo [Ngalih 1-8] (Fig. 2, ing sisih tengen). Sambungake kabel menyang terminal sing ditandhani [+ INP1 –] menyang [+ INP8 –].
Input Biasane Ditutup (NC):
Geser input logika kontrol DIP ngalih menyang posisi ON kanggo [Ngalih 1-8] (Fig. 2, ing sisih tengen). Sambungake kabel menyang terminal sing ditandhani [+ INP1 –] menyang [+ INP8 –].
Bukak Kolektor Sink Input:
Sambungake input sink kolektor mbukak menyang terminal sing ditandhani [+ INP1 -] menyang [+ INP8 -].
Wetan (Voltage) Konfigurasi Input:
Kasebut kanthi teliti, mirsani polaritas, sambungake voltagkabel pemicu input lan resistor 10K sing diwenehake menyang terminal sing ditandhani [+ INP1 –] kanggo [+ INP8 –].
Yen nglamar voltage kanggo pemicu input - nyetel saklar INP Logic sing cocog menyang posisi "OFF".
Yen njabut voltage kanggo pemicu input - nyetel saklar INP Logic sing cocog menyang posisi "ON". - Pilihan Antarmuka Alarm Kebakaran:
Input [NC] sing biasane ditutup, biasane mbukak [NO] utawa input pembalikan polaritas saka sirkuit sinyal FACP bakal micu output sing dipilih. Kanggo ngaktifake FACP Disconnect kanggo output nguripake tombol DIP sing cocog [SW1-SW8]. Kanggo mateni FACP pedhot kanggo output nguripake saklar DIP cocog [SW1-SW8] OFF. Ngalih dumunung langsung ing sisih kiwa Terminal Antarmuka Alarm Kebakaran.
Biasane mbukak Input:
Sambungake relay FACP lan resistor 10K kanthi paralel ing terminal sing ditandhani [GND] lan [EOL].
Input Biasane Ditutup:
Sambungake relay FACP lan resistor 10K kanthi seri ing terminal sing ditandhani [GND] lan [EOL].
Pemicu Input Sirkuit Sinyal FACP:
Sambungake positif (+) lan negatif (-) saka output sirkuit sinyal FACP menyang terminal sing ditandhani [+ FACP –]. Sambungake FACP EOL menyang terminal sing ditandhani [+ RET –] (polaritas dirujuk ing kondisi weker).
Putus Alarm Kebakaran Non-Latching: Sambungake jumper menyang terminal sing ditandhani [GND, RST]. - FACP Kering NC output:
Sambungake piranti sing dipengini supaya dipicu dening output kontak garing unit menyang terminal ditandhani [NC] lan [C]. Nalika [EOL JMP] katahan utuh, output saka 0 Ohm resistance ing kondisi normal. Nalika [EOL JMP] dipotong, resistensi 10k bakal diterusake menyang piranti sabanjure nalika kondisi normal. - Sambungan Baterei Stand-by (Gbr. 6, pg. 8):
Kanggo aplikasi Kontrol Akses AS, baterei opsional. Baterei dibutuhake kanggo instalasi Kanada (ULC-S319). Nalika baterei ora digunakake, mundhut saka AC bakal kasil mundhut saka output voltage. Nalika nggunakake baterei stand-by dikarepake, padha kudu asam timbal utawa jinis gel. Sambungake baterei menyang terminal sing ditandhani [– BAT +] (Gbr. 4g, pg. 6). Gunakake rong (2) baterei 12VDC disambungake ing seri kanggo operasi 24VDC (baterei ndadékaké klebu). Gunakake baterei - baterei Casil CL1270 (12V / 7AH), CL12120 (12V / 12AH), CL12400 (12V / 40AH), CL12650 (12V / 65AH) utawa baterei BAZR2 lan BAZR8 sing diakoni UL kanthi rating sing cocog. - Output Pengawasan Baterei lan AC (Gbr. 4, pg. 8):
Sambungake piranti notifikasi sinyal sing cocog menyang terminal sing ditandhani [AC FAIL & BAT FAIL] (Fig. 4b, pg. 5) output relay pengawas. Gunakake 22 AWG nganti 18 AWG kanggo laporan AC Gagal & Kurang/Ora Ana Baterei. - Kanggo tundha nglaporake nganti 6 jam, Cut jumper "Tundha AC" lan ngreset daya menyang unit (Fig. 4f, pg. 6).
