R. STAHL 8530/1-MCB-STA102-C1-500-3 Line Protection Circuit Breaker

Article Number: 267203

Product Overview

The R. STAHL 8530/1-MCB-STA102-C1-500-3 is a line protection circuit breaker designed for system technology. It offers high current limitation for short circuits and a high switching capacity of 10, 15, or 25 kA, ensuring low line load and high selectivity with upstream fuses. The components are modular and available in 1 to 4 pole versions with nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 installation units (UP).

Key Features

Technical Characteristics

Explosion Protection

CharacteristicValue
Application area (zones)1, 2
Application area (zones) AvisUsable in Zone 21 / 22 with protection by Ex tb / tc enclosure
IECEx certificate gasIECEx FMG 19.0029U
IECEx protection against gas explosionEx db eb IIC Gb
ATEX certificate gasFM19ATEX0191U
ATEX protection against gas explosionII 2 G Ex db eb IIC Gb
CertificatesATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
Certificate of conformityCertificate of conformity (ATEX), China (CCC)

Electrical Characteristics

CharacteristicValue
Rated operational voltage AC230/400 V
Rated service current1 A
Frequency50/60 Hz
Rated switching capacity10 kA
Electrical service life2 x 10⁴
Mechanical service life2 x 10⁴
1st auxiliary functionAuxiliary contact 1 changeover contact + signal error contact 1 changeover contact
Voltage 1st auxiliary function AC230 V
Max. current 1st auxiliary function2 A
2nd auxiliary functionnone
Max. voltage 2nd auxiliary function DC-
Tripping characteristicC
Number of poles2-pole

Ambient Conditions

CharacteristicValue
Ambient temperature-40 °C ... 70 °C
Ambient temperature-40 °C ... 70 °C
Ambient temperature-40 °F ... 158 °F
Ambient temperature AvisAmbient temperatures different from the current certificates, on request

Mechanical Characteristics

CharacteristicValue
Degree of protection (IP) (IEC 60529)IP2X
Enclosure materialThermoplastic
Connection terminal minimum cross-section1.5 mm²
Connection terminal maximum cross-section25 mm²
Connection terminal AWG min.16 AWG
Connection terminal AWG max.4 AWG
Connection terminal 2 minimum cross-section1.5 mm²
Connection terminal 2 maximum cross-section10 mm²
Connection terminal 2 AWG min.16 AWG
Connection terminal 2 AWG max.8 AWG
Auxiliary contact connection min. cross-section0.5 mm²
Auxiliary contact connection max. cross-section4 mm²
Auxiliary contact connection min. AWG18 (unece.unit.AWG)
Auxiliary contact connection max. AWG14 (unece.unit.AWG)
Min. torque2 N·m
Max. torque3 N·m
Connection terminal AvisConnection of 2 conductors (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum cross-section difference between the upper and lower chamber.)

Dimensions

DimensionValue
Width83 mm (3.27 in)
Length165 mm (6.5 in)
Mounting depth138.3 mm (5.44 in)
Weight1.3 kg (2.867 lb)

Mounting / Installation

CharacteristicValue
Torque2-3 N·m (17.7 ... 26.6 lbf·in)
Torque auxiliary contact0.4–0.6 Nm (3.5 ... 5.3 lbf·in)

Technical Drawings

Technical drawings are subject to change.

Diagrams

Auxiliary Contacts: Depicts a 2-pole configuration with one changeover auxiliary contact and one signal error contact.

Tripping Characteristic Curve: A graph illustrating the tripping time versus multiples of the rated current (I/In) for tripping characteristic C, showing the limit from a cold state for AC and DC.

Dimensional Drawing: Shows the overall dimensions of the unit, including width, length, and mounting depth, with measurements in both millimeters and inches. The unit is described as 8530/1; 3 division units.

Accessories

AccessoryDescriptionArticle Number

Quadruple Locking Device

A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.227232

Fixing Kit

A fixing kit to attach the component to the mounting plate without a DIN rail.276618

Cylinder Lock

For locking (stirrup Ø 3)107115

Subject to change in technical characteristics, dimensions, weight, construction types, and delivery possibilities. Figures are for illustrative purposes only.

Contact Information: R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG | Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta102-c1-500-3-267203-fr-fr-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA102-C1-500-3 Miniature Circuit Breaker - Technical Data and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA102-C1-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and installation information.
Preview R. STAHL 8530/1-MCB-STA102-C1-500-3 Miniature Circuit Breaker - Technical Data
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-C1-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C1-500-3 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C1-500-3 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Ex zones.
Preview R. STAHL MCB Miniature Circuit Breaker 8530/1-MCB-STA102-C40-500-3: Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-C40-500-3 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C2-500-3 Line Protection Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C2-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-B25-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B25-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C40-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C40-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C25-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C25-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.