R. STAHL 8530/1-MCB-STA102-C40-500-3 Circuit Breaker

Article No. 272140

Product Features

Technical Data

Explosion Protection

Applications (zones) 1, 2
Applications (zones) Note Can be used in zones 21/22 with protection by Ex tb/tc enclosure
IECEX gas certification IECEX FMG 19.0029U
IECEx gas explosion protection Ex db eb IIC Gb
Homologation ATEX gas FM19ATEX0191U
ATEX gas explosion protection II 2 G Ex db eb IIC Gb
Certifications ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM)
Certificate of conformity Certificate of conformity (ATEX), China (CCC)

Electrical Data

Rated operating voltage AC 230/400 V
Rated operating current 40 A
Frequency 50/60 Hz
Rated switching capacity 10 kA
Electrical service life 104
Mechanical service life 2 x 104
1st auxiliary function Auxiliary contact 1 changeover + Error signal contact 1 changeover
Voltage 1st auxiliary function AC 230 V
Max. current 1st auxiliary function 2 A
2nd auxiliary function None
Max. voltage 2nd auxiliary function DC -
Tripping characteristic C
Number of poles 2-pole

Technical Diagrams and Dimensions

The R. STAHL 8530 series circuit breakers offer good current limitation in case of short circuits and a high breaking capacity of 10, 15, or 25 kA. This results in reduced stress on electrical lines and high selectivity with respect to the upstream fuses. The modules are designed with a modular structure and are available in 1 to 4-pole versions for nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.

Technical Drawings:

Diagram 1: Shows the tripping characteristic curve (I/In) over time (seconds/minutes). The curve indicates the tripping time based on multiples of the rated current for a Type C characteristic.

Diagram 2: Shows the dimensions of the 8530/1; 3 division units. Key dimensions include:

Diagram 3: Illustrates the 8530/1; 3 division units with detailed measurements in millimeters and inches, showing mounting dimensions and overall size.

Diagram 4: Shows the 8530/1, 3 division units, and the 8530/1, 1 division unit, with their respective dimensions.

Environmental Conditions

Ambient temperature -40 °C ... 70 °C
Ambient temperature -40 °F ... 70 °C
Ambient temperature -40 °C ... 158 °F
Ambient temperature -40 °F ... +158°F
Ambient temperature Note Divergent ambient temperatures based on valid certificates upon request

Mechanical Data

Degree of protection (IP) (IEC 60529) IP2X
Enclosure material Thermoplastic
Connection terminal cross-section min. 1.5 mm²
Connection terminal cross-section max. 25 mm²
Connection terminal AWG min. 16 AWG
Connection terminal AWG max. 4 AWG
Connection terminal 2 cross-section min. 1.5 mm²
Connection terminal 2 cross-section max. 10 mm²
Connection terminal 2 AWG min. 16 AWG
Connection terminal 2 AWG max. 8 AWG
Connection terminal HIKO cross-section min. 0.5 mm²
Connection terminal HIKO cross-section max. 4 mm²
Connection terminal HIKO AWG min. 18 (unece.unit.AWG)
Connection terminal HIKO AWG max. 14 (unece.unit.AWG)
Tightening torque min. 2 N·m
Tightening torque max. 3 N·m
Connection terminal Note 2 conductor connections (upper and lower chamber simultaneously): lower chamber and upper chamber max. 16 / 10 mm² (only one cross-section difference between the upper and lower chamber can be connected.) Permitted connection cross-section combinations are listed in the operating instructions.

Dimensions

Width 83 mm
Mounting width in inches 3.27 in
Length 165 mm
Length inches 6.5 in
Installation depth 138.3 mm
Installation depth inches 5.44 in
Weight 1.3 kg
Weight 2.867 lb

Mounting / Installation

Tightening torque 2–3 N·m
Tightening torque lbf in 17.7 ... 26.6 lbf-in
Tightening torque auxiliary contact 0.4–0.6 N·m
Tightening torque auxiliary contact lbf in 3.5 ... 5.3 lbf in

Accessories

Cylinder lock

For locking (shackle Ø 3) Article No. 107115

Quadruple immobilization device

Locking/tagging tool for individual component locking using up to 4 cylinder locks. Article No. 227232

Fixing kit

A set of fixings for mounting the component on the mounting plate without a top-hat rail. Article No. 276618

R. STAHL reserves the right to modify technical data, dimensions, weights, designs, and delivery options.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta102-c40-500-3-272140-es-es-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL MCB Miniature Circuit Breaker 8530/1-MCB-STA102-C40-500-3: Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-C40-500-3 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C40-000-2 Circuit Breaker - Technical Specifications
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C40-000-2 circuit breaker, including electrical data, environmental conditions, mechanical data, and accessories. Suitable for hazardous environments.
Preview R. STAHL 8530/1-MCB-STA102-B6-500-3 Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-B6-500-3 circuit breaker, including features, electrical data, mechanical data, environmental conditions, and accessories. This document provides comprehensive information for system integrators and engineers.
Preview R. STAHL 8530/1-MCB-STA102-C40-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C40-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-B25-500-3 Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-B25-500-3 circuit breaker, including electrical data, mechanical data, environmental conditions, and accessories. This product is designed for systems requiring explosion protection.
Preview R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA102-C40-500-3 - Technical Data
Detailed technical specifications and features of the R. STAHL LS Miniature Circuit Breaker, model 8530/1-MCB-STA102-C40-500-3, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C6-500-3 Miniature Circuit Breaker Technical Specification
Detailed technical specifications, features, and certifications for the R. STAHL 8530/1-MCB-STA102-C6-500-3 Miniature Circuit Breaker (MCB), including explosion protection, electrical data, mechanical dimensions, and available accessories.
Preview R. STAHL 8530/1-MCB-STA102-B20-000-2 Circuit Breaker - Technical Specifications
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B20-000-2 circuit breaker, including electrical data, environmental conditions, mechanical specifications, and accessories. Suitable for use in hazardous areas.