Isolators
Loop-powered binary output
Ex i field circuit
Model: 9276/10-24-48-00s
Art. No.: 261442
An extensive portfolio for a wide variety of solenoid valves
Slim design saves space – just 12.5 mm wide
For use up to SIL 3 (IEC/EN 61508)
The Series 9276 binary outputs transmit signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps and horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs.
Technical Data
Explosion Protection
Parameter | Value | ||||
Application range (zones) | 2 | ||||
Ex interface zone | 0, 1, 2, 20, 21, 22 | ||||
IECEX gas certificate | IECEX IBE 17.0045X | ||||
IECEx gas explosion protection | Ex ec [ia Ga] IIC T4 Gc | ||||
IECEx dust certificate | IECEx IBE 17.0045X | ||||
IECEx dust explosion protection | [Ex ia Da] IIIC | ||||
IECEX firedamp certificate | IECEX IBE 17.0045X | ||||
IECEx firedamp protection | [Ex ia Ma] I | ||||
ATEX gas certificate | IBEXU 17 ATEX 1153 X | ||||
ATEX gas explosion protection | II 3 (1) G Ex ec [ia Ga] IIC T4 Gc | ||||
ATEX dust certificate | IBEXU 17 ATEX 1153 X | ||||
ATEX dust explosion protection | II (1) D [Ex ia Da] IIIC | ||||
ATEX firedamp certificate | IBEXU 17 ATEX 1153 X | ||||
ATEX firedamp protection | I (M1) [Ex ia Ma] I | ||||
cULus certificate | E81680 | ||||
Marking cULus | Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, AEx/Ex nA Group IIC AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC T4 any mounting pos. Ta = 60°C |
||||
Certificates | See Doc. 9276 6 031 001 3 ATEX (IBE), Canada (UL), China (CQM), IECEx (IBE), Korea (KTL), SIL (exida), USA (UL) |
||||
Ship approval | DNV | ||||
Declaration of conformity | ATEX (EUK), China (CCC) | ||||
Safety Data | |||||
Max. voltage U。 | 27.7 V | ||||
Max. current I (Ex ia) | 101 mA | ||||
Max. power P. | 697 mW | ||||
Max. permissible external capacity C. for IIC | 0.085 µF | ||||
Max. permissible external inductance L. for IIC | 4 mH | ||||
Max. permissible external capacity C. for IIB | 0.663 µF | ||||
Max. permissible external inductance L. for IIB | 17 mH | ||||
Max. permissible external capa.IIA | 2.2 µF | ||||
Max. permissible external inductance L. for IIA | 35 mH | ||||
Max. perm. ext. capacit. IIIC | 0.663 µF | ||||
Max. permis. ext. induct. IIIC | 17 mH | ||||
Max. permissible ext. capac. I | 2.2 µF | ||||
Max. permissible external inductance L. for I | 35 mH | ||||
Internal capacitance | Negligible | ||||
Internal inductance | Negligible | ||||
Safety-related max. voltage | 253 V AC | ||||
Intrinsically safe limiting values inductance L / capacitance C。 | Jointly connectable inductance L / capacitance C。 | ||||
IIC | IIB | IIA | IIIC | I | |
L. [mH] | 20 mH | 10 mH | 5 mH | 1 mH | 0.100 mH |
C. [µF] | 0.068 µF | 0.068 µF | 0.068 µF | 0.079 µF | 0.108 µF |
L. [mH] | 10 mH | 5 mH | 1 mH | 0.100 mH | |
C. [µF] | 0.250 µF | 0.250 µF | 0.350 µF | 0.663 µF | |
L. [mH] | 20 mH | 5 mH | 1 mH | 0.100 mH | |
C. [µF] | 0.440 µF | 0.440 µF | 0.680 µF | 0.960 µF | |
L. [mH] | 10 mH | 5 mH | 1 mH | 0.100 mH | |
C. [µF] | 0.250 µF | 0.250 µF | 0.350 µF | 0.663 µF | |
L. [mH] | 20 mH | 5 mH | 1 mH | 0.100 mH | |
C. [µF] | 0.440 µF | 0.440 µF | 0.680 µF | 0.960 µF | |
Functional Safety | |||||
SIL | 3 | ||||
