R. STAHL 8530/1-MCB-STA102-C1-500-3 Line Protection Circuit Breaker
Article Number: 267203
Product Overview
The R. STAHL 8530/1-MCB-STA102-C1-500-3 is a line protection circuit breaker designed for system technology. It offers high current limitation for short circuits and a high switching capacity of 10, 15, or 25 kA, ensuring low line load and high selectivity with upstream fuses. The components are modular and available in 1 to 4 pole versions with nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 installation units (UP).
Key Features
- Disconnecting function according to EN 60947-2
- Energy limitation class 3
- Easy replacement or expansion of your system due to modular design
- Simple snap-on mounting on a DIN rail in Ex e enclosures
- Fixed magneto-thermal releases
- Ergonomic control lever for safe switching on and off
- Padlock protection (accessories) prevents re-switching during maintenance operations
Technical Characteristics
Explosion Protection
Characteristic | Value |
---|---|
Application area (zones) | 1, 2 |
Application area (zones) Avis | Usable in Zone 21 / 22 with protection by Ex tb / tc enclosure |
IECEx certificate gas | IECEx FMG 19.0029U |
IECEx protection against gas explosion | Ex db eb IIC Gb |
ATEX certificate gas | FM19ATEX0191U |
ATEX protection against gas explosion | II 2 G Ex db eb IIC Gb |
Certificates | ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM) |
Certificate of conformity | Certificate of conformity (ATEX), China (CCC) |
Electrical Characteristics
Characteristic | Value |
---|---|
Rated operational voltage AC | 230/400 V |
Rated service current | 1 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 10⁴ |
Mechanical service life | 2 x 10⁴ |
1st auxiliary function | Auxiliary contact 1 changeover contact + signal error contact 1 changeover contact |
Voltage 1st auxiliary function AC | 230 V |
Max. current 1st auxiliary function | 2 A |
2nd auxiliary function | none |
Max. voltage 2nd auxiliary function DC | - |
Tripping characteristic | C |
Number of poles | 2-pole |
Ambient Conditions
Characteristic | Value |
---|---|
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature Avis | Ambient temperatures different from the current certificates, on request |
Mechanical Characteristics
Characteristic | Value |
---|---|
Degree of protection (IP) (IEC 60529) | IP2X |
Enclosure material | Thermoplastic |
Connection terminal minimum cross-section | 1.5 mm² |
Connection terminal maximum cross-section | 25 mm² |
Connection terminal AWG min. | 16 AWG |
Connection terminal AWG max. | 4 AWG |
Connection terminal 2 minimum cross-section | 1.5 mm² |
Connection terminal 2 maximum cross-section | 10 mm² |
Connection terminal 2 AWG min. | 16 AWG |
Connection terminal 2 AWG max. | 8 AWG |
Auxiliary contact connection min. cross-section | 0.5 mm² |
Auxiliary contact connection max. cross-section | 4 mm² |
Auxiliary contact connection min. AWG | 18 (unece.unit.AWG) |
Auxiliary contact connection max. AWG | 14 (unece.unit.AWG) |
Min. torque | 2 N·m |
Max. torque | 3 N·m |
Connection terminal Avis | Connection of 2 conductors (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum cross-section difference between the upper and lower chamber.) |
Dimensions
Dimension | Value |
---|---|
Width | 83 mm (3.27 in) |
Length | 165 mm (6.5 in) |
Mounting depth | 138.3 mm (5.44 in) |
Weight | 1.3 kg (2.867 lb) |
Mounting / Installation
Characteristic | Value |
---|---|
Torque | 2-3 N·m (17.7 ... 26.6 lbf·in) |
Torque auxiliary contact | 0.4–0.6 Nm (3.5 ... 5.3 lbf·in) |
Technical Drawings
Technical drawings are subject to change.
Diagrams
Auxiliary Contacts: Depicts a 2-pole configuration with one changeover auxiliary contact and one signal error contact.
Tripping Characteristic Curve: A graph illustrating the tripping time versus multiples of the rated current (I/In) for tripping characteristic C, showing the limit from a cold state for AC and DC.
Dimensional Drawing: Shows the overall dimensions of the unit, including width, length, and mounting depth, with measurements in both millimeters and inches. The unit is described as 8530/1; 3 division units.
Accessories
Accessory | Description | Article Number |
---|---|---|
Quadruple Locking Device | A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks. | 227232 |
Fixing Kit | A fixing kit to attach the component to the mounting plate without a DIN rail. | 276618 |
Cylinder Lock | For locking (stirrup Ø 3) | 107115 |
Subject to change in technical characteristics, dimensions, weight, construction types, and delivery possibilities. Figures are for illustrative purposes only.
Contact Information: R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG | Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com