Hykolity ACE Series LED UFO High Bay Light
Contact: inquiry@hykolity.com | Website: www.hykolity.com | Phone: +1 (562) 456-0507
Key Features: BRIGHT, TRUSTED, HIGH-QUALITY
Product Overview
Thank you for purchasing the Hykolity ACE Series UFO High Bay Light. Please read these instructions carefully for safe and proper use.
Warning:
- Input voltage range: AC100-277V, 50/60Hz. Exceeding this range may cause failure.
- Operating temperature range: -22°F (-30°C) to 122°F (50°C). Operation outside this range may reduce lifespan.
- Always turn off power before installation.
Attention:
- IP rating: IP65, suitable for wet locations.
- Keep away from corrosive substances. Clean with a damp or dry cloth only.
Specifications
Model | UFODY-150W-QL-1 | UFODY-200W-QL-1 | UFODY-250W-QL-1 | UFODY-300W-QL-1 |
---|---|---|---|---|
Power | 150W | 200W | 250W | 300W |
Input Current | 1.65A | 2.2A | 2.75A | 3A |
Input Voltage | AC100-277V | |||
Frequency | 50/60Hz | |||
CCT | 5000K | |||
Efficacy | 130LM/W | |||
CRI | 80+ | |||
Beam Angle | 120° | |||
Lumens | 19500LM | 26000LM | 32500LM | 39000LM |
Certification | ETL Listed | |||
Lifespan | >50,000 Hours | |||
IP Rating | IP65 | |||
Housing Color | Black | |||
Dimming | 0-10V | |||
Mounting | Hook | |||
Warranty | 5 Years |
Installation Instructions
1. Hook Type Mounting
Follow these steps for hook mounting:
- Lock the hook securely onto the fixture. [Diagram: Shows a hook being locked into the fixture.]
- Hang the safety hook onto the main hook. [Diagram: Shows a safety hook being attached to the main hook.]
- Hang the light fixture. [Diagram: Shows the light fixture being hung up.]
- Lock the screw into the screw hole to secure the connection. [Diagram: Shows a screw being inserted and locked into a screw hole.]
Wiring Connection
Ensure power is turned off before connecting wires.
AC Wiring: Connect the black wire to L (Live), the white wire to N (Neutral), and the green wire to E (Ground).
Dimmer Connection (for dimmable drivers):
- Compatible with 0-10V Dimming.
- Connect wires as follows: Purple wire to D+ (0-10V D+), Pink wire to D- (0-10V D-). Cap the black wire if not used.
[Diagram: Illustrates AC IN connections (Green to E, White to N, Black to L) and Dimmer connections (Purple to PUR(DIM+), Pink to Pink(DIM-)) to the driver unit, which is then connected to the UFO High Bay.]
Optional Feature: Motion Sensor
Motion Sensor Installation Instructions
- Remove the white rubber ring from the fixture. [Diagram: Shows the fixture with a white rubber ring.]
- Install the motion sensor in the designated position. [Diagram: Shows the sensor being placed into the fixture.]
- Tighten the sensor and turn on the fixture to verify normal operation. [Diagram: Shows the completed installation with the sensor attached.]
Motion Sensor Specifications
Category | Specification |
---|---|
Input | Working Voltage: 5~24V DC Working Current: 33mA |
Output | Output Signal: 10V PWM (0-10V optional) |
Parameters | Microwave Frequency: 5.8GHz±75MHz Microwave power: <0.3mW Detection Sensitivity: 100%/75%/50%/25% (Refer to remote control) Time Delay: 5s/1min/3min/10min (Refer to remote control) Photosensitive Threshold: 10Lux/25Lux/50Lux/Disable (Refer to remote control) Waiting Time: 0s/10s/10min/+∞ (Refer to remote control) Waiting Brightness: 20%/30% (Refer to remote control) Mounting Height: Max.42ft (surface mount) Detection Distance: Radius 19ft (mounting height 42ft) Detection Angle: 30°-150° Working Temperature: -30°F~158°F IP Grade: IP65 |
Remark | Factory default settings: detection sensitivity 100%, time delay 5s, photosensitive threshold disable, waiting time 0s. |
Inductive Priority Switch Function
When Photosensitive Threshold is disabled and Waiting Time is set to 0s, the sensor operates as follows:
- Detection Area Entry: The light fixture automatically turns on to 100% brightness when someone enters the detection area. [Visual Description: A person entering a lit area.]
- Occupancy Detected (Delay): After the person leaves the detection area, the sensor continues to detect movement, and the lights remain at 100% brightness, entering the delay time. [Visual Description: A person leaving an area, light stays on.]
- No Movement Detected (Turn Off): After the delay time or waiting time ends, if no movement is detected, the lights turn off automatically. [Visual Description: An empty area, light turns off.]
Important Notes
- Thoroughly inspect the fixture for freight damage. Report any damage to the delivery carrier.
- Installation must be carried out by a qualified electrician.