HFT | 0 | ||||
SFF | 100% | ||||
Lambda SD | 0 FIT | ||||
Lambda SU | 50 FIT | ||||
Lambda DD | 0 FIT | ||||
Lambda DU | 0 FIT | ||||
Electrical Data | |||||
Number of channels | 1 | ||||
Auxiliary Power | |||||
Auxiliary power | without | ||||
Max. power dissipation | 1.41 W |
Auxiliary Power
Parameter | Value |
Polarity reversal protection | Yes |
Galvanic Isolation | EN IEC 60079-11 |
Test voltage as per standard | 375 V AC peak value |
Galvanic separation Ex i output to input | 375 V AC peak value |
Input
Parameter | Value |
Input voltage for ON | 15 – 30 V |
Input voltage for OFF | 0 – 5 V |
Output
Parameter | Value |
Output open-circuit voltage U。 | 24 V |
Max. output current la max | 48 mA |
Output internal resistance R₁ | 275.5 Ω |
Switching delay ON/OFF | ≤ 20 ms |
Switching delay OFF/ON | ≤ 20 ms |
Response time output | 20 ms |
Switching state indication | Yellow "STAT" LED |
Ambient Conditions
Parameter | Value |
Ambient temperature | -40 °C ... 60 °C |
Ambient temperature | -40 °F ... +140 °F |
Storage temperature | -40 °C ... 80 °C |
Storage temperature | -40 °F ... +176 °F |
Maximum relative humidity | 10 to 95% |
Use at the height of | < 2000 m |
Electromagnetic compatibility | EN 61326-1 For use in industrial areas Immunity according to EN 61000-6-2 Interference radiation according to EN 61000-6-4 |
Mechanical Data
Parameter | Value |
Degree of protection (IP) | IP30 |
Degree of protection (IP) terminals | IP20 |
Fire resistance (UL 94) | V0 |
Enclosure material | Polyamide |
Grid dimension | 12.5 mm |
Width | 12.5 mm |
Width | 12.5 mm |
Width, inches | 0.49 in |
Height | 114.5 mm |
Height | 114.5 mm |
Height in inches | 4.51 in |
Length | 112.5 mm |
Length in inches | 4.43 in |
Weight | 165 g |
Weight | 0.36 lb |
Mounting / Installation
Parameter | Value |
Mounting type | DIN rail NS35/15, NS35/7.5 |
Mounting orientation | Vertical Horizontal |
Connection type | Screw terminal |
Min. rigid conductor cross section | 0.2 mm² |
Max. rigid conductor cross section | 2.5 mm² |
Min. flex conductor cross section | 0.2 mm² |
Max. flex conductor cross section | 2.5 mm² |
Connection cross-section AWG | 24 ... 14 |
Technical Drawings - Subject to Alterations
Hazardous area
Diagram showing a simplified representation of an Ex i circuit with connections labeled 1, 2, and 3.
Safe area
Diagram showing a simplified representation of a safe area connection with labels O, I, and 1.
Output characteristic curve 9276/10-24-48-00
Graph showing output voltage [V] on the y-axis and output current I, [mA] on the x-axis. The curve starts at approximately 24V at 0mA and decreases as current increases, reaching 10.5V at 20mA.
9276/10-21-25-00 connection diagram
Diagram illustrating a connection configuration.
Dimensional Drawings (All Dimensions in mm [inches]) - Subject to Alterations
Diagram showing the dimensions of the device. Key dimensions include:
- Height: 114.50 [4.51]
- Length: 112.50 [4.43]
- Width: 12.50 [0.49]
The diagram also indicates compatibility with ISpace Series 9260, 9265, 9270, 9275, 9276, 9282 with screw terminals.
R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG
Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com