ACM4 Series UL Listed Sub-Majelis Akses Power Controllers
Guide Instalasi
Model kalebu:
ACM4: - Sekawan (4) Output sing Dilindungi Sekring
ACM4CB: – Papat (4) PTC Protected Output
Swaraview:
Altronix ACM4 lan ACM4CB ngowahi siji (1) 12 kanggo 24 volt AC utawa input DC dadi papat (4) independen kontrol nggabungke utawa PTC output dilindhungi. Output daya iki bisa diowahi dadi kontak "C" garing (mung ACM4). Output diaktifake dening sink kolektor mbukak utawa biasane mbukak (NO) input pemicu garing saka Sistem Kontrol Akses, Card Reader, Keypad, Push Button, PIR, etc. Unit bakal rute daya kanggo macem-macem piranti kontrol akses hardware kalebu Mag Kunci, Serangan Listrik, Pemegang Door Magnetik, lsp. Kabeh piranti sing nyambungake kudu UL Listed. Output bakal digunakake ing mode Gagal-Aman lan/utawa Gagal-Aman. Unit dirancang kanggo powered by siji sumber daya umum kang bakal nyedhiyani daya kanggo loro operasi Papan lan piranti ngunci, utawa loro (2) sumber daya babar blas sawijining, siji (1) nyediakake daya kanggo operasi Papan lan liyane kanggo kunci/aksesori. daya. Antarmuka FACP mbisakake Egress Darurat, Pemantauan Alarm, utawa bisa digunakake kanggo micu piranti tambahan liyane. Fitur pedhot weker geni bisa dipilih kanthi individu kanggo salah siji utawa kabeh saka papat (4) output.
Bagan Referensi Konfigurasi ACM4 lan ACM4CB:
Nomer Model Altronix | Jumlah Output | Output sing dilindhungi sekring | Output sing dilindhungi PTC | Rating Output | Kelas 2 Rated Power-Limited Auto-settable | Listings Agensi |
ACM4 | 4 | 3A | ![]() |
|||
ACM4CB | 4 | 2.5A |
UL Listings lan File Angka:
UL File # BP6714.
UL 294* - UL Dhaptar kanggo Unit Sistem Kontrol Akses.
*ANSI/UL 294 7th Ed. Tingkat Kinerja Kontrol Akses:
Serangan ngrusak - I; Ketahanan - IV; Keamanan Line - I; Daya Stand-by - I. "Peralatan Sinyal" Dievaluasi kanggo Standar CSA C22.2 No.205-M1983
Spesifikasi:
- 12 kanggo 24 volt AC utawa DC operasi (setelan ora dibutuhake).
- Rating Input: 12VDC @ 0.4A utawa 24VDC @ 0.2A.
- Pilihan input daya:
a) Siji (1) input daya umum (papan lan daya kunci).
b) Loro (2) input daya terisolasi (siji (1) kanggo daya papan lan siji (1) kanggo daya kunci/hardware). - Papat (4) input pemicu Sistem Kontrol Akses:
a) Sekawan (4) input normally open (NO).
b) Sekawan (4) input sink kolektor mbukak.
c) Sembarang kombinasi saka ndhuwur. - Papat (4) output sing dikontrol kanthi mandiri:
a) Papat (4) output daya Gagal-Aman lan/utawa Gagal-Aman.
b) Papat (4) wangun garing "C" 5A output relay (mung ACM4).
c) Sembarang kombinasi saka ndhuwur (mung ACM4). - Papat (4) output daya tambahan (unswitched).
- Rating output:
- Sekring dirating 2.5A saben.
- PTC dirating 2A saben. - Sekring utama dirating ing 10A.
Cathetan: Kanggo Model ACM4/ACM4CB deleng Bagan Referensi Konfigurasi ACM4 lan ACM4CB, Pg 2.
Cathetan: Kisaran suhu operasi kudu 0 nganti 49ºC. - LED abang nuduhake output sing dipicu (relay energized).
- Pedhot Alarm Kebakaran (latching utawa non-latching) bisa dipilih kanthi individu kanggo salah siji utawa kabeh saka papat (4) output.
Opsi input pedhot Alarm Kebakaran:
a) Biasane mbukak (NO) utawa biasane ditutup (NC) input kontak garing.
b) Input pembalikan polaritas saka sirkuit sinyal FACP. - Relay output FACP (bentuk kontak "C" dirating @ 1A/28VDC, ora dievaluasi dening UL).
- LED ijo nuduhake yen FACP pedhot dipicu.
- Blok terminal sing bisa dicopot nggampangake instalasi.
Ukuran Papan (L x W x H kira-kira): 5.175" x 3.36" x 1.25" (131.5mm x 85.6mm x 31.8mm).
Instruksi Instalasi:
Cara kabel kudu sesuai karo Kode Listrik Nasional / NFPA 70 / ANSI, lan kabeh kode lan panguwasa lokal sing duwe yurisdiksi. Produk mung digunakake kanggo njero ruangan.
- Waca Instruksi Instalasi Sub Majelis kanggo mounting Rev. MS050913.
