Product Overview
The JA-110N-DIN is a component of the JABLOTRON system designed to provide a relay for switching PG bus power output. It is suitable for controlling devices such as lighting or ventilation systems. Installation requires a qualified specialist holding a valid certificate issued by an authorized distributor.
Installation
[Warning] Connecting electrical appliances must only be performed by a qualified specialist.
Always disconnect power before connecting the module to the system bus.
- Mount the module on a DIN rail.
- Connect the bus cable to terminals (1).
- Check module operation by pressing button (4). The red RELAY (2) LED will light up when the module is activated.
- Connect the controlled device to the output terminals (5).
Note: If communication is lost, the yellow STATUS (3) LED will indicate this condition, and after 60 seconds, the relay will switch to standby mode.
Figure 1: Product Overview
The diagram illustrates the JA-110N-DIN module with the following labeled components: 1 – Bus terminals; 2 – Red RELAY indicator LED; 3 – Yellow STATUS indicator LED; 4 – Learn/Manual trigger button; 5 – Relay terminals.
System Registration and Settings
To register the module within the system, use the recommended software or application, depending on your control panel type. Refer to the control panel's user manual for specific instructions.
Technical Specifications
Power Source | From the control panel bus 12 V (9–15 V) |
Current Consumption (relay off) | 5 mA |
Max. Current Consumption (relay on) | 45 mA |
Relay Contact Load: (Galvanically and reliably isolated from the bus) | |
Max. AC switching voltage | 250 V AC / 24 V DC |
Resistive load (cos φ = 1) | max. 16 A |
Inductive, capacitive load (cos φ = 0.3) | max. 6 A |
Halogen lighting | max. 1000 W |
DC current | 384 W |
Min. DC switching output | 0.5 W |
Power dissipation | 1.6 W |
Power dissipation for control panel heating | 1.9 W |
Connected Wire Diameter | max. 2 x 1.5 mm²; 1 x 2.5 mm² |
Environment | For indoor use |
Operating Temperature Range | -10 °C to +40 °C |
Average Operating Humidity | 75% relative humidity, non-condensing |
Dimensions | 18 x 90 x 64 mm (according to EN 60715) |
Weight | 65 g |
Certification Body | Trezor Test sro (no. 3025) |
Complies with | EN 50130-4, EN 55032, EN IEC 62368-1, EN IEC 63000 |
Compliance and Contact
JABLOTRON a.s. hereby declares that the JA-110N-DIN complies with the harmonized EU legislation: Directives No. 2014/35/EU, 2014/30/EU, 2011/65/EU, provided it is used as intended. The original Declaration of Conformity is available at www.jablotron.com in the 'Downloads' section.
Environmental Information: Please dispose of this product responsibly to conserve resources and prevent potential negative impacts on human health and the environment that may result from improper waste handling. Return the product to your dealer or contact your local authorities for more information on the nearest collection point.