SUBMITTAL DATA SHEET
4-Way Cassette Heat Pump System
Efficiency
Cooling | Heating | |
SEER2 | 21.2 | HSPF2-4 |
EER2 | 12.0 | COP |
3.43 |
Performance of Cooling
Cooling (Btu/hr) | |
Rated Capacity | 36600 |
Min/Max Capacity | 4900~38000 |
Moisture Removal(L/h) | 4.30 |
Standard Operating Range (°F/°C) | -22~122 (-30~50) |
Conditions: | Indoor: 80°F DB/67°F WB Outdoor: 95°F DB/75°F WB |
Performance of Heating
Heating (Btu/hr) | |
1. @ 47°F Rated | 37000 |
1. @ 47°F Min/Max Capacity | 11400~44600 |
2. @ 17°F Rated | 30600 |
3. @ 5°F Rated: Capacity / COP | 37000/1.95 |
3. @ 5°F Max: Capacity | 37000 |
Standard Operating Range (°F/°C) | -22~75 (-30~24) |
1. Conditions: | Indoor: 70°F DB/60°F WB Outdoor: 47°F DB/43°F WB |
2. Conditions: | Indoor: 70°F DB/60°F WB Outdoor: 17°F DB/15°F WB |
3. Conditions | Indoor: 70°F DB/60°F WB Outdoor: 5°F DB/5°F WB |
Indoor Unit Specifications
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) | 1041.8 / 947.6 / 853.5 / 753.4 / 659.2 |
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) | N/A / 52.0 / 47.5 / 40.0 / 38.00 |
Dimension (W×D×H) | inch: 32.68 x 32.68 x 9.65 mm: 830.0×830.0×245.0 |
Package (W×D×H) | inch: 35.83 x 35.83 x 11.42 mm: 910×910×290 |
Net/Gross Weight | lbs: 59.30/71.43 kg: 26.9/32.4 |
Outdoor Unit Specifications
Compressor Type | TWIN-ROTARY |
Compressor Model | EKPQ420D1UMUA |
Refrigerant | R454B |
Refrigerant Oil Charge(mL) | 1460ml |
Refrigerant Oil | 3265 |
Outdoor Air Flow (Max) (CFM) | 3001.9 |
Outdoor Noise Level (dBA) | 64.5 |
Dimension (W×D×H) | inch: 38.58 x 16.34 x 38.39 mm: 980.0×415.0×975.0 |
Package (W×D×H) | inch: 45.08 x 19.68 x 42.52 mm: 1145×500×1080 |
Net/Gross Weight | lbs: 206.57/237.44 kg: 93.7/107.7 |
Electrical Specifications
Power Supply | 208/230V,60Hz,1Ph |
System MCA | 38.00 |
Connection Wiring | 14#x3 |
System MOCP | 40 |
Compressor RLA | 24.5 |
Outdoor Fan Motor RLA | 2.1 |
Outdoor Fan Motor W | 250 |
Indoor Fan Motor RLA | 1.0 |
Indoor Fan Motor W | 125 |
System Power Input @ Cooling (W) | 3042 (580 ~ 3480) |
System Power Input @ Heating (W) | 3161 (740 ~ 4160) |
MCA: Min. circuit amps (A) | MOCP: Max. over current protection (A) |
RLA: Rated load amps (A) | W: Fan motor rated output (W) |
Piping Specifications
Throttle type(Indoor) | N/A |
Throttle type(Outdoor) | EXV+Throttle valve |
Liquid Size | 9.52mm (3/8in) |
Gas Size | 19mm (3/4in) |
Max. Piping Length(ft/m) | 246.00 (75) |
Max. Height Difference(ft/m) | 98.40 (30) |
Max. Pre-charged Length(ft/m) | 24.6 (7.5) |
Refrigerant Pre-charged Amount(oz/kg) | 126.99 (3.60) |
Additional Charge of Refrigerant((oz/ft)/(g/m)) | 0.32 (30) |
Connection Method | Flared |
Indoor Unit Dimensions
This section provides dimensional data for the indoor unit. The unit is designed for ceiling mounting and has a square cassette form factor. Key dimensions include the main body width and depth of 32-5/8 inches (830mm) and a height of 9.65 inches (245mm). The front panel extends to approximately 37-1/2 inches (950mm) square. It also details the drain hole size (1 inch / ø25mm) and indicates the locations for liquid and gas line connections.
Indoor Unit Installation Instructions
This section illustrates the recommended installation clearances for the indoor unit within a ceiling space. It depicts the unit suspended from the ceiling, with considerations for ventilation and illumination. Crucially, it specifies minimum clearances: 59.1 inches (150cm) from the ceiling to the unit, with 78.7 inches (200cm) recommended for optimal performance. Further clearance of 157.5 inches (400cm) is shown for ventilation. A table provides model-specific data for the distance from the ceiling (Length of A), required overhead clearance (Length of H), and the ceiling opening size (Length of B).
MODEL | Length of A | Length of H | Length of B |
9K/12K/18K | 9.6in (245mm) | >10.8in (275mm) | 23.6in (600mm) |
24K | 8.03in (205mm) | 9.06in (230mm) | 35.4in (900mm) |
36K | 9.65in (245mm) | 10.7in (271mm) | |
48K | 11.3in (287mm) | 12.3in (313mm) |
Outdoor Unit Dimensions and Installation
This section details the physical dimensions and required installation clearances for the outdoor unit. The unit is rectangular. Key dimensions are approximately 38-1/2 inches (980mm) in width, 16-3/8 inches (415mm) in depth, and 38-3/8 inches (975mm) in height. Installation requires significant clearance around the unit for proper airflow and maintenance: 20 inches (500mm) or more is needed at the front and sides if two adjacent sides are clear, and 4 inches (100mm) or more is required on other sides, with 14 inches (350mm) specified for the rear. The document emphasizes meeting all spatial requirements.
Features
- 360° Air Flow
- Remote on-off and alarm ports
- Refrigerant leakage detection sensor (Optional)
- Humidity sensor
- Built-in pump
- 1~100% fan speed setting
- WiFi capability: through WiFi dongle or wired controller with built-in WiFi
- OTA (by using WiFi dongle)
- 2-pin connector (HA/HB) for programmable wired controller
- Multiple control options available:
- Two way communication wired controller: 120N(X6)
- Two way communication wired controller with built-in WiFi: 120N(X6W)
- Infrared wired controller: 120L
- Wireless remote controller
- Third-Party 24V Thermostat*
*24V interface is required.