R. STAHL 9276A Galvanic Isolator
Product Name: Loop-powered binary output without auxiliary output
Field Circuit Type: Ex i
Article Number: 9276/10-24-48-00k
Order Number: 261446
Product Overview
The R. STAHL 9276A series binary outputs provide signals for the intrinsically safe operation of Ex i solenoid valves, signal lamps, or sirens. These devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are electrically isolated from the inputs.
- Important portfolio for a wide range of solenoid valves
- Space-saving due to narrow construction – 12.5 mm wide
- Usable up to SIL 3 (IEC/EN 61508)
Technical Characteristics
Explosion Protection
Parameter | Value |
---|---|
Application Domain (Zones) | 2 |
Interface Ex zone | 0, 1, 2, 20, 21, 22 |
IECEx gas certificate | IECEx IBE 17.0045X |
IECEx gas explosion protection | Ex ec [ia Ga] IIC T4 Gc |
IECEx dust certificate | IECEx IBE 17.0045X |
IECEx dust explosion protection | [Ex ia Da] IIIC |
IECEx firedamp certificate | IECEX IBE 17.0045X |
IECEx firedamp protection | [Ex ia Ma] I |
ATEX gas certificate | IBEXU 17 ATEX 1153 X |
ATEX gas explosion protection | II 3 (1) G Ex ec [ia Ga] IIC T4 Gc |
ATEX dust certificate | IBEXU 17 ATEX 1153 X |
ATEX dust explosion protection | II (1) D [Ex ia Da] IIIC |
ATEX firedamp certificate | IBEXU 17 ATEX 1153 X |
ATEX firedamp protection | I (M1) [Ex ia Ma] I |
cULus certificate | E81680 |
cULus identification | Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, AEx/Ex nA Group IIC AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC T4 any mounting pos. Ta = 60°C |
Certificates | ATEX (IBE), Canada (CSA), China (CQM), États-Unis (UL), IECEx (IBE), SIL (exida) |
Marine approval | DNV |
Certificate of conformity | ATEX (EUK), China (CCC) |
Safety Values
Parameter | Value |
---|---|
Maximum voltage Uo | 27.7 V |
Maximum current Isc (Ex ia) | 101 mA |
Maximum power Po | 697 mW |
Max. permissible external capacitance Co for IIC | 0.085 μF |
Max. permissible external inductance Lo for IIC | 4 mH |
Max. permissible external capacitance Co for IIB | 0.663 μF |
Max. permissible external inductance Lo for IIB | 17 mH |
Max. permissible external capacitance for IIA | 2.2 μF |
Max. permissible external inductance for IIA | 35 mH |
Max. permissible external capacitance for IIIC | 0.663 μF |
Max. permissible external inductance for IIIC | 17 mH |
Max. permissible external capacitance for I | 2.2 μF |
Max. permissible external inductance Lo for I | 35 mH |
Internal capacitance | Negligible |
Internal inductance | Negligible |
Maximum safety technical voltage | 253 V AC |
Intrinsic Safety Limit Values (Inductance L / Capacitance Co that can be connected together)
Group | Inductance Lo [mH] | |||||
---|---|---|---|---|---|---|
20 mH | 10 mH | 5 mH | 1 mH | 0.100 mH | ||
IIC | Co [μF] | 0.068 μF | 0.068 μF | 0.068 μF | 0.079 μF | 0.108 μF |
IIB | Co [μF] | 0.250 μF | 0.250 μF | 0.350 μF | 0.663 μF | |
IIA | Co [μF] | 0.440 μF | 0.440 μF | 0.680 μF | 0.960 μF | |
IIIC | Co [μF] | 0.250 μF | 0.250 μF | 0.350 μF | 0.663 μF | |
I | Co [μF] | 0.440 μF | 0.440 μF | 0.680 μF | 0.960 μF |
Functional Safety
Parameter | Value |
---|---|
SIL | 3 |
HFT | 0 |
SFF | 100% |
Lambda SD | 0 FIT |
Lambda SU | 50 FIT |
Lambda DD | 0 FIT |
Lambda DU | 0 FIT |
Electrical Characteristics
Parameter | Value |
---|---|
Number of channels | 1 |
Auxiliary supply | None |
Maximum dissipated power | 1.41 W |
Reverse polarity protection | Yes |
Electrical separation voltage test according to standard | EN IEC 60079-11 |
Electrical separation Output Ex i to input | 375 V AC peak value |
Input voltage for ON | 15 - 30 V |
Input voltage for OFF | 0 - 5 V |
Output open-circuit voltage Uo | 24 V |
Maximum output current Ia | 48 mA |
Internal resistance R | 275.5 Ω |
Switching delay ON/OFF | ≤ 20 ms |
Switching delay OFF/ON | ≤ 20 ms |
Output establishment time | 20 ms |
Switching status indication | Yellow LED "STAT" |
Ambient Conditions
Parameter | Value |
---|---|
Ambient temperature | -40 °C ... 60 °C (-40 °F ... +140 °F) |
Storage temperature | -40 °C ... 80 °C (-40 °F ... +176 °F) |
Maximum relative humidity | 10 ... 95% |
Operation at altitude | < 2000 m |
Electromagnetic compatibility | EN 61326-1, industrial environment use Immunity to disturbances according to EN 61000-6-2 Emission of disturbances according to EN 61000-6-4 |
Mechanical Characteristics
Parameter | Value |
---|---|
Degree of protection (IP) | IP30 |
Degree of protection (IP) pins | IP20 |
Flammability resistance (UL 94) | V0 |
Housing material | Polyamide |
Pitch | 12.5 mm |
Width | 12.5 mm (0.49 in) |
Height | 114.5 mm (4.51 in) |
Length | 116 mm (4.57 in) |
Weight | 165 g (0.36 lb) |
Mounting / Installation
Parameter | Value |
---|---|
Mounting type | DIN rail NS35/15, NS35/7.5 |
Mounting position | Vertical / Horizontal |
Connection type | Spring clamp terminal |
Rigid conductor cross-section min. | 0.2 mm² |
Rigid conductor cross-section max. | 1.5 mm² |
Flexible conductor cross-section min. | 0.2 mm² |
Flexible conductor cross-section max. | 1.5 mm² |
AWG connection size | 24 ... 16 |
Outline Drawing
Outline drawing (all dimensions in mm [inches]) – subject to change.
Drawing Description:
The drawing shows a rectangular device with a width of 12.50 mm [0.49 in] and a height of 114.50 mm [4.51 in]. The length is 116 mm [4.57 in]. Terminal blocks are visible on the top and bottom. The drawing indicates compatibility with ISpac series 9260, 9270, 9275, 9276, 9282 with spring clamp terminals.
Subject to change regarding technical characteristics, dimensions, weight, construction types, and delivery options. Figures are for indicative purposes only.
Contact Information:
R. STAHL Schaltgeräte GmbH
Am Bahnhof 30
74638 WALDENBURG
Tel: +49 7942 943 1700
Fax: +49 7942 943 1777
Email: sales.de@r-stahl.com
Website: r-stahl.com