R. STAHL 8530/1-MCB-STA102-C40-500-3 Circuit Breaker
Article No. 272140
Product Features
- Disconnecting function according to EN 60947-2
- Energy limitation class 3
- Simple substitution or expansion of installations thanks to the modular design of the protection switch
- Easy mounting via DIN mounting rail in Ex e enclosures
- Fixed thermal and magnetic tripping adjustment
- Ergonomic operating lever ensures safe connection and disconnection
- Protection against re-connection during maintenance using padlocks (Accessories)
Technical Data
Explosion Protection
Applications (zones) | 1, 2 |
Applications (zones) Note | Can be used in zones 21/22 with protection by Ex tb/tc enclosure |
IECEX gas certification | IECEX FMG 19.0029U |
IECEx gas explosion protection | Ex db eb IIC Gb |
Homologation ATEX gas | FM19ATEX0191U |
ATEX gas explosion protection | II 2 G Ex db eb IIC Gb |
Certifications | ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM) |
Certificate of conformity | Certificate of conformity (ATEX), China (CCC) |
Electrical Data
Rated operating voltage AC | 230/400 V |
Rated operating current | 40 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 104 |
Mechanical service life | 2 x 104 |
1st auxiliary function | Auxiliary contact 1 changeover + Error signal contact 1 changeover |
Voltage 1st auxiliary function AC | 230 V |
Max. current 1st auxiliary function | 2 A |
2nd auxiliary function | None |
Max. voltage 2nd auxiliary function DC | - |
Tripping characteristic | C |
Number of poles | 2-pole |
Technical Diagrams and Dimensions
The R. STAHL 8530 series circuit breakers offer good current limitation in case of short circuits and a high breaking capacity of 10, 15, or 25 kA. This results in reduced stress on electrical lines and high selectivity with respect to the upstream fuses. The modules are designed with a modular structure and are available in 1 to 4-pole versions for nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.
Technical Drawings:
Diagram 1: Shows the tripping characteristic curve (I/In) over time (seconds/minutes). The curve indicates the tripping time based on multiples of the rated current for a Type C characteristic.
Diagram 2: Shows the dimensions of the 8530/1; 3 division units. Key dimensions include:
- Width: 83 mm [3.27 in]
- Height: 165 mm [6.50 in]
- Installation Depth: 138.3 mm [5.44 in]
- Overall width of the unit is 3 division units.
Diagram 3: Illustrates the 8530/1; 3 division units with detailed measurements in millimeters and inches, showing mounting dimensions and overall size.
Diagram 4: Shows the 8530/1, 3 division units, and the 8530/1, 1 division unit, with their respective dimensions.
Environmental Conditions
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 70 °C |
Ambient temperature | -40 °C ... 158 °F |
Ambient temperature | -40 °F ... +158°F |
Ambient temperature Note | Divergent ambient temperatures based on valid certificates upon request |
Mechanical Data
Degree of protection (IP) (IEC 60529) | IP2X |
Enclosure material | Thermoplastic |
Connection terminal cross-section min. | 1.5 mm² |
Connection terminal cross-section max. | 25 mm² |
Connection terminal AWG min. | 16 AWG |
Connection terminal AWG max. | 4 AWG |
Connection terminal 2 cross-section min. | 1.5 mm² |
Connection terminal 2 cross-section max. | 10 mm² |
Connection terminal 2 AWG min. | 16 AWG |
Connection terminal 2 AWG max. | 8 AWG |
Connection terminal HIKO cross-section min. | 0.5 mm² |
Connection terminal HIKO cross-section max. | 4 mm² |
Connection terminal HIKO AWG min. | 18 (unece.unit.AWG) |
Connection terminal HIKO AWG max. | 14 (unece.unit.AWG) |
Tightening torque min. | 2 N·m |
Tightening torque max. | 3 N·m |
Connection terminal Note | 2 conductor connections (upper and lower chamber simultaneously): lower chamber and upper chamber max. 16 / 10 mm² (only one cross-section difference between the upper and lower chamber can be connected.) Permitted connection cross-section combinations are listed in the operating instructions. |
Dimensions
Width | 83 mm |
Mounting width in inches | 3.27 in |
Length | 165 mm |
Length inches | 6.5 in |
Installation depth | 138.3 mm |
Installation depth inches | 5.44 in |
Weight | 1.3 kg |
Weight | 2.867 lb |
Mounting / Installation
Tightening torque | 2–3 N·m |
Tightening torque lbf in | 17.7 ... 26.6 lbf-in |
Tightening torque auxiliary contact | 0.4–0.6 N·m |
Tightening torque auxiliary contact lbf in | 3.5 ... 5.3 lbf in |
Accessories
Cylinder lock
For locking (shackle Ø 3) | Article No. 107115 |
Quadruple immobilization device
Locking/tagging tool for individual component locking using up to 4 cylinder locks. | Article No. 227232 |
Fixing kit
A set of fixings for mounting the component on the mounting plate without a top-hat rail. | Article No. 276618 |
R. STAHL reserves the right to modify technical data, dimensions, weights, designs, and delivery options.
Related Documents
![]() |
R. STAHL MCB Miniature Circuit Breaker 8530/1-MCB-STA102-C40-500-3: Technical Specifications Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-C40-500-3 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. |
![]() |
R. STAHL 8530/1-MCB-STA102-C40-000-2 Circuit Breaker - Technical Specifications Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C40-000-2 circuit breaker, including electrical data, environmental conditions, mechanical data, and accessories. Suitable for hazardous environments. |
![]() |
R. STAHL 8530/1-MCB-STA102-B6-500-3 Circuit Breaker - Technical Specifications Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-B6-500-3 circuit breaker, including features, electrical data, mechanical data, environmental conditions, and accessories. This document provides comprehensive information for system integrators and engineers. |
![]() |
R. STAHL 8530/1-MCB-STA102-C40-500-3 Line Protection Circuit Breaker Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C40-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories. |
![]() |
R. STAHL 8530/1-MCB-STA102-B25-500-3 Circuit Breaker - Technical Specifications Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-B25-500-3 circuit breaker, including electrical data, mechanical data, environmental conditions, and accessories. This product is designed for systems requiring explosion protection. |
![]() |
R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA102-C40-500-3 - Technical Data Detailed technical specifications and features of the R. STAHL LS Miniature Circuit Breaker, model 8530/1-MCB-STA102-C40-500-3, including explosion protection, electrical data, mechanical data, and accessories. |
![]() |
R. STAHL 8530/1-MCB-STA102-C6-500-3 Miniature Circuit Breaker Technical Specification Detailed technical specifications, features, and certifications for the R. STAHL 8530/1-MCB-STA102-C6-500-3 Miniature Circuit Breaker (MCB), including explosion protection, electrical data, mechanical dimensions, and available accessories. |
![]() |
R. STAHL 8530/1-MCB-STA102-B20-000-2 Circuit Breaker - Technical Specifications Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B20-000-2 circuit breaker, including electrical data, environmental conditions, mechanical specifications, and accessories. Suitable for use in hazardous areas. |