- Pedhot Alarm Kebakaran (Gbr. 4c, pg. 6):
- Kanggo ngaktifake Fire Alarm Disconnect, atur switch DIP [Shutdown] menyang posisi ON.
- Kanggo mateni Alarm Kebakaran Pedhot setel saklar DIP [Shutdown] menyang posisi OFF.
- Pemasangan tamper ngalih:
Gunung UL Listed tampngalih er (model Altronix TS112 utawa padha) ing ndhuwur pager. Geser tamper ngalih krenjang menyang pojok pager kira-kira 2 "saka sisih tengen (Fig. 6a, pg. 8). Nyambung tampngalih kabel menyang input Panel Kontrol Akses utawa piranti laporan UL Listed sing cocog. Kanggo ngaktifake sinyal weker mbukak lawang pager.
Pangopènan
Unit kudu dites paling ora sepisan taun kanggo operasi sing tepat kaya ing ngisor iki:
- Output Voltage Tes: Ing kondisi mbukak normal, DC output voltage kudu dipriksa kanggo vol sing tepattagtingkat e.
- Test baterei: Ing kahanan mbukak normal mriksa yen baterei wis kebak, mriksa kasebut voltage loro ing terminal baterei lan ing terminal Papan ditandhani [- BAT +] kanggo mesthekake yen ana break ing kabel sambungan baterei.
Cathetan: Arus pangisian daya maksimal ing discharge yaiku 3.6A.
Cathetan: Umur baterei sing dikarepake yaiku 5 taun; Nanging, dianjurake ngganti baterei ing 4 taun utawa kurang yen perlu
Gambar 4 - Konfigurasi Papan AL1024ULXB2
Diagnostik LED
AL1024ULXB2 - Papan Sumber Daya
Abang (DC) | Hijau (AC) | Status Pasokan Daya |
ON | ON | Kondisi operasi normal. |
ON | OFF | Mundhut AC. Baterei stand-by nyedhiyakake daya. |
OFF | ON | Ora ana output DC. |
OFF | OFF | Mundhut AC. Baterei kosong utawa ora ana stand-by. Ora ana output DC. |
ACMS8 lan ACMS8CB Akses Power Controller
LED | ON | OFF |
LED 1- LED 8 (Abang) | Output relay (s) de-energized. | Output relay (s) energized. |
FACP | Input FACP dipicu (kondisi weker). | FACP normal (kondisi non-alarm). |
Output Ijo 1-8 | 12VDC | – |
Output abang 1-8 | 24VDC | – |
Identifikasi Terminal
AL1024ULXB2 - Papan Sumber Daya
Katrangan Terminal | Fungsi/Deskripsi |
L, N | Sambungake 115VAC menyang terminal iki: L kanggo panas, N kanggo netral (Gbr. 4a, pg. 6). |
+ DC - | Pabrik disambungake menyang ACMS8(CB) (Gbr. 4d, pg. 6). |
AC Gagal NC, C, NO |
Digunakake kanggo ngabari mundhut daya AC, egnyambung menyang piranti sing bisa dirungokake utawa panel weker. Relay biasane diuripake nalika daya AC ana. Rating kontak 1A @ 28VDC. AC utawa brownout gagal dilaporake sajrone 1 menit sawise acara.
Kanggo tundha laporan nganti 6 jam, potong jumper "Tundha AC" lan setel daya menyang unit. (Gbr. 4f, pg. 6). |
Bat Gagal NC, C, NO | Digunakake kanggo nuduhake kahanan baterei sithik, contone, nyambung menyang panel weker.
