SUBMITTAL DATA SHEET

4-Way Cassette Heat Pump System

Efficiency

CoolingHeating
SEER221.2HSPF2-4
EER212.0COP
3.43

Performance of Cooling

Cooling (Btu/hr)
Rated Capacity36600
Min/Max Capacity4900~38000
Moisture Removal(L/h)4.30
Standard Operating Range (°F/°C)-22~122 (-30~50)
Conditions:Indoor: 80°F DB/67°F WB
Outdoor: 95°F DB/75°F WB

Performance of Heating

Heating (Btu/hr)
1. @ 47°F Rated37000
1. @ 47°F Min/Max Capacity11400~44600
2. @ 17°F Rated30600
3. @ 5°F Rated: Capacity / COP37000/1.95
3. @ 5°F Max: Capacity37000
Standard Operating Range (°F/°C)-22~75 (-30~24)
1. Conditions:Indoor: 70°F DB/60°F WB
Outdoor: 47°F DB/43°F WB
2. Conditions:Indoor: 70°F DB/60°F WB
Outdoor: 17°F DB/15°F WB
3. ConditionsIndoor: 70°F DB/60°F WB
Outdoor: 5°F DB/5°F WB

Indoor Unit Specifications

Indoor Air Flow (Turbo/H/M/L/Si) (CFM)1041.8 / 947.6 / 853.5 / 753.4 / 659.2
Indoor Noise Level (Turbo/H/M/L/Si) (dBA)N/A / 52.0 / 47.5 / 40.0 / 38.00
Dimension (W×D×H)inch: 32.68 x 32.68 x 9.65
mm: 830.0×830.0×245.0
Package (W×D×H)inch: 35.83 x 35.83 x 11.42
mm: 910×910×290
Net/Gross Weightlbs: 59.30/71.43
kg: 26.9/32.4

Outdoor Unit Specifications

Compressor TypeTWIN-ROTARY
Compressor ModelEKPQ420D1UMUA
RefrigerantR454B
Refrigerant Oil Charge(mL)1460ml
Refrigerant Oil3265
Outdoor Air Flow (Max) (CFM)3001.9
Outdoor Noise Level (dBA)64.5
Dimension (W×D×H)inch: 38.58 x 16.34 x 38.39
mm: 980.0×415.0×975.0
Package (W×D×H)inch: 45.08 x 19.68 x 42.52
mm: 1145×500×1080
Net/Gross Weightlbs: 206.57/237.44
kg: 93.7/107.7

Electrical Specifications

Power Supply208/230V,60Hz,1Ph
System MCA38.00
Connection Wiring14#x3
System MOCP40
Compressor RLA24.5
Outdoor Fan Motor RLA2.1
Outdoor Fan Motor W250
Indoor Fan Motor RLA1.0
Indoor Fan Motor W125
System Power Input @ Cooling (W)3042 (580 ~ 3480)
System Power Input @ Heating (W)3161 (740 ~ 4160)
MCA: Min. circuit amps (A)MOCP: Max. over current protection (A)
RLA: Rated load amps (A)W: Fan motor rated output (W)

Piping Specifications

Throttle type(Indoor)N/A
Throttle type(Outdoor)EXV+Throttle valve
Liquid Size9.52mm (3/8in)
Gas Size19mm (3/4in)
Max. Piping Length(ft/m)246.00 (75)
Max. Height Difference(ft/m)98.40 (30)
Max. Pre-charged Length(ft/m)24.6 (7.5)
Refrigerant Pre-charged Amount(oz/kg)126.99 (3.60)
Additional Charge of Refrigerant((oz/ft)/(g/m))0.32 (30)
Connection MethodFlared

Indoor Unit Dimensions

This section provides dimensional data for the indoor unit. The unit is designed for ceiling mounting and has a square cassette form factor. Key dimensions include the main body width and depth of 32-5/8 inches (830mm) and a height of 9.65 inches (245mm). The front panel extends to approximately 37-1/2 inches (950mm) square. It also details the drain hole size (1 inch / ø25mm) and indicates the locations for liquid and gas line connections.

Indoor Unit Installation Instructions

This section illustrates the recommended installation clearances for the indoor unit within a ceiling space. It depicts the unit suspended from the ceiling, with considerations for ventilation and illumination. Crucially, it specifies minimum clearances: 59.1 inches (150cm) from the ceiling to the unit, with 78.7 inches (200cm) recommended for optimal performance. Further clearance of 157.5 inches (400cm) is shown for ventilation. A table provides model-specific data for the distance from the ceiling (Length of A), required overhead clearance (Length of H), and the ceiling opening size (Length of B).

