R. STAHL Isolator Barriers
Loop-powered binary output
Ex i field circuit
Model: 9276/10-21-60-00k
Art. No.: 261447
Key Features
- A comprehensive portfolio for a wide range of solenoid valves
- Space savings due to a slim design – 12.5 mm wide
- Can be used for functional safety levels up to SIL 3 (IEC/EN 61508)
Product Description: Series 9276 digital outputs issue signals for the intrinsically safe operation of Ex i solenoid valves, indicator lamps or horns. The devices do not require a separate auxiliary power supply as they are powered by the control circuit. The intrinsically safe outputs are galvanically separated from the inputs.
Certifications: Ex SIL, IEC 61508, IEC 61511
Technical Data
Explosion Protection
Parameter | Value |
Application range (zones) | 2 |
Ex interface zone | 0, 1, 2, 20, 21, 22 |
IECEX gas certificate | IECEX IBE 17.0045X |
IECEx gas explosion protection | Ex ec [ia IIB Ga] IIC T4 Gc |
IECEx dust certificate | IECEx IBE 17.0045X |
IECEx dust explosion protection | [Ex ia Da] IIIC |
IECEX firedamp certificate | IECEX IBE 17.0045X |
IECEx firedamp protection | [Ex ia Ma] I |
ATEX gas certificate | IBEXU 17 ATEX 1153 X |
ATEX gas explosion protection | II 3 (1) G Ex ec [ia IIB Ga] IIC T4 Gc |
ATEX dust certificate | IBEXU 17 ATEX 1153 X |
ATEX dust explosion protection | II (1) D [Ex ia Da] IIIC |
ATEX firedamp certificate | IBEXU 17 ATEX 1153 X |
ATEX firedamp protection | I (M1) [Ex ia Ma] I |
cULus certificate | E81680 |
Marking cULus | Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, AEx/Ex nA Group IIC AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC T4 any mounting pos. Ta = 60°C |
Certificates | See Doc. 9276 6 031 001 3 |
Ship approval | ATEX (IBE), Canada (UL), China (CQM), IECEx (IBE), SIL (exida), USA (UL) |
Declaration of conformity | ATEX (EUK), China (CCC) |
Safety Data
Parameter | Value | |||
Max. voltage U。/VOC | 25.1 V | |||
Max. current Ia max (Ex ia) | 188 mA | |||
Max. power Po | 1180 mW | |||
Max. permissible external capacitance Co for IIB | 0.83 µF | |||
Max. permissible external inductance Lo/La for IIB | 4 mH | |||
Max. permissible external capa. IIA | 2.93 µF | |||
Max. permissible external inductance Lo for IIA | 7.5 mH | |||
Max. perm. ext. capacit. IIIC | 0.83 µF | |||
Max. permis. ext. induct. IIIC | 4 mH | |||
Max. permissible ext. capac. I | 2.93 µF | |||
Max. permissible external inductance Lo for I | 7.5 mH | |||
Internal capacitance | Negligible | |||
Internal inductance | Negligible | |||
Safety-related max. voltage | 253 V AC | |||
Intrinsically safe limiting values inductance Lo/capacitance Co | Jointly connectable inductance Lo/capacitance Co | |||
Circuit | Lo [mH] | Co [µF] | Lo [mH] | Co [µF] |
IIC | 2 mH | 1 mH | 0.500 mH | 0.100 mH |
IIB | 0.300 µF | 0.370 µF | 0.460 µF | 0.790 µF |
IIA | 5 mH | 1 mH | 0.500 mH | 0.100 mH |
0.510 µF | 0.560 µF | 0.660 µF | 1 µF | |
IIIC | 2 mH | 1 mH | 0.500 mH | 0.100 mH |
0.300 µF | 0.370 µF | 0.460 µF | 0.790 µF | |
I | 5 mH | 1 mH | 0.500 mH | 0.100 mH |
0.510 µF | 0.560 µF | 0.660 µF | 1 µF |
Functional Safety
Parameter | Value |
SIL | 3 |
HFT | 0 |
SFF | 100% |
Lambda SD | 0 FIT |
Lambda SU | 50 FIT |
Lambda DD | 0 FIT |
Lambda DU | 0 FIT |
Electrical Data
Parameter | Value |
Number of channels | 1 |
Auxiliary Power | without |
Max. power dissipation | 1.33 W |
Polarity reversal protection | Yes |
Galvanic Isolation Test voltage as per standard | EN IEC 60079-11 |
Galvanic separation Ex i output to input | 375 V AC peak value |
Input
Parameter | Value |
Input voltage for ON | 15–30 V |
Input voltage for OFF | 0–5 V |
Output
Parameter | Value |
Output open-circuit voltage Uo | 21.9 V |
Max. output current Ia max | 58 mA |
Output internal resistance Ri | 133.4 Ω |
Switching delay ON/OFF | ≤ 20 ms |
Switching delay OFF/ON | ≤ 20 ms |
Response time output | 20 ms |
Switching state indication | Yellow "STAT" LED |
Ambient Conditions
Parameter | Value |
Ambient temperature °C | -40 °C ... 60 °C |
Ambient temperature °F | -40 °F ... +140 °F |
Storage temperature °C | -40 °C ... 80 °C |
Storage temperature °F | -40 °F ... +176 °F |
Max. relative humidity | 10 to 95% |
Use at the height of | < 2000 m |
Electromagnetic compatibility | EN 61326-1 Use in industrial environment Immunity according to EN 61000-6-2 Interference emission to EN 61000-6-4 |
