SUBMITTAL DATA SHEET

Location: [Not Specified]

Engineer: [Not Specified]

Submitted to: [Not Specified]

Submitted by: [Not Specified]

Reference: [Not Specified]

Certifications: ARI CERTIFIED, ENERGY STAR, UL, ETL

EFFICIENCY

CoolingHeating
SEER216.0HSPF2-4 10.0
EER210.0COP 3.37

PERFORMANCE OF COOLING

Cooling (Btu/hr)

Rated Capacity29,000
Min/Max Capacity13,900~37,900
Moisture Removal(L/h)3.7
Standard Operating Range (°F/°C)-22~122 (-30~50)
Rated Cooling Conditions:Indoor: 80°F DB/67°F WB
Outdoor: 95°F DB/75°F WB

PERFORMANCE OF HEATING

Heating (Btu/hr)

1. @ 47°F Rated32,000
2. @ 47°F Min/Max Capacity13,00~40,000
3. @ 17°F Rated25,000
4. @ 5°F Rated: Capacity / COP33,000 / 1.9
5. @ 5°F Max: Capacity33,000
Standard Operating Range (°F/°C)-22~75 (-30~24)
1. Rated Heating Conditions:Indoor: 70°F DB/60°F WB
Outdoor: 47°F DB/43°F WB
2. Rated Heating Conditions:Indoor: 70°F DB/60°F WB
Outdoor: 17°F DB/15°F WB
3. Heating Conditions, Compressor Operating at Max. FrequencyIndoor: 70°F DB/60°F WB
Outdoor: 5°F DB/5°F WB

INDOOR SPECIFICATION

Dimension (W×D×H)17-1/2 x 21 x 23-1/2 inches (445 x 533 x 599 mm)
Package (W×D×H)20-1/2 x 26-1/8 x 26-3/8 inches (520 x 665 x 670 mm)
Net/Gross Weight59.5/68 lbs (27/30.9 kg)

OUTDOOR SPECIFICATION

Compressor TypeROTARY
Compressor ModelMTH356UKRC8FQL
RefrigerantR454B
Refrigerant Oil Charge(mL)1300
Refrigerant OilHAF68D1A
Outdoor Air Flow (Max) (CFM)3,002
Outdoor Noise Level (dBA)64
Dimension (W×D×H)37-1/4 x 16-1/8 x 31-7/8 inches (946 x 410 x 810 mm)
Package (W×D×H)42-7/8 x 19-5/8 x 34-7/8 inches (1090 x 500 x 885 mm)
Net/Gross Weight164/175 lbs (74.4/79.2 kg)

ELECTRICAL

Indoor Power Supply24V,60Hz, 1Ph
Indoor MCA 115V/(208/230V)/
Indoor MOP/
Outdoor Power Supply208/230,60Hz, 1Ph
Outdoor MCA29.5 A
Outdoor MOP30 A
Communication WiringAWG 20-2
Compressor RLA22.4 A
Outdoor Fan Motor RLA1.5 A
Outdoor Fan Motor W/
Indoor Fan Motor RLA/
Indoor Fan Motor W/
System Power Input @ Cooling (W)2900 (1,160 ~ 3,740)
System Power Input @ Heating (W)2780 (1,088 ~ 3,482)
MCA: Min. circuit amps (A)[Value not explicitly listed for outdoor, but MCA is listed]
MOCP: Max. over current protection (A)[Value not explicitly listed for outdoor, but MOP is listed]
RLA: Rated load amps (A)[Value not explicitly listed for outdoor, but RLA is listed]
W: Fan motor rated output (W)[Value not explicitly listed for outdoor, but W is listed]

PIPING

Throttle type(Indoor)EXV
Throttle type(Outdoor)EXV
Liquid Size9.52mm (3/8in)
Gas Size19mm (3/4in)
Max. Piping Length(ft/m)164 (50)
Max. Height Difference(ft/m)82 (25)
Max. Pre-charged Length(ft/m)24.6 (7.5)
Refrigerant Pre-charged Amount (oz/kg)105.82 (3)
Additional Charge of Refrigerant((oz/ft)/(g/m))0.7 (65)
Connection MethodFlared

Indoor Unit Dimensions

Diagrams illustrating the dimensions of the indoor unit. Includes front, side, and top views, showing key measurements labeled A through F. A table provides specific dimensions (Height, Width, Supply Air Opening Width, Return Air Opening Width, Condensate Drains Height, Liquid Line Height) in inches and millimeters for various models (MVBM-24B18T3N10, MVBM-24A18T3N10, MVBM-36A24T4N10, MVBM-36B24T4N10, MVBM-36C24T4N10, MVBM-60D28T6N10).