Kasebut kanthi teliti manehview: Diagram Aplikasi Khas (kaca 4) Diagnostik LED (kaca 5) Tabel Identifikasi Terminal (kaca 5) Diagram Hook-up (kaca 6) - Input pasokan listrik:
Unit kasebut bisa disedhiyakake karo siji (1) Pasokan Daya Kontrol Akses Terdhaptar sing bakal nyedhiyakake daya kanggo operasi papan lan piranti ngunci utawa loro (2) Pasokan Daya Kontrol Akses Terdhaptar, siji (1) kanggo nyedhiyakake daya kanggo operasi papan. lan liyane kanggo nyedhiyakake daya kanggo piranti ngunci lan/utawa hardware kontrol akses.
Cathetan: Daya input bisa uga 12 nganti 24 volt AC utawa operasi DC.
Rating Input (mung ACM4 / ACM4CB): 12VDC @ 0.4A utawa 24VDC @ 0.2A.
a) Input sumber daya tunggal:
Yen unit lan piranti ngunci arep didayakake nggunakake Pasokan Daya Kontrol Akses Terdhaptar siji, sambungake output (12 nganti 24 volt AC utawa DC) menyang terminal sing ditandhani [– Daya +].
b) Input sumber daya dobel (Gambar 1, pg. 5):
Nalika nggunakake loro Listed Access Control Power Supplies dikarepake, jumper J1 lan J2 (dumunung ing sisih kiwa daya / terminal kontrol) kudu Cut. Sambungake daya kanggo unit menyang terminal sing ditandhani [– Daya +] lan sambungake daya kanggo piranti ngunci menyang terminal sing ditandhani [– Kontrol +].
Cathetan: Nalika nggunakake DC Listed Access Control Power Supplies polaritas kudu diamati.
Nalika nggunakake AC Listed Access Control Power Supplies polaritas ora perlu diamati.
Cathetan: Kanggo kepatuhan UL, sumber daya kudu UL Listed kanggo Sistem Kontrol Akses lan aksesoris. - Pilihan output (Gambar 1, kaca 5):
ACM4 bakal nyedhiyakake papat (4) output daya sing diuripake, papat (4) output "C" sing garing, utawa kombinasi apa wae saka output daya sing diuripake lan output "C", ditambah karo papat (4) output daya tambahan sing ora diuripake. ACM4CB bakal nyedhiyakake papat (4) output daya sing diuripake utawa papat (4) output daya tambahan sing ora diowahi.
a) Output Daya Ngalih:
Sambungake input negatif (-) piranti sing didhukung menyang terminal sing ditandhani [COM]. Kanggo operasi Gagal-Aman, sambungake input positif (+) piranti sing didhukung menyang terminal sing ditandhani [NC]. Kanggo operasi Fail-Secure, sambungake input positif (+) piranti sing didhukung menyang terminal sing ditandhani [NO].
b) Formulir "C" output (ACM4):
Nalika wangun "C" output dikarepake sekring output cocog (1-4) kudu dibusak. Sambungake negatif (-) saka sumber daya langsung menyang piranti ngunci. Sambungake positif (+) catu daya menyang terminal sing ditandhani [C]. Kanggo operasi Gagal-Aman, sambungake positif (+) piranti sing didhukung menyang terminal sing ditandhani [NC]. Kanggo operasi Fail-Secure sambungake positif (+) piranti sing didhukung menyang terminal sing ditandhani [NO].
c) Output Daya Tambahan (unswitched):
Sambungake input positif (+) piranti sing didhukung menyang terminal sing ditandhani [C] lan negatif (-) saka piranti sing didhukung menyang terminal sing ditandhani [COM]. Output bisa digunakake kanggo nyedhiyani daya kanggo maca kertu, keypads etc.
Cathetan: Nalika kabel kanggo output winates daya, gunakake kalah sing kapisah saka sing digunakake kanggo kabel sing ora winates. - Pilihan pemicu input (Gambar 1, kaca 5):
a) Biasane mbukak pemicu input [NO]:
Input 1-4 diaktifake kanthi input sink kolektor sing biasane mbukak utawa mbukak.
Sambungake piranti (maca kertu, papan tombol, njaluk tombol metu, lsp.) menyang terminal sing ditandhani [IN] lan [GND].
b) Input Kolektor Open Sink:
Sambungake panel kontrol akses output kolektor mbukak menyang terminal ditandhani [IN] lan umum (negatif) kanggo terminal ditandhani [GND]. - Pilihan Antarmuka Alarm Kebakaran (Gambar 3 nganti 7, kaca 6 – 7):
Input [NC] sing biasane ditutup, biasane mbukak [NO] utawa input pembalikan polaritas saka sirkuit sinyal FACP bakal micu output sing dipilih. Kanggo ngaktifake FACP Disconnect kanggo output mateni saklar sing cocog [SW1- SW4]. Kanggo mateni FACP pedhot kanggo output nguripake saklar sing cocog [SW1-SW4] ON.
a) Biasane mbukak input [NO]:
Kanggo non-latching hook-up ndeleng Fig. 4, pg. 6. Kanggo latching hook-up ndeleng Fig. 5, pg. 7.
