R. STAHL LS Leitungsschutzschalter (Miniature Circuit Breaker)

Model: 8530/1-MCB-STA102-C40-000-2

Article Number: 293975

Product Overview

The R. STAHL 8530/1-MCB-STA102-C40-000-2 series of miniature circuit breakers offers excellent current limitation for short circuits and high breaking capacity of 10, 15, or 25 kA. This results in reduced stress on conductors and higher selectivity with upstream fuses. The modules are designed for modularity, available in 1- to 4-pole versions, and for rated currents from 0.5–63 A. The maximum installation capacity is 4.5 modules (TE).

Key features include:

Technical Data

Explosion Protection

Einsatzbereich (Zonen) 1, 2
Einsatzbereich (Zonen) Hinweis Usable in Zone 21 / 22 when protected by enclosure Ex tb / tc
IECEx Bescheinigung Gas IECEx FMG 19.0029U
IECEx Gasexplosionsschutz Ex db eb IIC Gb
ATEX Bescheinigung Gas FM19ATEX0191U
ATEX Gasexplosionsschutz II 2 G Ex db eb IIC Gb
Bescheinigungen ATEX (FM), Brazil (ULB), IECEx (FM), People's Republic of China (CQST)
Konformitätserklärungen Conformity Certificate (ATEX)

Electrical Data

Bemessungsbetriebsspannung AC (Rated operating voltage AC) 230/400 V
Bemessungsbetriebsstrom (Rated operating current) 40 A
Frequenz (Frequency) 50/60 Hz
Bemessungsschaltvermögen (Rated breaking capacity) 10 kA
Elektrische Lebensdauer (Electrical service life) 104
Mechanische Lebensdauer (Mechanical service life) 2 x 104
1. Hilfsfunktion (1st Auxiliary function) ohne (none)
Bemessungsspannung 1. Hilfsfunktion AC (Rated voltage 1st auxiliary function AC) -
Max. Bemessungsstrom 1. Hilfsfunktion (Max. rated current 1st auxiliary function) -
2. Hilfsfunktion (2nd Auxiliary function) ohne (none)
Max. Spannung 2. Hilfsfunktion DC (Max. voltage 2nd auxiliary function DC) -
Auslösecharakteristik (Trip characteristic) C
Polzahl (Number of poles) 2-pole

Umgebungsbedingungen (Environmental Conditions)

Umgebungstemperatur (Ambient temperature) -40 °C ... 70 °C (-40 °F ... 158 °F)
Umgebungstemperatur Hinweis (Ambient temperature note) Deviating ambient temperatures based on current certificates are available upon request.

Mechanische Daten (Mechanical Data)

Schutzart (IP) (IEC 60529) (Degree of protection (IP)) IP2X
Gehäusematerial (Housing material) Thermoplast
Anschlussquerschnitt min. (Connection cross-section min.) 1.5 mm²
Anschlussquerschnitt max. (Connection cross-section max.) 25 mm²
Anschlussquerschnitt AWG min. (Connection cross-section AWG min.) 16 AWG
Anschlussquerschnitt AWG max. (Connection cross-section AWG max.) 4 AWG
Anschlussquerschnitt 2 min. (Connection cross-section 2 min.) 1.5 mm²
Anschlussquerschnitt 2 max. (Connection cross-section 2 max.) 10 mm²
Anschlussquerschnitt 2 AWG min. (Connection cross-section 2 AWG min.) 16 AWG
Anschlussquerschnitt 2 AWG max. (Connection cross-section 2 AWG max.) 8 AWG
Anzugsdrehmoment min. (Tightening torque min.) 2 N·m
Anzugsdrehmoment max. (Tightening torque max.) 3 N·m
Anschlussquerschnitt Hinweis (Connection cross-section note) 2-conductor connection (upper and lower chamber simultaneously): upper and lower chamber max. 16 / 10 mm² (A maximum cross-section difference between the upper and lower chamber is permitted.) The permissible combinations of connection cross-sections can be found in the operating manual.
Breite (Width) 65 mm (2.56 in)
Breite Zoll (Width inches) 2.56 in
Länge (Length) 165 mm (6.50 in)
Länge Zoll (Length inches) 6.5 in
Einbautiefe (Mounting depth) 138.3 mm (5.44 in)
Einbautiefe Zoll (Mounting depth inches) 5.44 in
Gewicht (Weight) 1 kg (2.205 lb)
Gewicht (Weight) 2.205 lb

Montage / Installation (Mounting / Installation)

Anzugsdrehmoment (Tightening torque) 2-3 N·m
Anzugsdrehmoment lbf in (Tightening torque lbf in) 17.7 ... 26.6 lbf·in
Anzugsdrehmoment Hilfskontakt (Tightening torque auxiliary contact) 0.4-0.6 Nm
Anzugsdrehmoment Hilfskontakt Ibf in (Tightening torque auxiliary contact lbf in) 3.5 ... 5.3 lbf·in

Technical Drawing

Trip Characteristic C:

A graph shows tripping time in seconds and minutes versus multiples of the rated current (I/In). The curves represent tripping behavior from a cold state and for AC/DC operation.

Dimensional Drawing (all dimensions in mm [inch]):

Diagrams illustrating the dimensions of the 8530/1, 2-pole unit without auxiliary contact, showing width, depth, and height.

Accessories

Abschließvorrichtung vierfach (Lock-out/Tag-out Device, Quadruple)

A Lock-out/Tag-out device for individually locking the component, allowing up to 4 padlocks.

Description Article Number
Lock-out/Tag-out device for individual locking of the component using up to 4 padlocks. 227232

Befestigungsset (Mounting Set)

A mounting set for attaching the component to the mounting plate without a top-hat rail.

Description Article Number
Mounting set for attaching the component to the mounting plate without a top-hat rail. 276618

Zylinderschloss (Cylinder Lock)

For locking (shackle Ø 3).

Description Article Number
For locking (shackle Ø 3) 107115

Subject to change: Technical data, dimensions, weights, constructions, and delivery options are subject to change. Illustrations are non-binding.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta102-c40-000-2-293975-de-de-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA102-B16-000-2 - Technical Data
Detailed technical specifications and features of the R. STAHL LS Miniature Circuit Breaker, model 8530/1-MCB-STA102-B16-000-2. Includes information on explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C20-000-2 Miniature Circuit Breaker - Technical Data and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA102-C20-000-2 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and installation information.
Preview R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA102-C25-000-2: Technical Data and Features
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C25-000-2 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 1, 2, 21, and 22 hazardous areas.
Preview R. STAHL 8530/1-MCB-STA102-B10-000-2 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-B10-000-2 miniature circuit breaker, including electrical data, explosion protection, mechanical data, and accessories. Features good current limitation, high breaking capacity, and modular design for various applications.
Preview R. STAHL 8530 Series Miniature Circuit Breaker - Technical Data and Specifications
Detailed technical specifications for the R. STAHL 8530 Series Miniature Circuit Breaker (MCB), including explosion protection, electrical data, mechanical data, and accessories. Part number 8530/1-MCB-STA102-C40-000-2, Art. No. 293975.
Preview R. STAHL 8530/1-MCB-STA101-C40-500-2 Miniature Circuit Breaker - Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA101-C40-500-2 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-B16-500-3 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B16-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C1-500-3 Miniature Circuit Breaker - Technical Data and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA102-C1-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and installation information.