Isolator Barriers

Loop-powered binary output

Ex i field circuit

9276/10-24-48-00s Art. No. 261442

Key Features

Image of the R. STAHL 9276A Isolator Barrier

Series 9276 digital outputs issue signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs.

Technical Data

Explosion Protection

ParameterValue
Application range (zones)2
Ex interface zone0, 1, 2, 20, 21, 22
IECEX gas certificateIECEX IBE 17.0045X
IECEx gas explosion protectionEx ec [ia Ga] IIC T4 Gc
IECEx dust certificateIECEx IBE 17.0045X
IECEx dust explosion protection[Ex ia Da] IIIC
IECEX firedamp certificateIECEX IBE 17.0045X
IECEX firedamp protection[Ex ia Ma] I
ATEX gas certificateIBEXU 17 ATEX 1153 X
ATEX gas explosion protectionII 3 (1) G Ex ec [ia Ga] IIC T4 Gc
ATEX dust certificateIBEXU 17 ATEX 1153 X
ATEX dust explosion protectionII (1) D [Ex ia Da] IIIC
ATEX firedamp certificateIBEXU 17 ATEX 1153 X
ATEX firedamp protectionI (M1) [Ex ia Ma] I
cULus certificateE81680
Marking cULusClass I, Div. 2, Groups A,B,C,D;
Class I, Zone 2, AEx/Ex nA Group IIC
AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G;
Class I, Zone 0, [AEx ia]/[Ex ia] IIC
T4 any mounting pos. Ta = 60°C
CertificatesSee Doc. 9276 6 031 001 3
ATEX (IBE), Canada (UL), China (CQM), IECEx (IBE), Korea (KTL), SIL (exida), USA (UL)
Ship approvalDNV
Declaration of conformityATEX (EUK), China (CCC)
Safety Data
Max. voltage U/Voc27.7 V

Safety Data

ParameterValue
Max. current I (Ex ia)101 mA
Max. power P.697 mW
Max. permissible external capacitance C/C for IIC0.085 μF
Max. permissible external inductance L/La for IIC4 mH
Max. permissible external capacitance C/C for IIB0.663 µF
Max. permissible external inductance L/La for IIB17 mH
Max. permissible external capa.IIA2.2 μF
Max. permissible external inductance L。 for IIA35 mH
Max. perm. ext. capacit. IIIC0.663 μF
Max. permis. ext. induct. IIIC17 mH
Max. permissible ext. capac. I2.2 μF
Max. permissible external inductance L。 for I35 mH
Internal capacitanceNegligible
Internal inductanceNegligible
Safety-related max. voltage253 V AC
Intrinsically safe limiting values inductance L/capacitance C。Jointly connectable inductance L/capacitance Co
IICL. [mH]: 20 mH, 10 mH, 5 mH, 1 mH, 0.100 mH
C. [µF]: 0.068 μF, 0.068 μF, 0.068 μF, 0.079 μF, 0.108 μF
IIBL. [mH]: 10 mH, 5 mH, 1 mH, 0.100 mH
C. [µF]: 0.250 μF, 0.250 μF, 0.350 μF, 0.663 μF
IIAL. [mH]: 20 mH, 5 mH, 1 mH, 0.100 mH
C. [µF]: 0.440 μF, 0.440 μF, 0.680 μF, 0.960 μF
IIICL. [mH]: 10 mH, 5 mH, 1 mH, 0.100 mH
C. [µF]: 0.250 μF, 0.250 μF, 0.350 μF, 0.663 µF
IL. [mH]: 20 mH, 5 mH, 1 mH, 0.100 mH
C. [µF]: 0.440 μF, 0.440 μF, 0.680 μF, 0.960 μF

Functional Safety

ParameterValue
SIL3
HFT0
SFF100%
Lambda SD0 FIT
Lambda SU50 FIT
Lambda DD0 FIT
Lambda DU0 FIT

Electrical Data

ParameterValue
Number of channels1
Auxiliary powerwithout
Max. power dissipation1.41 W

Auxiliary Power

ParameterValue
Polarity reversal protectionYes
Galvanic IsolationEN IEC 60079-11
Test voltage as per standard375 V AC peak value
Galvanic separation Ex i output to input

Input

ParameterValue
Input voltage for ON15 – 30 V
Input voltage for OFF0 – 5 V

Output

ParameterValue
Output open-circuit voltage U24 V
Max. output current Ia max48 mA
Output internal resistance Ri275.5 Ω
Switching delay ON/OFF≤ 20 ms
Switching delay OFF/ON≤ 20 ms
Response time output20 ms
Switching state indicationYellow "STAT" LED