Mechanical Data
Parameter | Value |
Degree of protection (IP) | IP30 |
Degree of protection (IP) terminals | IP20 |
Fire resistance (UL 94) | V0 |
Enclosure material | Polyamide |
Grid dimension | 12.5 mm |
Width | 12.5 mm |
Width, inches | 0.49 in |
Height | 114.5 mm |
Height in inches | 4.51 in |
Length | 116 mm |
Length in inches | 4.57 in |
Weight | 165 g |
Weight | 0.36 lb |
Mounting / Installation
Parameter | Value |
Connection cross-section AWG | 24 ... 16 |
Mounting type | DIN rail NS35/15, NS35/7.5 |
Mounting orientation | Vertical / Horizontal |
Connection type | Spring clamp terminal |
Min. rigid conductor cross section | 0.2 mm² |
Max. rigid conductor cross section | 1.5 mm² |
Min. flex conductor cross section | 0.2 mm² |
Max. flex conductor cross section | 1.5 mm² |
Technical Drawings
Output Characteristic Curve
A graph shows the relationship between output voltage (Uo) and output current (Io) for the 9276/10-21-60-00k. The output voltage ranges from 0V to 30V, and the output current ranges from 0mA to 60mA. Key points indicated are 12.9V at 11mA and 21.9V at 58mA.
Connection Diagram
A diagram illustrates the connection of the isolator barrier between a hazardous location and a nonhazardous location, showing input and output terminals.
Dimensional Drawings
Diagrams provide the dimensions of the isolator barrier in millimeters and inches. Key dimensions include a width of 12.5 mm (0.49 in), a height of 114.5 mm (4.51 in), and a length of 116 mm (4.57 in).
Note: Applicable for iSpaC Series 9260, 9270, 9275, 9276 with spring clamp terminal.
General Information
R. STAHL reserves the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.
Related Documents
![]() |
R. STAHL 9276A: Loop-Powered Binary Output for Ex i Field Circuits Technical data and specifications for the R. STAHL 9276A, a loop-powered binary output device for intrinsically safe Ex i field circuits. Features include compact design, SIL 3 capability, and suitability for hazardous areas. |
![]() |
R. STAHL 9276A Binary Output Ex i Field Circuit Isolator - Technical Specifications Detailed technical specifications for the R. STAHL 9276A loop-powered binary output Ex i field circuit isolator. Includes safety data, electrical characteristics, environmental conditions, and mechanical dimensions for explosion protection applications. |
![]() |
R. STAHL 9276A Loop-Powered Binary Output Ex i Field Circuit - Technical Data Technical specifications and data for the R. STAHL 9276A loop-powered binary output for Ex i field circuits. Details include explosion protection, safety data, electrical specifications, environmental conditions, and mechanical data. |
![]() |
R. STAHL Series 9276 Loop-Powered Binary Output Ex i Field Circuit Datasheet Technical datasheet for the R. STAHL Series 9276 loop-powered binary output Ex i field circuit isolator. Details explosion protection, technical data, safety data, electrical data, ambient conditions, mechanical data, and mounting information. |
![]() |
R. STAHL 9276A Loop-Powered Binary Output Ex i Field Circuit - Technical Data Detailed technical specifications and safety information for the R. STAHL 9276A loop-powered binary output Ex i field circuit, including explosion protection, electrical data, safety, and mechanical dimensions. |
![]() |
R. STAHL Series 9276 Loop-Powered Binary Output Isolator - Technical Data Detailed technical specifications for the R. STAHL Series 9276 loop-powered binary output isolator (Ex i field circuit), including explosion protection, safety data, electrical data, ambient conditions, and mechanical dimensions. |
![]() |
R. STAHL 9276 Series Isolators: Loop-Powered Binary Output for Ex i Field Circuits Technical data sheet for R. STAHL Series 9276 isolators, featuring loop-powered binary output for Ex i field circuits. Details explosion protection, safety data, electrical specifications, mechanical data, and mounting information. |
![]() |
R. STAHL 9276A Series: Loop-Powered Binary Output Ex i Field Circuit Isolators Technical specifications and data for the R. STAHL 9276A series loop-powered binary output Ex i field circuit isolators. Details include explosion protection, safety data, electrical characteristics, environmental conditions, and mechanical data for model 9276/10-21-40-00s. |