R. STAHL Miniature Circuit Breaker - 8530 Series
Model: 8530/1-MCB-STA102-C40-000-2
Article Number: 293975
Product Overview
The R. STAHL 8530 series miniature circuit breakers (MCBs) are overcurrent devices designed for robust protection. They offer excellent current limiting for short circuits and a high switching capacity of 10, 15, or 25 kA, ensuring reduced load on cables and high selectivity for upstream fuses. These components feature a modular design, available in 1- to 4-pole versions, with rated currents ranging from 0.5 A to 63 A. The maximum installation capacity is 4.5 subunits.
Key features include:
- Isolation function in accordance with EN60947-2
- Energy limitation class 3
- Simple replacement or expansion of systems due to modular design
- Easy installation: snaps onto the mounting rail in Ex e enclosures
- Non-adjustable thermal and magnetic releases
- Ergonomically shaped operating lever for safe switching
- Optional padlocks for protection against accidental switching during maintenance
Technical Data
Explosion Protection
Parameter | Value |
---|---|
Application range (zones) | 1, 2 |
Application range (Zone) note | For use in Zone 21/22 when protected by Ex tb/tc enclosure |
IECEx gas certificate | IECEx FMG 19.0029U |
IECEx gas explosion protection | Ex db eb IIC Gb |
ATEX gas certificate | FM19ATEX0191U |
ATEX gas explosion protection | II 2 G Ex db eb IIC Gb |
Certificates | ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM) |
Declaration of conformity | Certificate of conformity (ATEX) |
Electrical Data
Parameter | Value |
---|---|
Rated operational voltage AC | 230/400 V |
Rated operational current | 40 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 104 |
Mechanical service life | 2 x 104 |
1st auxiliary function | without |
1st auxiliary function for AC rated voltage | - |
1st auxiliary function for rated current max. | - |
2nd auxiliary function | without |
2nd auxiliary function voltage max. DC | - |
Tripping characteristic | C |
No. of poles | 2-pole |
Ambient Conditions
Parameter | Value |
---|---|
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature note | Deviating ambient temperatures based on current certificates available on request |
Mechanical Data
Parameter | Value |
---|---|
Degree of protection (IP) (IEC 60529) | IP2X |
Enclosure material | Thermoplast |
Connection cross section min. | 1.5 mm² |
Connection cross-section max. | 25 mm² |
Connection cross-section AWG min. | 16 AWG |
Connection cross-section AWG max. | 4 AWG |
Connection cross-section 2 min. | 1.5 mm² |
Connection cross-section 2 max. | 10 mm² |
Connection cross-section 2 AWG min. | 16 AWG |
Connection cross-section 2 AWG max. | 8 AWG |
Min. tightening torque | 2 N·m |
Max. tightening torque | 3 N·m |
Connection cross-section note | 2-conductor connection (upper and lower chamber at the same time): upper and lower chamber max. 16/10 mm² (A maximum difference of one cross section may be clamped between the upper and lower chamber.) The permitted combinations of connection cross-sections can be found in the operating instructions. |
Width | 65 mm |
Width, inches | 2.56 in |
Length | 165 mm |
Length in inches | 6.5 in |
Mounting depth | 138.3 mm |
Mounting depth in inches | 5.44 in |
Weight | 1 kg |
Weight | 2.205 lb |
Mounting / Installation
Parameter | Value |
---|---|
Tightening torque | 2-3 N·m |
Tightening torque lbf in | 17.7 to 26.6 lbf-in |
Tightening torque auxiliary contact | 0.4 - 0.6 N·m |
Tightening torque auxiliary contact lbf in | 3.5 to 5.3 lbf in |
Technical Drawings
Tripping Characteristic C:
The document includes a graph illustrating the tripping time in seconds against the multiple of rated current for tripping characteristic C, for both AC and DC circuits. The graph shows curves for cold state tripping.
Dimensional Drawings:
Detailed dimensional drawings are provided in millimeters and inches, showing the front, side, and top views of the 2-pole miniature circuit breaker without auxiliary contacts. Key dimensions include width (65 mm / 2.56 in), length (165 mm / 6.50 in), and mounting depth (138.3 mm / 5.44 in).
Accessories
4-way locking device
Description: A lock-out/tag-out hasp for individually locking the component using up to four cylinder locks.
Article Number: 227232
Cylinder lock
Description: For closing (bracket Ø 3)
Article Number: 107115
Fastening set
Description: A fastening set for fastening the component on the mounting plate without a DIN rail.
Article Number: 276618
R. STAHL reserves the right to make alterations to the technical data, dimensions, weights, designs, and products available without notice. The illustrations cannot be considered binding.