R. STAHL 8530/1-MCB-STA102-B16-000-2 Line Protection Circuit Breaker
Article Number: 293918
Product Overview
The R. STAHL 8530 series line protection circuit breakers (MCBs) offer robust current limitation for short circuits with high switching capacities of 10, 15, or 25 kA. These components are designed for minimal line load and high selectivity with upstream fuses. They feature a modular design, are available in 1 to 4-pole versions, and support nominal currents from 0.5 to 63 A. The maximum installation capacity is 4.5 installation units (UP).
Key features include:
- Switch-disconnector function according to EN 60947-2
- Energy limitation class 3
- Easy replacement or system extension due to modular design
- Simple mounting by clipping onto a DIN rail in Ex e enclosures
- Fixed magneto-thermal releases
- Ergonomic operating lever for safe operation and shutdown
- Padlock protection (accessories) prevents re-operation during maintenance
Technical Characteristics
Explosion Protection
Application Area (Zones) | 1, 2 |
---|---|
Application Area (Zones) Note | Usable in Zone 21 / 22 with Ex tb / tc enclosure protection |
IECEx Gas Certificate | IECEX FMG 19.0029U |
IECEx Gas Explosion Protection | Ex db eb IIC Gb |
ATEX Gas Certificate | FM19ATEX0191U |
ATEX Gas Explosion Protection | II 2G Ex db eb IIC Gb |
Certificates | ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM) |
Certificate of Conformity | ATEX Conformity Certificate (ATEX) |
Electrical Characteristics
Rated Operational Voltage AC | 230/400 V |
---|---|
Rated Service Current | 16 A |
Frequency | 50/60 Hz |
Rated Switching Capacity | 10 kA |
Electrical Service Life | 2 x 10⁴ |
Mechanical Service Life | 2 x 10⁴ |
1st Auxiliary Function | None |
Voltage 1st Auxiliary Function AC | - |
Max. Current 1st Auxiliary Function | - |
2nd Auxiliary Function | None |
Max. Voltage 2nd Auxiliary Function DC | - |
Tripping Characteristic | B |
Number of Poles | 2 poles |
Ambient Conditions
Ambient Temperature | -40 °C ... 70 °C (-40 °F ... 158 °F) |
---|---|
Ambient Temperature Note | Different ambient temperatures based on current certificates, upon request |
Mechanical Characteristics
Degree of Protection (IP) (IEC 60529) | IP2X |
---|---|
Housing Material | Thermoplastic |
Minimum Connection Terminal Size | 1.5 mm² |
Maximum Connection Terminal Size | 25 mm² |
Minimum AWG Connection Terminal Size | 16 AWG |
Maximum AWG Connection Terminal Size | 4 AWG |
Connection Terminal Size 2 Min. | 1.5 mm² |
Connection Terminal Size 2 Max. | 10 mm² |
Connection Terminal Size 2 AWG Min. | 16 AWG |
Connection Terminal Size 2 AWG Max. | 8 AWG |
Minimum Tightening Torque | 2 N·m |
Maximum Tightening Torque | 3 N·m |
Connection Terminal Note | 2-conductor connection (upper and lower terminals simultaneously): Upper and lower terminals max. 16 / 10 mm² (Connection can be made with a maximum cross-section difference between the upper and lower terminals.) |
Allowed combination possibilities for connection terminals are indicated in the operating manual. | |
Width | 65 mm (2.56 in) |
Length | 165 mm (6.5 in) |
Mounting Depth | 138.3 mm (5.44 in) |
Weight | 1 kg (2.205 lb) |
Mounting / Installation
Tightening Torque | 2-3 N·m (17.7 ... 26.6 lbf·in) |
---|---|
Auxiliary Contact Tightening Torque | 0.4-0.6 Nm (3.5 ... 5.3 lbf·in) |
Technical Drawings and Diagrams
Tripping Characteristic Curve: The document includes a graph illustrating the tripping characteristic curve from a cold state for AC and DC, with the tripping characteristic labeled as 'B'. The x-axis represents multiples of the rated current (I/In), and the y-axis represents time in seconds and minutes.
Overall Dimensions: A diagram shows the overall dimensions of the circuit breaker in millimeters (with inches in parentheses). Key dimensions include:
- Width: 65 mm [2.56 in]
- Height: 165 mm [6.50 in]
- Depth: 138.3 mm [5.44 in]
- Unit dimensions: 8530/1; 2 division units
Accessories
Quadruple Locking Device: A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks. Article Number: 227232.
Fixing Kit: A kit for fixing the component onto a mounting plate without a DIN rail. Article Number: 276618.
Cylinder Lock: For locking (shackle Ø 3). Article Number: 107115.