R. STAHL 8530/1-MCB-STA102-C40-000-2 Circuit Breaker
Article Number: 293975
Product Overview
The R. STAHL 8530/1-MCB-STA102-C40-000-2 circuit breaker is part of the system technology components. It is designed for use in hazardous environments and offers good current limitation in case of short circuits with a high breaking capacity of 10, 15, or 25 kA. This reduces the load on electrical lines and provides high selectivity with respect to upstream fuses. The modules feature a modular design, are available in 1 to 4-pole models, and support nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.
Key Features:
- Disconnector function according to EN 60947-2
- Energy limitation class 3
- Simple replacement or expansion of installations due to modular design
- Easy mounting via DIN mounting rail in Ex e enclosures
- Thermally and magnetically tripped
- Ergonomic operating lever for safe connection and disconnection
- Protection against re-closing during maintenance using padlocks (Accessories)
Technical Data
Explosion Protection
Parameter | Value |
---|---|
Applications (zones) | 1, 2 |
Applications (zones) Note | Can be used in zones 21/22 with protection by Ex tb/tc enclosure |
IECEX gas certification | IECEx FMG 19.0029U |
IECEx Gas Explosion Protection | Ex db eb IIC Gb |
ATEX gas certification | FM19ATEX0191U |
ATEX Gas Explosion Protection | II 2 G Ex db eb IIC Gb |
Certifications | ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM) |
Certificate of Conformity | Certificate of Conformity (ATEX) |
Electrical Data
Parameter | Value |
---|---|
Rated operating voltage AC | 230/400 V |
Rated operating current | 40 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 104 |
Mechanical service life | 2 x 104 |
1st Auxiliary function | none |
1st Auxiliary function voltage AC | - |
Max. current 1st auxiliary function | - |
2nd Auxiliary function | none |
Max. voltage 2nd aux. function CC | - |
Trip characteristic | C |
Number of poles | 2-pole |
Environmental Conditions
Parameter | Value |
---|---|
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature | -40°F ... +158°F |
Ambient temperature Note | Divergent ambient temperatures based on valid certificates upon request |
Mechanical Data
Parameter | Value |
---|---|
Degree of protection (IP) (IEC 60529) | IP2X |
Enclosure material | Thermoplastic |
Connection terminal cross-section min. | 1.5 mm² |
Connection terminal cross-section max. | 25 mm² |
Connection terminal AWG min. | 16 AWG |
Connection terminal AWG max. | 4 AWG |
Connection terminal 2 cross-section min. | 1.5 mm² |
Connection terminal 2 cross-section max. | 10 mm² |
Connection terminal 2 AWG min. | 16 AWG |
Connection terminal 2 AWG max. | 8 AWG |
Minimum tightening torque | 2 N·m |
Maximum tightening torque | 3 N·m |
Connection terminal Note | 2 conductor connections (upper and lower chamber simultaneously): Lower and upper chamber max. 16 / 10 mm² (only one cross-sectional difference between the upper and lower chamber can be connected). Permitted connection cross-section combinations are shown in the user instructions. |
Width | 65 mm |
Mounting width in inches | 2.56 in |
Length | 165 mm |
Length in inches | 6.5 in |
Installation depth | 138.3 mm |
Installation depth in inches | 5.44 in |
Weight | 1 kg |
Weight in lbs | 2.205 lb |
Mounting / Installation
Parameter | Value |
---|---|
Tightening torque | 2-3 N·m |
Tightening torque lbf·in | 17.7 ... 26.6 lbf·in |
Auxiliary contact tightening torque | 0.4–0.6 Nm |
Auxiliary contact tightening torque lbf·in | 3.5 ... 5.3 lbf·in |
Technical Diagrams
Technical Diagrams - Subject to change
Trip Characteristic C: A graph shows the trip time in seconds and minutes against multiples of the rated current (I/In). The curve illustrates the tripping behavior for a C-type characteristic, indicating the time it takes for the breaker to trip based on the overcurrent level. The graph includes a limit curve from the cold state.
Measurement Diagram (all dimensions in [inches]): This diagram provides the overall dimensions of the circuit breaker, including width, depth, and height, with both metric and imperial units indicated. It also shows the mounting dimensions and details related to the pole configuration.
Accessories
- Cylinder Lock: For blocking (shackle Ø 3). Part Number: 107115. This accessory allows for the physical locking of the circuit breaker.
- Fixing Kit: A set of fixings for mounting the component on a mounting plate without a top-hat rail. Part Number: 276618.
- Quadruple Immobilization Device: Locking pliers / labeling device for individual component locking using up to 4 cylinder locks. Part Number: 227232.
R. STAHL reserves the right to modify technical data, dimensions, weights, constructions, and delivery options.