MODELLength of ALength of HLength of B
9K/12K/18K9.6in (245mm)>10.8in (275mm)23.6in (600mm)
24K8.03in (205mm)9.06in (230mm)35.4in (900mm)
36K9.65in (245mm)10.7in (271mm)
48K11.3in (287mm)12.3in (313mm)

Outdoor Unit Dimensions and Installation

This section details the physical dimensions and required installation clearances for the outdoor unit. The unit is rectangular. Key dimensions are approximately 38-1/2 inches (980mm) in width, 16-3/8 inches (415mm) in depth, and 38-3/8 inches (975mm) in height. Installation requires significant clearance around the unit for proper airflow and maintenance: 20 inches (500mm) or more is needed at the front and sides if two adjacent sides are clear, and 4 inches (100mm) or more is required on other sides, with 14 inches (350mm) specified for the rear. The document emphasizes meeting all spatial requirements.

Features

  • 360° Air Flow
  • Remote on-off and alarm ports
  • Refrigerant leakage detection sensor (Optional)
  • Humidity sensor
  • Built-in pump
  • 1~100% fan speed setting
  • WiFi capability: through WiFi dongle or wired controller with built-in WiFi
  • OTA (by using WiFi dongle)
  • 2-pin connector (HA/HB) for programmable wired controller
  • Multiple control options available:
    • Two way communication wired controller: 120N(X6)
    • Two way communication wired controller with built-in WiFi: 120N(X6W)
    • Infrared wired controller: 120L
    • Wireless remote controller
    • Third-Party 24V Thermostat*

*24V interface is required.

PDF preview unavailable. Download the PDF instead.

blueridgebxl2a36uc0-36cc4specificationssheet 67C21556-1F4B-45F5-8449-C44F7893220D Google Sheets

Related Documents

Preview Blue Ridge XS5 FC Ceiling & Floor Heat Pump System Submittal Data Sheet
Submittal data sheet for the Blue Ridge XS5 FC Ceiling & Floor Heat Pump System, detailing specifications, performance, dimensions, and features for HVAC applications.
Preview Blue Ridge XS5 CDH High Static Slim Duct Hyper Heat Series Submittal Data Sheet
Submittal data sheet for the Blue Ridge XS5 CDH High Static Slim Duct Hyper Heat Series heat pump system, detailing efficiency ratings, cooling and heating performance, indoor and outdoor specifications, electrical requirements, piping details, installation guidelines, and fan performance.
Preview Blueridge XS5 CC 4-Way Cassette Heat Pump System Submittal Data Sheet
Comprehensive submittal data sheet for the Blueridge XS5 CC 4-Way Cassette Heat Pump System, featuring R454B refrigerant. Includes detailed specifications, performance data for cooling and heating, electrical requirements, piping information, and installation clearance guidelines.
Preview Blue Ridge Slim Duct Heat Pump System: Submittal Data Sheet & Specifications
Detailed submittal data sheet for the Blue Ridge Slim Duct Heat Pump System, including specifications, performance data, dimensions, and installation clearances. Features R454B refrigerant and Energy Star certification.
Preview Blue Ridge One Way Cassette Heat Pump System - Submittal Data Sheet & Specifications
Detailed submittal data sheet for the Blue Ridge One Way Cassette Heat Pump System, including efficiency ratings, performance data, electrical specifications, dimensions, installation clearances, and features. Model KSK103D33UEZ3, R454B refrigerant.
Preview Ceiling & Floor Heat Pump System Submittal Data Sheet
Submittal data sheet for the Ceiling & Floor Heat Pump System, detailing efficiency, performance, indoor and outdoor specifications, electrical, and piping information. Includes features and installation clearance requirements.
Preview Blue Ridge Air Handler Heat Pump System Submittal Data Sheet
Detailed technical specifications, performance data, dimensions, and features for the Blue Ridge Air Handler Heat Pump System, including SEER2, EER2, HSPF2-4, COP ratings, cooling and heating capacities, electrical requirements, and piping details for models MVBM-24B18T3N10, MVBM-24A18T3N10, MVBM-36A24T4N10, MVBM-36B24T4N10, MVBM-36C24T4N10, and MVBM-60D28T6N10.
Preview Blueridge XS2+Entry High Wall Heat Pump System - 21 SEER2 Submittal Data Sheet
Comprehensive submittal data sheet for the Blueridge XS2+Entry high wall heat pump system, detailing efficiency ratings (21 SEER2), performance specifications for cooling and heating, electrical requirements, piping details, and key features. Includes indoor and outdoor unit dimensions and installation clearance guidelines.