R. STAHL 8530/1-MCB-STA102-B6-500-3 Line Protection Circuit Breaker
Article No. 272123
System Components for System Technology
Disjoncteur Disjonct. protection de ligne
The R. STAHL 8530 series line protection circuit breakers offer excellent current limitation for short circuits and high switching capacities of 10, 15, or 25 kA. This ensures minimal load on lines and high selectivity to upstream fuses. The components are modular and available in 1 to 4-pole versions for nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (PU).
Key Features:
- Disconnecting function according to EN 60947-2
- Energy limitation class 3
- Easy replacement or extension of your system thanks to the modular design of the circuit breakers
- Simple mounting by clipping onto a DIN rail in Ex e enclosures
- Fixed magneto-thermal releases
- Ergonomic control lever for safe switching on and off
- Padlock protection (accessories) prevents restarting during maintenance operations
Technical Characteristics
Explosion Protection
Application Area (Zones) | Application Area (Zones) Notice | IECEx Gas Certificate | IECEx Gas Explosion Protection | ATEX Gas Certificate | ATEX Gas Explosion Protection | Certificates | Certificate of Conformity |
---|---|---|---|---|---|---|---|
1, 2 | Usable in Zone 21 / 22 with protection by Ex tb / tc enclosure | IECEX FMG 19.0029U | Ex db eb IIC Gb | FM19ATEX0191U | II 2 G Ex db eb IIC Gb | ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM) | Certificate of Conformity (ATEX), China (CCC) |
Electrical Characteristics
sansRated Operational Voltage AC | Rated Service Current | Frequency | Rated Switching Capacity | Electrical Service Life | Mechanical Service Life | 1st Auxiliary Function | Voltage 1st Auxiliary Function AC | Max. Current 1st Auxiliary Function | 2nd Auxiliary Function | Max. Voltage 2nd Auxiliary Function DC | Trip Characteristic | Number of Poles |
---|---|---|---|---|---|---|---|---|---|---|---|---|
230/400 V | 6 A | 50/60 Hz | 10 kA | 2 x 104 | 2 x 104 | Auxiliary contact 1 changeover contact + 1 signal contact two-way + 1 error signal contact two-way | 230 V | 2 A | - | B | 2 poles |
Ambient Conditions
Ambient Temperature | Ambient Temperature | Ambient Temperature Notice |
---|---|---|
-40 °C ... 70 °C | -40 °F ... 158 °F | Ambient temperatures different based on current certificates, upon request |
Mechanical Characteristics
Degree of Protection (IP) (IEC 60529) | Housing Material | Minimum Connection Terminal Size | Maximum Connection Terminal Size | Minimum AWG Connection Terminal Size | Maximum AWG Connection Terminal Size | Minimum Connection Terminal Size 2 | Maximum Connection Terminal Size 2 | Minimum AWG Connection Terminal Size 2 | Maximum AWG Connection Terminal Size 2 | Min. Connection Terminal Size (Auxiliary) | Max. Connection Terminal Size (Auxiliary) | Min. AWG Connection Terminal Size (Auxiliary) | Max. AWG Connection Terminal Size (Auxiliary) | Minimum Tightening Torque | Maximum Tightening Torque | Connection Terminal Size Notice |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
IP2X | Thermoplastic | 1.5 mm² | 25 mm² | 16 AWG | 4 AWG | 1.5 mm² | 10 mm² | 16 AWG | 8 AWG | 0.5 mm² | 4 mm² | 18 (unece.unit.AWG) | 14 (unece.unit.AWG) | 2 N·m | 3 N·m | 2 conductors connection (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.) Permitted combination possibilities of connection terminals are indicated in the operating manual. |
Dimensions
Width | Width in Inches | Length | Length in Inches | Mounting Depth | Mounting Depth in Inches | Weight | Weight in Lbs |
---|---|---|---|---|---|---|---|
83 mm | 3.27 in | 165 mm | 6.5 in | 138.3 mm | 5.44 in | 1.3 kg | 2.867 lb |
Mounting / Installation
Tightening Torque | Tightening Torque in lbf-in | Auxiliary Contact Tightening Torque | Auxiliary Contact Tightening Torque in lbf-in |
---|---|---|---|
2-3 N·m | 17.7 ... 26.6 lbf-in | 0.4 – 0.6 N·m | 3.5 ... 5.3 lbf-in |
Technical Drawings
(Drawings are subject to change)
Diagram 1: Shows the auxiliary contacts configuration: 2 poles, 1 changeover auxiliary contact + 1 error signal contact.
Diagram 2: Trip characteristic curve (limit curve from cold state) for AC and DC, showing multiples of rated current (I/In) versus time in seconds and minutes. The characteristic is labeled 'B'.
Diagram 3: Overall dimensions (all dimensions in mm [inches]). The diagram shows the width, length, mounting depth, and indicates the product is 3 division units.
Accessories
Quadruple Locking Device
A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.
Description | Article No. |
---|---|
Quadruple locking device for individual locking with up to 4 cylinder locks. | 227232 |
Fixing Kit
Description | Article No. |
---|---|
A fixing kit for mounting the component on a mounting plate without a DIN rail. | 276618 |
Cylinder Lock
Description | Article No. |
---|---|
For locking (Ø 3 shackle) | 107115 |
Subject to change in technical characteristics, dimensions, weight, construction types, and delivery possibilities. Figures are for indicative purposes only.