Isolators

Loop-powered binary output

Ex i field circuit

Model: 9276/10-24-48-00s

Art. No.: 261442

An extensive portfolio for a wide variety of solenoid valves

Slim design saves space – just 12.5 mm wide

For use up to SIL 3 (IEC/EN 61508)

The Series 9276 binary outputs transmit signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps and horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs.

Technical Data

Explosion Protection

Parameter Value
Application range (zones) 2
Ex interface zone 0, 1, 2, 20, 21, 22
IECEX gas certificate IECEX IBE 17.0045X
IECEx gas explosion protection Ex ec [ia Ga] IIC T4 Gc
IECEx dust certificate IECEx IBE 17.0045X
IECEx dust explosion protection [Ex ia Da] IIIC
IECEX firedamp certificate IECEX IBE 17.0045X
IECEx firedamp protection [Ex ia Ma] I
ATEX gas certificate IBEXU 17 ATEX 1153 X
ATEX gas explosion protection II 3 (1) G Ex ec [ia Ga] IIC T4 Gc
ATEX dust certificate IBEXU 17 ATEX 1153 X
ATEX dust explosion protection II (1) D [Ex ia Da] IIIC
ATEX firedamp certificate IBEXU 17 ATEX 1153 X
ATEX firedamp protection I (M1) [Ex ia Ma] I
cULus certificate E81680
Marking cULus Class I, Div. 2, Groups A,B,C,D;
Class I, Zone 2, AEx/Ex nA Group IIC
AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G;
Class I, Zone 0, [AEx ia]/[Ex ia] IIC
T4 any mounting pos. Ta = 60°C
Certificates See Doc. 9276 6 031 001 3
ATEX (IBE), Canada (UL), China (CQM), IECEx (IBE), Korea (KTL), SIL (exida), USA (UL)
Ship approval DNV
Declaration of conformity ATEX (EUK), China (CCC)
Safety Data
Max. voltage U。 27.7 V
Max. current I (Ex ia) 101 mA
Max. power P. 697 mW
Max. permissible external capacity C. for IIC 0.085 µF
Max. permissible external inductance L. for IIC 4 mH
Max. permissible external capacity C. for IIB 0.663 µF
Max. permissible external inductance L. for IIB 17 mH
Max. permissible external capa.IIA 2.2 µF
Max. permissible external inductance L. for IIA 35 mH
Max. perm. ext. capacit. IIIC 0.663 µF
Max. permis. ext. induct. IIIC 17 mH
Max. permissible ext. capac. I 2.2 µF
Max. permissible external inductance L. for I 35 mH
Internal capacitance Negligible
Internal inductance Negligible
Safety-related max. voltage 253 V AC
Intrinsically safe limiting values inductance L / capacitance C。 Jointly connectable inductance L / capacitance C。
IIC IIB IIA IIIC I
L. [mH] 20 mH 10 mH 5 mH 1 mH 0.100 mH
C. [µF] 0.068 µF 0.068 µF 0.068 µF 0.079 µF 0.108 µF
L. [mH] 10 mH 5 mH 1 mH 0.100 mH
C. [µF] 0.250 µF 0.250 µF 0.350 µF 0.663 µF
L. [mH] 20 mH 5 mH 1 mH 0.100 mH
C. [µF] 0.440 µF 0.440 µF 0.680 µF 0.960 µF
L. [mH] 10 mH 5 mH 1 mH 0.100 mH
C. [µF] 0.250 µF 0.250 µF 0.350 µF 0.663 µF
L. [mH] 20 mH 5 mH 1 mH 0.100 mH
C. [µF] 0.440 µF 0.440 µF 0.680 µF 0.960 µF
Functional Safety
SIL 3
HFT 0
SFF 100%
Lambda SD 0 FIT
Lambda SU 50 FIT
Lambda DD 0 FIT
Lambda DU 0 FIT
Electrical Data
Number of channels 1
Auxiliary Power
Auxiliary power without
Max. power dissipation 1.41 W

Auxiliary Power

Parameter Value
Polarity reversal protection Yes
Galvanic Isolation EN IEC 60079-11
Test voltage as per standard 375 V AC peak value
Galvanic separation Ex i output to input 375 V AC peak value

Input

Parameter Value
Input voltage for ON 15 – 30 V
Input voltage for OFF 0 – 5 V

Output

Parameter Value
Output open-circuit voltage U。 24 V
Max. output current la max 48 mA
Output internal resistance R₁ 275.5 Ω
Switching delay ON/OFF ≤ 20 ms
Switching delay OFF/ON ≤ 20 ms
Response time output 20 ms
Switching state indication Yellow "STAT" LED

