R. STAHL 8530/1-MCB-STA102-C40-500-3 Line Protection Circuit Breaker
Article Number: 272140
Product Overview
The R. STAHL 8530 series line protection circuit breakers, specifically the 8530/1-MCB-STA102-C40-500-3 model, offer excellent current limitation for short circuits and high switching capacities of 10, 15, or 25 kA. These components ensure minimal load on lines and high selectivity with upstream fuses. They are modularly designed and available in 1 to 4 pole versions with nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).
Key features include:
- Isolation function according to EN 60947-2
- Energy limitation class 3
- Easy replacement or extension of systems due to modular design
- Simple mounting by clipping onto a DIN rail in Ex e enclosures
- Fixed thermal-magnetic releases
- Ergonomic operating lever for safe switching on and off
- Padlock protection (accessories) prevents re-operation during maintenance
Technical Specifications
Explosion Protection
Application Area (Zones) | 1, 2 |
---|---|
Application Area (Zones) Note | Usable in Zone 21 / 22 with protection by Ex tb / tc enclosure |
IECEx Certificate Gas | IECEx FMG 19.0029U |
IECEx Gas Explosion Protection | Ex db eb IIC Gb |
Certificat ATEX Gas | FM19ATEX0191U |
ATEX Gas Explosion Protection | II 2 G Ex db eb IIC Gb |
Certificates | ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM) |
Certificate of Conformity | Certificate of conformity (ATEX), China (CCC) |
Electrical Characteristics
Rated Operational Voltage AC | 230/400 V |
---|---|
Rated Service Current | 40 A |
Frequency | 50/60 Hz |
Rated Switching Capacity | 10 kA |
Electrical Service Life | 104 |
Mechanical Service Life | 2 x 104 |
1. Auxiliary Function | Auxiliary contact 1 changeover contact + signal contact 1 changeover contact |
Voltage 1st Auxiliary Function AC | 230 V |
Max. Current 1st Auxiliary Function | 2 A |
2. Auxiliary Function | None |
Max. Voltage 2nd Auxiliary Function DC | - |
Tripping Characteristic | C |
Number of Poles | 2 poles |
Ambient Conditions
Ambient Temperature | -40 °C ... 70 °C |
---|---|
Ambient Temperature | -40 °F ... 158 °F |
Ambient Temperature Note | Ambient temperatures different from the base of the current certificates, upon request. |
Mechanical Characteristics
Degree of Protection (IP) (IEC 60529) | IP2X |
---|---|
Enclosure Material | Thermoplastic |
Minimum Connection Terminal Size | 1.5 mm² |
Maximum Connection Terminal Size | 25 mm² |
Minimum AWG Connection Terminal Size | 16 AWG |
Maximum AWG Connection Terminal Size | 4 AWG |
Minimum Connection Terminal Size 2 | 1.5 mm² |
Maximum Connection Terminal Size 2 | 10 mm² |
Minimum AWG Connection Terminal Size 2 | 16 AWG |
Maximum AWG Connection Terminal Size 2 | 8 AWG |
Min. Connection Terminal Size (Auxiliary Contact) | 0.5 mm² |
Max. Connection Terminal Size (Auxiliary Contact) | 4 mm² |
Min. AWG Connection Terminal Size (Auxiliary Contact) | 18 (unece.unit.AWG) |
Max. AWG Connection Terminal Size (Auxiliary Contact) | 14 (unece.unit.AWG) |
Minimum Tightening Torque | 2 N·m |
Maximum Tightening Torque | 3 N·m |
Connection Terminal Note | Connection of 2 conductors (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.) |
Dimensions
Width | 83 mm (3.27 in) |
---|---|
Length | 165 mm (6.5 in) |
Mounting Depth | 138.3 mm (5.44 in) |
Weight | 1.3 kg (2.867 lb) |
Mounting / Installation
Tightening Torque | 2-3 N·m (17.7 ... 26.6 lbf-in) |
---|---|
Tightening Torque (Auxiliary Contact) | 0.4–0.6 Nm (3.5 ... 5.3 lbf-in) |
Technical Drawings
Diagrams show technical drawings and dimensions. Please refer to the original document for visual representation.
A tripping characteristic curve is provided, illustrating the relationship between multiple of the rated current (I/In) and tripping time in seconds for characteristic C.
Overall dimensions are shown in mm [inches].
Accessories
Quadruple Locking Device
A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.
Description | Article Number |
---|---|
Quadruple locking/unlocking system for individual component locking with up to 4 cylinder locks. | 227232 |
Mounting Kit
Description | Article Number |
---|---|
Mounting kit for fixing the component to the mounting plate without a DIN rail. | 276618 |
Cylinder Lock
Description | Article Number |
---|---|
For locking (shackle Ø 3) | 107115 |
Note: Technical specifications, dimensions, weight, construction types, and delivery possibilities are subject to change. Figures are for indicative purposes only.
Manufacturer: R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG
Contact: Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | Website: r-stahl.com