DimensionModelMVBM-24B18T3N10MVBM-24A18T3N10MVBM-36A24T4N10MVBM-36B24T4N10MVBM-36C24T4N10MVBM-60D28T6N10
inch | mminch | mminch | mminch | mminch | mminch | mm
A: Model Height18 | 45718 | 45723-5/16 | 59223-9/16 | 59924 | 61128 | 711
B: Model Width17-1/2 | 44514-1/2 | 36814-1/2 | 36817-1/2 | 44521 | 53424-1/2 | 622
C: Supply Air Opening Width16-3/16 | 41113-1/4 | 33613-1/4 | 33616-3/16 | 41119-3/4 | 50223-1/4 | 591
D: Return Air Opening Width15/16 | 38015/16 | 30315/16 | 30315/16 | 38019-1/2 | 49823-1/8 | 587
E: Condensate Drains Height1-7/16 | 381-7/16 | 381-7/16 | 381-7/16 | 382-3/16 | 552-3/16 | 55
F: Liquid Line Height11-3/8 | 29011-3/8 | 29017-15/16 | 45516-3/8 | 41717-1/2 | 44521-7/16 | 545

Outdoor Unit Dimensions

Diagrams showing the external dimensions of the outdoor unit from multiple angles (front, side, top). Includes measurements for overall width, depth, and height, as well as details for pipe connections and mounting points.

Installation Instruction For Outdoor Unit

Diagram illustrating required clearances for the outdoor unit installation. Specifies minimum distances: 20 inches (500mm) or more from the front and sides when any two sides (left, right, rear) are clear; 4 inches (100mm) or more from the sides and rear. Also indicates 4 inches (100mm) or more clearance from the front and sides when the unit is clear.

✓ Meets all spatial requirements shown in Installation Clearance Requirements above.

Features

PDF preview unavailable. Download the PDF instead.

blueridgebng3a30scn-36enbspecificationssheet FD047897-15C5-481E-837F-12F02BADF6B7 Google Sheets

Related Documents

Preview Air Handler Heat Pump System Submittal Data Sheet - Specifications and Performance
Detailed submittal data sheet for the Air Handler Heat Pump System, including indoor and outdoor unit specifications, performance data, electrical requirements, and piping details. Features R454B refrigerant and rotary compressor.
Preview Blue Ridge Air Handler Heat Pump System Specifications | KTM240D46UKT2
Detailed submittal data sheet for the Blue Ridge Air Handler Heat Pump System, featuring efficiency, performance, electrical, and piping specifications. Includes models like KTM240D46UKT2 and MVBM series.
Preview Blue Ridge ETPQ480D66UMU1 Air Handler Heat Pump System Submittal Data Sheet
This submittal data sheet provides detailed specifications for the Blue Ridge ETPQ480D66UMU1 Air Handler Heat Pump System, covering performance, efficiency ratings (SEER2, EER2, HSPF2, COP), dimensions, electrical requirements, and key features like multi-position installation and R454B refrigerant compatibility.
Preview Blue Ridge High Wall Heat Pump System Submittal Data Sheet
Detailed submittal data sheet for the Blue Ridge High Wall Heat Pump System, covering efficiency ratings, performance specifications for cooling and heating, indoor and outdoor unit details, electrical requirements, and piping information.
Preview Blue Ridge High Wall Heat Pump System Submittal Data Sheet
Technical specifications and performance data for the Blue Ridge High Wall Heat Pump System, including efficiency ratings, cooling and heating performance, indoor/outdoor unit details, electrical requirements, and piping specifications.
Preview Blueridge XS2+Entry High Wall Heat Pump System - 21 SEER2 Submittal Data Sheet
Comprehensive submittal data sheet for the Blueridge XS2+Entry high wall heat pump system, detailing efficiency ratings (21 SEER2), performance specifications for cooling and heating, electrical requirements, piping details, and key features. Includes indoor and outdoor unit dimensions and installation clearance guidelines.
Preview Blue Ridge DS2 High Wall Heat Pump System - Technical Specifications & Features
Detailed submittal data sheet for the Blue Ridge DS2 High Wall Heat Pump System, including efficiency ratings (SEER2, HSPF2-4), performance data, indoor/outdoor unit specifications, electrical requirements, piping details, and features like WiFi connectivity.
Preview Blue Ridge High Wall Heat Pump System: Technical Specifications and Installation Guide
Comprehensive technical specifications, performance data, electrical requirements, and installation guidelines for the Blue Ridge High Wall Heat Pump System, including SEER2, HSPF2-4, and detailed operating conditions.