R. STAHL Circuit Breaker 8530/1-MCB-STA102-C25-000-2

Article No.: 293973

Key Features

Product Overview

The R. STAHL 8530 series circuit breakers offer excellent current limitation in case of short circuits and high breaking capacity of 10, 15, or 25 kA. This results in reduced load on electrical lines and high selectivity with respect to upstream fuses. The modules feature a modular structure and are available in 1 to 4 pole versions for nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.

Technical Data

Explosion Protection

Applications (Zones)1, 2
Applications (Zones) NoteCan be used in zones 21/22 with Ex tb/tc enclosure protection
IECEX Gas HomologationIECEX FMG 19.0029U
IECEx Gas Explosion ProtectionEx db eb IIC Gb
ATEX Gas HomologationFM19ATEX0191U
ATEX Gas Explosion ProtectionII 2 G Ex db eb IIC Gb
CertificationsATEX (FM), Brazil (ULB), China (CQST), IECEX (FM)
Certificate of ConformityCertificate of Conformity (ATEX)

Electrical Data

Rated Operating Voltage AC230/400 V
Rated Operating Current25 A
Frequency50/60 Hz
Rated Switching Capacity10 kA
Electrical Service Life2 x 104
Mechanical Service Life2 x 104
1st Auxiliary FunctionNone
1st Auxiliary Voltage AC-
Max. Current 1st Auxiliary Function-
2nd Auxiliary FunctionNone
Max. Voltage 2nd Auxiliary DC-
Trip CharacteristicC
Number of Poles2-pole

Environmental Conditions

Ambient Temperature-40 °C ... 70 °C
Ambient Temperature-40 °F ... 158 °F
Ambient Temperature NoteDivergent ambient temperatures based on valid certificates upon request

Mechanical Data

Degree of Protection (IP) (IEC 60529)IP2X
Enclosure MaterialThermoplastic
Minimum Connection Terminal Size1.5 mm²
Maximum Connection Terminal Size25 mm²
Minimum AWG Connection Size16 AWG
Maximum AWG Connection Size4 AWG
Minimum 2nd Connection Terminal Size1.5 mm²
Maximum 2nd Connection Terminal Size10 mm²
Minimum 2nd AWG Connection Size16 AWG
Maximum 2nd AWG Connection Size8 AWG
Minimum Tightening Torque2 N·m
Maximum Tightening Torque3 N·m
Connection Terminal Note2 conductor connections (upper and lower chamber simultaneously): lower and upper chamber max. 16 / 10 mm² (only a maximum cross-sectional difference between the upper and lower chamber can be connected.) Combinations of permitted connection terminal sizes are shown in the user manual.
Width65 mm
Mounting Width in Inches2.56 in
Length165 mm
Length in Inches6.5 in
Installation Depth138.3 mm
Installation Depth in Inches5.44 in
Weight1 kg
Weight in Pounds2.205 lb

Mounting / Installation

Tightening Torque2-3 N·m
Tightening Torque lbf·in17.7 ... 26.6 lbf·in
Auxiliary Contact Tightening Torque0.4–0.6 N·m
Auxiliary Contact Tightening Torque lbf·in3.5 ... 5.3 lbf·in

Technical Diagrams

Technical Diagrams - Subject to change.

Technical diagrams showing tripping characteristics and measurement schemes are available. These include tripping time curves and dimension drawings in millimeters and inches.

Accessories

Cylinder Lock

DescriptionArticle No.
Cylinder lock / label for individual component locking using up to 4 cylinder locks.227232

Fixing Kit

DescriptionArticle No.
A fixing kit for mounting the component on the mounting plate without a top hat rail.276618

R. STAHL reserves the right to modify technical data, dimensions, weights, constructions, and delivery options.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta102-c25-000-2-293973-es-es-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA102-C25-000-2 Circuit Breaker: Technical Specifications and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA102-C25-000-2 line protection circuit breaker, including explosion protection and electrical characteristics.
Preview R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA102-C25-000-2: Technical Data and Features
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C25-000-2 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 1, 2, 21, and 22 hazardous areas.
Preview R. STAHL 8530/1-MCB-STA102-C20-000-2 Circuit Breaker - Technical Specifications and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA102-C20-000-2 circuit breaker, including explosion protection data, electrical characteristics, mechanical data, and installation guidelines.
Preview R. STAHL 8530/1-MCB-STA103-B40-000-3 Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103-B40-000-3 circuit breaker, including electrical data, mechanical data, environmental conditions, and accessories. Suitable for use in hazardous areas.
Preview R. STAHL 8530/1-MCB-STA102-C2-500-3 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C2-500-3 circuit breaker, including explosion protection, electrical data, mechanical dimensions, and accessories. Suitable for use in Ex e enclosures.
Preview R. STAHL 8530/1-MCB-STA103N-C25-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C25-000-4 circuit breaker, including explosion protection data, electrical characteristics, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-B16-000-2 Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-B16-000-2 circuit breaker, including electrical data, environmental conditions, mechanical data, and accessories. Features include IECEx and ATEX gas protection.
Preview R. STAHL 8530/1-MCB-STA103-B6-000-3 Circuit Breaker - Technical Specifications and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA103-B6-000-3 circuit breaker, designed for systems in potentially explosive atmospheres.