R. STAHL Isolator Barriers
Loop-powered binary output
Ex i field circuit
9276/10-24-48-00k Art. No. 261446
Key Features
- A comprehensive portfolio for a wide range of solenoid valves
- Space savings due to a slim design – 12.5 mm wide
- Can be used for functional safety levels up to SIL 3 (IEC/EN 61508)
Series 9276 digital outputs issue signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs.
Certifications: ATEX (IBE), Canada (UL), China (CQM), IECEx (IBE), SIL (exida), USA (UL), DNV, ATEX (EUK), China (CCC)
Technical Data
Explosion Protection
Application range (zones) | 2 |
Ex interface zone | 0, 1, 2, 20, 21, 22 |
IECEX gas certificate | IECEx IBE 17.0045X |
IECEx gas explosion protection | Ex ec [ia Ga] IIC T4 Gc |
IECEx dust certificate | IECEx IBE 17.0045X |
IECEx dust explosion protection | [Ex ia Da] IIIC |
IECEX firedamp certificate | IECEx IBE 17.0045X |
IECEx firedamp protection | [Ex ia Ma] I |
ATEX gas certificate | IBEXU 17 ATEX 1153 X |
ATEX gas explosion protection | II 3 (1) G Ex ec [ia Ga] IIC T4 Gc |
ATEX dust certificate | IBEXU 17 ATEX 1153 X |
ATEX dust explosion protection | II (1) D [Ex ia Da] IIIC |
ATEX firedamp certificate | IBEXU 17 ATEX 1153 X |
ATEX firedamp protection | I (M1) [Ex ia Ma] I |
cULus certificate | E81680 |
Marking cULus | Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, AEx/Ex nA Group IIC; AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC; T4 any mounting pos. Ta = 60°C |
Safety Data
Max. power P₀ | 697 mW |
Max. permissible external capacitance C/C for IIC | 0.085 μF |
Max. permissible external inductance L/La for IIC | 4 mH |
Max. permissible external capacitance C/C for IIB | 0.663 µF |
Max. permissible external inductance L/La for IIB | 17 mH |
Max. permissible external capa.IIA | 2.2 μF |
Max. permissible external inductance L₀ for IIA | 35 mH |
Max. perm. ext. capacit. IIIC | 0.663 µF |
Max. permis. ext. induct. IIIC | 17 mH |
Max. permissible ext. capac. I | 2.2 μF |
Max. permissible external inductance L₀ for I | 35 mH |
Internal capacitance | Negligible |
Internal inductance | Negligible |
Safety-related max. voltage | 253 V AC |
Intrinsically safe limiting values inductance L/capacitance C₀
20 mH | 10 mH | 5 mH | 1 mH | 0.100 mH | |
IIC | C₀ [µF] 0.068 μF | 0.068 μF | 0.068 μF | 0.079 μF | 0.108 μF |
IIB | L₀ [mH] 10 mH | 5 mH | 1 mH | 0.100 mH | |
C₀ [µF] 0.250 μF | 0.250 μF | 0.350 μF | 0.663 µF | ||
IIA | L₀ [mH] 20 mH | 5 mH | 1 mH | 0.100 mH | |
C₀ [µF] 0.440 μF | 0.440 μF | 0.680 μF | 0.960 μF | ||
IIIC | L₀ [mH] 10 mH | 5 mH | 1 mH | 0.100 mH | |
C₀ [µF] 0.250 μF | 0.250 μF | 0.350 μF | |||
I | L₀ [mH] 20 mH | 5 mH | 1 mH | 0.100 mH | |
C₀ [µF] 0.440 μF | 0.440 μF | 0.680 μF | 0.960 μF |
Functional Safety
SIL | 3 |
HFT | 0 |
SFF | 100% |
Lambda SD | 0 FIT |
Lambda SU | 50 FIT |
Lambda DD | 0 FIT |
Lambda DU | 0 FIT |
Electrical Data
Number of channels | 1 |
Auxiliary power | without |
Max. power dissipation | 1.41 W |
Polarity reversal protection | Yes |
Galvanic Isolation
Test voltage as per standard | EN IEC 60079-11 |
Galvanic separation Ex i output to input | 375 V AC peak value |
Input
Input voltage for ON | 15 – 30 V |
Input voltage for OFF | 0 – 5 V |
Output
Output open-circuit voltage U₂ | 24 V |
Max. output current Iₐ max | 48 mA |
Output internal resistance Rᵢ | 275.5 Ω |
Switching delay ON/OFF | ≤ 20 ms |
Switching delay OFF/ON | ≤ 20 ms |
Response time output | 20 ms |
Switching state indication | Yellow "STAT" LED |
Ambient Conditions
Ambient temperature °C | -40 °C ... 60 °C |
Ambient temperature °F | -40 °F ... +140 °F |
Storage temperature °C | -40 °C ... 80 °C |
Storage temperature °F | -40 °F ... +176 °F |
Max. relative humidity | 10 to 95% |
Use at the height of | < 2000 m |
Electromagnetic compatibility | EN 61326-1 Use in industrial environment; Immunity according to EN 61000-6-2; Interference emission to EN 61000-6-4 |
Mechanical Data
Degree of protection (IP) | IP30 |
Degree of protection (IP) terminals | IP20 |
Fire resistance (UL 94) | V0 |
Enclosure material | Polyamide |
Grid dimension | 12.5 mm |
Width | 12.5 mm |
Width, inches | 0.49 in |
Height | 114.5 mm |
Height in inches | 4.51 in |
Length | 116 mm |
Length in inches | 4.57 in |
Weight | 165 g |
Weight | 0.36 lb |
Mounting / Installation
Mounting type | DIN rail NS35/15, NS35/7.5 |
Mounting orientation | Vertical / Horizontal |
Connection type | Spring clamp terminal |
Min. rigid conductor cross section | 0.2 mm² |
Max. rigid conductor cross section | 1.5 mm² |
Min. flex conductor cross section | 0.2 mm² |
Max. flex conductor cross section | 1.5 mm² |
Connection cross-section AWG | 24 ... 16 |
Technical Drawings
Hazardous Location
Diagram showing input and output connections for hazardous and non-hazardous locations.
Output characteristic curve
A graph illustrating the output characteristic curve of the 9276/10-24-48-00 device, plotting output current (mA) against output voltage (V).
Connection diagram
Diagram showing the connection of the 9276/10 device.
Dimensional Drawings