Components for system solutions
MCB Miniature circuit breaker
Model: 8530/1-MCB-STA102-C40-500-3 | Art. No.: 272140
Product Overview
The R. STAHL 8530 series miniature circuit breakers are overcurrent devices designed for robust system solutions. They offer excellent current limiting for short circuits and a high switching capacity of 10, 15, or 25 kA, resulting in reduced load on cables and improved selectivity for upstream fuses. These components feature a modular design, available in 1- to 4-pole versions, with rated currents from 0.5-63 A. The maximum installation capacity is 4.5 subunits.
Key Features:
- Isolation function in accordance with EN60947-2
- Energy limitation class 3
- Simple replacement or expansion of systems due to modular design
- Easy installation: snaps onto the mounting rail in Ex e enclosures
- Non-adjustable thermal and magnetic releases
- Ergonomically shaped operating lever for safe switching
- Padlocks (accessories) prevent accidental switching on during maintenance
Explosion Protection:
- Application range (zones): 1, 2
- Application range (Zone) note: For use in Zone 21/22 when protected by Ex tb/tc enclosure
- IECEx gas certificate: IECEx FMG 19.0029U
- IECEx gas explosion protection: Ex db eb IIC Gb
- ATEX gas certificate: FM19ATEX0191U
- ATEX gas explosion protection: II 2 G Ex db eb IIC Gb
- Certificates: ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
- Declaration of conformity: Certificate of conformity (ATEX), China (CCC)
Technical Data
Electrical Data
Rated operational voltage AC | 230/400 V |
Rated operational current | 40 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 104 |
Mechanical service life | 2 x 104 |
1st auxiliary function | Auxiliary contact 1 change-over contact + fault signal contact 1 change-over contact |
1st auxiliary function for AC rated voltage | 230 V |
1st auxiliary function for rated current max. | 2 A |
2nd auxiliary function | without |
2nd auxiliary function voltage max. DC | - |
Tripping characteristic | C |
No. of poles | 2-pole |
Ambient Conditions
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature note | Deviating ambient temperatures based on current certificates available on request |
Mechanical Data
Degree of protection (IP) (IEC 60529) | IP2X |
Enclosure material | Thermoplast |
Connection cross section min. | 1.5 mm² |
Connection cross-section max. | 25 mm² |
Connection cross-section AWG min. | 16 AWG |
Connection cross-section AWG max. | 4 AWG |
Connection cross-section 2 min. | 1.5 mm² |
Connection cross-section 2 max. | 10 mm² |
Connection cross-section 2 AWG min. | 16 AWG |
Connection cross-section 2 AWG max. | 8 AWG |
Min. aux. cont. con. cr.-sect. | 0.5 mm² |
Max. aux. cont. conn. cr.-sec. | 4 mm² |
Min. aux. co. con. cr.-se. AWG | 18 (unece.unit.AWG) |
Connection cross-section of auxiliary contact AWG max. | 14 (unece.unit.AWG) |
Min. tightening torque | 2 N·m |
Max. tightening torque | 3 N·m |
Connection cross-section note | 2-conductor connection (upper and lower chamber at the same time): upper and lower chamber max. 16 / 10 mm² (A maximum difference of one cross section may be clamped between the upper and lower chamber.) The permitted combinations of connection cross-sections can be found in the operating instructions. |
Dimensions
Width | 83 mm |
Width, inches | 3.27 in |
Length | 165 mm |
Length in inches | 6.5 in |
Mounting depth | 138.3 mm |
Mounting depth in inches | 5.44 in |
Weight | 1.3 kg |
Weight | 2.867 lb |
Mounting / Installation
Tightening torque | 2-3 N·m |
Tightening torque lbf·in | 17.7 to 26.6 lbf·in |
Tightening torque auxiliary contact | 0.4-0.6 N·m |
Tightening torque auxiliary contact lbf·in | 3.5 to 5.3 lbf·in |
Technical Drawings
Tripping Characteristic C:
A graphical representation shows the tripping time in minutes and seconds against multiples of the rated current for both AC and DC. The curves indicate the tripping behavior from a cold state for tripping characteristic C.
Dimensional Drawings:
Diagrams illustrate the dimensions of the circuit breaker in millimeters and inches, including width, length, and mounting depth. The diagrams also show the connection terminals and the overall structure of the 2-pole unit.
Accessories
4-way locking device
A lock-out/tag-out hasp for individually locking the component using up to four cylinder locks.
- Art. No.: 227232
Cylinder lock
For closing (bracket Ø 3)
- Art. No.: 107115
Fastening set
A fastening set for securing the component on the mounting plate without a DIN rail.
- Art. No.: 276618
Note: R. STAHL reserves the right to make alterations to technical data, dimensions, weights, designs, and products without notice. Illustrations are not binding.