Ambient Conditions

ParameterValue
Ambient temperature °C-40 °C ... 60 °C
Ambient temperature °F-40 °F ... +140 °F
Storage temperature °C-40 °C ... 80 °C
Storage temperature °F-40 °F ... +176 °F
Max. relative humidity10 to 95%
Use at the height of< 2000 m
Electromagnetic compatibilityEN 61326-1 Use in industrial environment
Immunity according to EN 61000-6-2
Interference emission to EN 61000-6-4

Mechanical Data

ParameterValue
Degree of protection (IP)IP30
Degree of protection (IP) terminalsIP20
Fire resistance (UL 94)VO
Enclosure materialPolyamide
Grid dimension12.5 mm
Width12.5 mm
Width, inches0.49 in
Height114.5 mm
Height in inches4.51 in
Length112.5 mm
Length in inches4.43 in
Weight165 g
Weight0.36 lb

Mounting / Installation

ParameterValue
Mounting typeDIN rail NS35/15, NS35/7.5
Mounting orientationVertical
Horizontal
Connection typeScrew terminal
Min. rigid conductor cross section0.2 mm²
Max. rigid conductor cross section2.5 mm²
Min. flex conductor cross section0.2 mm²
Max. flex conductor cross section2.5 mm²
Connection cross-section AWG24 ... 14

Technical Drawings - Subject to Alterations

Hazardous Location vs. Nonhazardous Location Output characteristic curve 9276/10-24-48-00

Output characteristic curve 9276/10-24-48-00

Shows output current (mA) vs. input voltage (V).

Connection diagram 9276/10

Diagram showing connection details.

Dimensional Drawings (All Dimensions in mm [inches]) – Subject to Alterations

Diagram showing the dimensions of the isolator barrier, including height, width, and length in both millimeters and inches.

We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.

PDF preview unavailable. Download the PDF instead.

ex-single-data-sheet-loop-powered-binary-output-ex-i-field-circuit-9276-10-24-48-00s-261442-en-us-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 9276A Series Loop-Powered Binary Output Ex i Field Circuit Isolators
Technical specifications and safety data for the R. STAHL 9276A series loop-powered binary output isolators, designed for Ex i field circuits. Features include ATEX, IECEx, and cULus certifications, various protection methods, and detailed electrical and mechanical data.
Preview R. STAHL 9276/10-21-40-00s Isolator Barrier: Technical Specifications and Safety Data
Detailed technical specifications, safety data, and application information for the R. STAHL 9276/10-21-40-00s loop-powered binary output isolator barrier for Ex i field circuits.
Preview R. STAHL 9276/10-24-48-00s: Loop-Powered Binary Output for Ex i Field Circuits
Technical data sheet for the R. STAHL 9276/10-24-48-00s, a loop-powered binary output for Ex i field circuits. Features include intrinsic safety, SIL 3 capability, and a compact design.
Preview R. STAHL 9276/10-24-48-00s Loop-Powered Binary Output Isolator - Technical Data
Detailed technical specifications for the R. STAHL 9276/10-24-48-00s loop-powered binary output isolator, including explosion protection, safety data, electrical characteristics, and mechanical dimensions. Suitable for intrinsically safe operation of Ex i solenoid valves.
Preview R. STAHL 9276A Loop-Powered Binary Output Ex i Field Circuit - Technical Data
Detailed technical specifications and safety information for the R. STAHL 9276A loop-powered binary output Ex i field circuit, including explosion protection, electrical data, safety, and mechanical dimensions.
Preview R. STAHL 9276A Loop-Powered Binary Output Ex i Field Circuit - Technical Data
Technical specifications and safety data for the R. STAHL 9276A loop-powered binary output for Ex i field circuits. Details include explosion protection, electrical data, safety parameters, environmental conditions, and mechanical dimensions.
Preview R. STAHL 9276A Series: Loop-Powered Binary Output Ex i Field Circuit Isolators
Technical specifications and data for the R. STAHL 9276A series loop-powered binary output Ex i field circuit isolators. Details include explosion protection, safety data, electrical characteristics, environmental conditions, and mechanical data for model 9276/10-21-40-00s.
Preview R. STAHL 9276A Galvanic Isolator: Technical Specifications for Ex i Field Circuits
Detailed technical specifications for the R. STAHL 9276A galvanic isolator, a loop-powered binary output device for Ex i field circuits. Includes ATEX, IECEx, and cULus certifications, electrical and mechanical characteristics, and safety data.