Ambient Conditions

Parameter Value
Ambient temperature -40 °C ... 60 °C
Ambient temperature -40 °F ... +140 °F
Storage temperature -40 °C ... 80 °C
Storage temperature -40 °F ... +176 °F
Maximum relative humidity 10 to 95%
Use at the height of < 2000 m
Electromagnetic compatibility EN 61326-1 For use in industrial areas
Immunity according to EN 61000-6-2
Interference radiation according to EN 61000-6-4

Mechanical Data

Parameter Value
Degree of protection (IP) IP30
Degree of protection (IP) terminals IP20
Fire resistance (UL 94) V0
Enclosure material Polyamide
Grid dimension 12.5 mm
Width 12.5 mm
Width 12.5 mm
Width, inches 0.49 in
Height 114.5 mm
Height 114.5 mm
Height in inches 4.51 in
Length 112.5 mm
Length in inches 4.43 in
Weight 165 g
Weight 0.36 lb

Mounting / Installation

Parameter Value
Mounting type DIN rail NS35/15, NS35/7.5
Mounting orientation Vertical
Horizontal
Connection type Screw terminal
Min. rigid conductor cross section 0.2 mm²
Max. rigid conductor cross section 2.5 mm²
Min. flex conductor cross section 0.2 mm²
Max. flex conductor cross section 2.5 mm²
Connection cross-section AWG 24 ... 14

Technical Drawings - Subject to Alterations

Hazardous area

Diagram showing a simplified representation of an Ex i circuit with connections labeled 1, 2, and 3.

Safe area

Diagram showing a simplified representation of a safe area connection with labels O, I, and 1.

Output characteristic curve 9276/10-24-48-00

Graph showing output voltage [V] on the y-axis and output current I, [mA] on the x-axis. The curve starts at approximately 24V at 0mA and decreases as current increases, reaching 10.5V at 20mA.

9276/10-21-25-00 connection diagram

Diagram illustrating a connection configuration.

Dimensional Drawings (All Dimensions in mm [inches]) - Subject to Alterations

Diagram showing the dimensions of the device. Key dimensions include:

The diagram also indicates compatibility with ISpace Series 9260, 9265, 9270, 9275, 9276, 9282 with screw terminals.

R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG

Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com

PDF preview unavailable. Download the PDF instead.

ex-single-data-sheet-loop-powered-binary-output-ex-i-field-circuit-9276-10-24-48-00s-261442-en-gb-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL Series 9276 Loop-Powered Binary Output Isolator - Technical Data
Detailed technical specifications for the R. STAHL Series 9276 loop-powered binary output isolator (Ex i field circuit), including explosion protection, safety data, electrical data, ambient conditions, and mechanical dimensions.
Preview R. STAHL 9276/10-24-48-00s Isolator Barrier for Ex i Field Circuits
Technical data sheet for the R. STAHL 9276/10-24-48-00s loop-powered binary output isolator barrier, designed for Ex i field circuits. Features include SIL 3 capability, slim design, and comprehensive explosion protection certifications.
Preview R. STAHL 9276/10-24-48-00s: Loop-Powered Binary Output for Ex i Field Circuits
Technical data sheet for the R. STAHL 9276/10-24-48-00s, a loop-powered binary output for Ex i field circuits. Features include intrinsic safety, SIL 3 capability, and a compact design.
Preview R. STAHL 9276/10-21-40-00s Loop-Powered Binary Output Isolator - Technical Data
Detailed technical specifications for the R. STAHL 9276/10-21-40-00s loop-powered binary output isolator, designed for Ex i field circuits. Includes explosion protection, safety data, electrical specifications, ambient conditions, and mechanical data.
Preview R. STAHL 9276A Series Loop-Powered Binary Output Ex i Field Circuit Isolators
Technical specifications and safety data for the R. STAHL 9276A series loop-powered binary output isolators, designed for Ex i field circuits. Features include ATEX, IECEx, and cULus certifications, various protection methods, and detailed electrical and mechanical data.
Preview R. STAHL 9176/20-15-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical specifications and details for the R. STAHL 9176/20-15-00s loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous areas.
Preview R. STAHL 9176 Series Loop-Powered Binary Output Isolator Barriers for Ex i Field Circuits
Technical data and specifications for the R. STAHL 9176 series loop-powered binary output isolator barriers, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous locations.
Preview R. STAHL 9176/20-16-00s Loop-Powered Binary Output Isolator for Ex i Field Circuits
Technical specifications and data for the R. STAHL 9176/20-16-00s loop-powered binary output isolator, designed for intrinsically safe operation of Ex i solenoid valves, indicator lamps, and horns in hazardous areas.