b) Input [NC] Biasane Ditutup:
Kanggo non-latching hook-up ndeleng Fig. 6, pg. 7. Kanggo latching hook-up ndeleng Fig. 7, pg. 7.
c) Pemicu input Sirkuit Sinyal FACP:
Sambungake positif (+) lan negatif (-) saka output sirkuit sinyal FACP menyang terminal sing ditandhani [+ INP –]. Sambungake FACP EOL menyang terminal sing ditandhani [+ RET –] (polaritas dirujuk ing kondisi weker). Jumper J3 kudu Cut (Fig. 3, pg. 6). - Output "C" formulir garing FACP (Gambar 1a, kaca 5):
Sambungake piranti sing dipengini supaya dipicu dening output kontak garing unit menyang terminal sing ditandhani [NO] lan [C] FACP kanggo output biasane mbukak utawa terminal ditandhani [NC] lan [C] FACP kanggo output biasane ditutup. - Pemasangan tamper switch (Ora Klebu):
Gunung UL Listed tampngalih er (Altronix Model TS112 utawa padha) ing ndhuwur pager. Geser tamper ngalih krenjang menyang pojok pager kira-kira 2 "saka sisih tengen.
Nyambung tampngalih kabel menyang input Panel Kontrol Akses Listed utawa piranti pelapor UL Listed sing cocog kanggo ngaktifake sinyal weker nalika lawang pager mbukak.
Pangopènan:
Unit kudu dites paling sethithik sapisan taun kanggo operasi sing tepat. Voltage ing saben output kudu dites kanggo negara pemicu lan non-pemicu lan operasi antarmuka FACP kudu simulasi.
Diagnostik LED:
LED | ON | OFF |
LED 1 – LED 4 (Abang) | Output relay (s) energized. | Output relay (s) de-energized. |
TRG (Ijo) | Input FACP dipicu (kondisi weker). | FACP normal (kondisi non-alarm). |
Tabel Identifikasi Terminal:
Katrangan Terminal | Fungsi/Deskripsi |
- Daya + | 12VDC kanggo 24VDC input saka UL Listed Access Control Power Supply. |
- Kontrol + | Terminal iki bisa disambungake menyang kapisah, UL Listed Access Control Power Supply kanggo nyedhiyani daya operasi terisolasi kanggo ACM4 / ACM4CB (jumpers J1lan J2 kudu dibusak). |
INPUT TRIGGER 1 – INPUT 4 IN, GND | Saka input pemicu sink kolektor sing biasane mbukak lan / utawa mbukak (panyuwunan kanggo metu tombol, metu PIRs, etc.). |
– OUTPUT 1 OUTPUT 4 NC, C, NO, COM | 12 nganti 24 volt AC/DC output kontrol pemicu: Gagal-Aman [NC positif (+) & COM Negatif (—)], Gagal-Aman [NO positif (+) & COM Negatif (—)], Output tambahan [C positif (+) & COM Negatif (—A (Nalika nggunakake AC sumber daya polaritas ora perlu diamati), NC, C, NO dadi wangun "C" 5A 24VACNDC dirating output garing nalika sekring dibusak (ACM4). Kontak sing ditampilake ing negara sing ora dipicu. |
ANTARMUKA FACP T, + INPUT — | Fire Alarm Interface micu input saka FACP. Input pemicu bisa biasane mbukak, biasane ditutup saka sirkuit output FACP (Fig. 3 nganti 7, pg. 6-7). |
ANTARA FACP NC, C, NO | Kontak relay Formulir "C" dirating @ 1A/28VDC kanggo laporan weker. (Output iki durung dievaluasi dening UL). |
Diagram Aplikasi Umum:
Diagram penghubung:
Gambar 2
Pancing opsional nggunakake rong (2) input sumber daya terisolasi:
Gambar 3
Input pembalikan polaritas saka output sirkuit sinyal FACP (polaritas dirujuk ing kondisi weker): (Output iki durung dievaluasi dening UL)
Gambar 4
Biasane Bukak - Input pemicu FACP Non-Latching:
Gambar 5
Biasane Bukak input pemicu FACP Latching kanthi ngreset: (Output iki durung dievaluasi dening UL)
Gambar 6
Biasane Ditutup - Input pemicu FACP Non-Latching:
Gambar 7
Biasane Ditutup - Latching input pemicu FACP kanthi ngreset (Output iki durung dievaluasi dening UL):
Cathetan:
Altronix ora tanggung jawab kanggo kesalahan tipografi.
140 58th Street, Brooklyn, New York 11220 USA
Telpon: 718-567-8181
Fax: 718-567-9056
Websitus: www.altronix.com
E-mail: info@altronix.com
Garansi seumur hidup
IIACM4/ACM4CB
F22U
Dokumen / Sumber Daya
![]() |
Altronix ACM4 Series UL Listed Sub-Majelis Akses Power Controllers [pdf] Pandhuan Instalasi ACM4 Series UL Listed Sub-Akses Pengontrol Daya, ACM4 Series, UL Listed Sub-Akses Akses Kontroler, Assembly Access Power Controllers, Power Controllers |