Relay biasane diuripake nalika daya DC ana. Rating kontak 1A @ 28VDC. Baterei sing dicopot dilaporake sajrone 1 menit. Sambungan maneh baterei dilaporake sajrone 1 menit. Batesan baterei sithik: kira-kira 21VDC (Gambar 4b, kaca 6). |
– BAT+ | Sambungan baterei stand-by. Pangisian daya maksimum saiki 3.6A (Gbr. 4c, pg. 6). |
ACMS8 lan ACMS8CB Akses Power Controller
Katrangan Terminal | Fungsi/Deskripsi |
+ PWR1 – | Pabrik disambungake menyang AL1024ULXB2. Aja nggunakake terminal iki. |
+ PWR2 – | Pabrik disambungake menyang VR6 voltage pengatur. Aja nggunakake terminal iki. |
+ INP1 - liwat
+ INP8 - |
Wolung (8) kontrol independen Normally Open (NO), Normally Closed (NC), Open Collector Sink utawa Wet Input Triggers. |
C, NC | FACP Garing NC output dirating 1A / 28VDC @ 0.6 Power Factor. Kelas 2 winates daya. Kanthi EOL JMP utuh, bakal nyedhiyani resistance 10k ing negara normal. |
GND, RST | antarmuka FACP latching utawa non-latching. Ora ana input garing. Kelas 2 winates daya. Disingkat kanggo antarmuka FACP non-latching utawa Latch FACP reset. |
GND, EOL | Terminal Input FACP Diawasi EOL kanggo fungsi FACP pembalikan polaritas. Kelas 2 winates daya. |
– F, + F, – R, + R | Input Sirkuit Sinyal FACP lan terminal Bali. Kelas 2 winates daya. |
Output 1 liwat
Hasil 8 NO, C, NC, COM |
Wolung (8) output kontrol independen sing bisa dipilih [Fail-Safe (NC) utawa Fail-Secure (NO)] lan wolung (8) output Relay Formulir "C" sing dikontrol sacara mandiri. |
Gambar 6 – AL1024NKA8(D)
AWAS: Gunakake rong (2) baterei siyaga 12VDC.
- Tetep kabel winates daya kapisah saka non-daya winates. Gunakake spasi minimal 0.25".
- Baterei sing bisa diisi ulang 12AH minangka baterei paling gedhe sing bisa dipasang ing kurungan iki.
- Enclosure baterei eksternal sing kadhaptar UL kudu digunakake yen nggunakake baterei 40AH utawa 65AH.
Diagram Aplikasi Khas
Diagram Hook-Up
- Fig.. 8 - Daisy-chaining siji utawa luwih ACMS8 (CB) Unit. EOL Jumper [EOL JMP] kudu diinstal ing posisi EOL. Non-Latching.
- Fig.. 9 - Daisy-chaining siji utawa luwih ACMS8 (CB) Unit. EOL Jumper [EOL JMP] kudu diinstal ing posisi EOL. Latching Single Reset.
- Fig.. 10 - Daisy chaining siji utawa luwih ACMS8 (CB) Unit. EOL Jumper [EOL JMP] kudu diinstal ing posisi EOL. Latching Reset Individu.
Diagram Hook-Up
- Fig. 11 - Input pembalikan polaritas saka output sirkuit sinyal FACP (polaritas dirujuk ing kondisi weker). Non-Latching
- Fig. 12 - Input pembalikan polaritas saka output sirkuit sinyal FACP (polaritas dirujuk ing kondisi weker). Ngunci
- Fig. 13 - Input pemicu Biasane Ditutup (Non-Latching).
- Fig. 14 - Input pemicu Biasane Ditutup (Latching).
- Fig. 15 – Input pemicu Biasane Bukak (Non-Latching)
- Fig. 16 - Biasane mbukak input pemicu (Latching).
Ukuran Enclosure (BC400)
15.5" x 12" x 4.5" (393.7mm x 304.8mm x 114.3mm)
Altronix ora tanggung jawab kanggo kesalahan tipografi. 140 58th Street, Brooklyn, New York 11220 USA
- telpon: 718-567-8181
- fax: 718-567-9056
- websitus: www.altronix.com
- e-mail: info@altronix.com
- Garansi seumur hidup
Dokumen / Sumber Daya
![]() |
Altronix AL1024NKA8 Series Dual Output Akses Power Controllers [pdf] Pandhuan Instalasi AL1024NKA8, AL1024NKA8D, AL1024NKA8 Series Dual Output Access Power Controllers, Dual Output Access Power Controllers, Access Power Controllers, Dual Output Power Controllers, Power Controllers |