R. STAHL 9276A Loop-Powered Binary Output Ex i Field Circuit
Article No. 261446
Product Overview
The R. STAHL 9276A is a loop-powered binary output designed for Ex i field circuits. It is used to emit signals for the operation of intrinsically safe Ex i solenoid valves, pilot lights, or horns. The device does not require separate auxiliary power as it is supplied via the control circuit. The intrinsic safety outputs are galvanically isolated from the inputs.
Key features include:
- Extensive catalog for a wide range of solenoid valves.
- Space-saving design with a small construction width of 12.5 mm.
- Usable up to SIL 3 (IEC/EN 61508).
Technical Data
Explosion Protection
Applications (zones) | 2 |
Ex zone interface | 0, 1, 2, 20, 21, 22 |
IECEX gas homologation | IECEx IBE 17.0045X |
IECEx gas explosion protection | Ex ec [ia Ga] IIC T4 Gc |
IECEx dust homologation | IECEx IBE 17.0045X |
IECEx dust explosion protection | [Ex ia Da] IIIC |
IECEx firedamp homologation | IECEx IBE 17.0045X |
IECEx firedamp explosion protection | [Ex ia Ma] I |
ATEX gas homologation | IBEXU 17 ATEX 1153 X |
ATEX gas explosion protection | II 3 (1) G Ex ec [ia Ga] IIC T4 Gc |
ATEX dust homologation | IBEXU 17 ATEX 1153 X |
ATEX dust explosion protection | II (1) D [Ex ia Da] IIIC |
ATEX firedamp homologation | IBEXU 17 ATEX 1153 X |
ATEX firedamp explosion protection | I (M1) [Ex ia Ma] I |
cULus homologation | E81680 |
cULus identification | Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, AEx/Ex nA Group IIC AIS Class I,II,III, Div. 1, Groups A,B,C,D,E,F,G; Class I, Zone 0, [AEx ia]/[Ex ia] IIC T4 any mounting pos. Ta = 60°C See Doc. 9276 6 031 001 3 |
Certifications
Marine certification | ATEX (IBE), Canada (CSA), China (CQM), EE.UU. (UL), IECEx (IBE), SIL (exida) |
Certificate of conformity | ATEX (EUK), China (CCC) |
Safety Data
Maximum voltage U | 27.7 V |
Maximum current I (Ex ia) | 101 mA |
Maximum power P | 697 mW |
Maximum permissible external capacitance C, for IIC | 0.085 µF |
Maximum permissible external inductance L, for IIC | 4 mH |
Maximum permissible external capacitance C, for IIB | 0.663 µF |
Maximum permissible external inductance L, for IIB | 17 mH |
Maximum permissible external capacitance IIA | 2.2 µF |
Maximum permissible external inductance IIA | 35 mH |
Max. external capacitance IIIC | 0.663 µF |
Max. external inductance IIIC | 17 mH |
Max. external capacitance I | 2.2 µF |
Maximum external inductance L, for I | 35 mH |
Internal capacitance | Irrelevant |
Internal inductance | Irrelevant |
Maximum technical safety voltage | 253 V AC |
Intrinsic Safety Limits (Inductance L / Capacitance C₀)
20 mH | 10 mH | 5 mH | 1 mH | 0.100 mH | |
IIC | L. [mH] C. [µF] |
0.068 µF 0.068 µF |
0.068 µF 0.068 µF |
0.068 µF 0.079 µF |
0.108 µF |
IIB | L. [mH] C. [µF] |
0.250 µF 0.250 µF |
0.350 µF 0.663 µF |
1 mH 0.100 mH |
0.100 mH |
IIA | L. [mH] C. [µF] |
0.440 µF 0.440 µF |
0.680 µF 0.960 µF |
1 mH 0.100 mH |
0.100 mH |
IIIC | L. [mH] C. [µF] |
0.250 µF 0.250 µF |
0.350 µF 0.663 µF |
1 mH 0.100 mH |
0.100 mH |
I | L. [mH] C. [µF] |
0.440 µF 0.440 µF |
0.680 µF 0.960 µF |
1 mH 0.100 mH |
0.100 mH |
Functional Safety
SIL | 3 |
HFT | 0 |
SFF | 100% |
Lambda SD | 0 FIT |
Lambda SU | 50 FIT |
Lambda DD | 0 FIT |
Lambda DU | 0 FIT |
Electrical Data
Number of channels | 1 |
Auxiliary Power
Auxiliary power | None |
Electrical Characteristics
Maximum dissipated power | 1.41 W |
Reverse polarity protection | Yes ✔️ |
Galvanic separation | |
Test voltage according to standard | EN IEC 60079-11 |
Galvanic separation Ex i output to input | 375 V AC maximum value |
Input
Input voltage for ON | 15 - 30 V |
Input voltage for OFF | 0 - 5 V |
Output
Output voltage in open circuit U₂ | 24 V |
Maximum output current Iₐ max | 48 mA |
Output internal resistance R | 275.5 Ω |
Switching delay ON/OFF | ≤ 20 ms |
Switching delay OFF/ON | ≤ 20 ms |
Output stabilization time | 20 ms |
Switching status indication | Yellow LED "STAT" |
Environmental Conditions
Ambient temperature | -40 °C ... 60 °C (-40 °F ... +140 °F) |
Storage temperature | -40 °C ... 80 °C (-40 °F ... +176 °F) |
Maximum relative humidity | 10 ... 95% |
Altitude utilization | < 2000 m |
Electromagnetic compatibility | EN 61326-1 industrial use. Immunity according to EN 61000-6-2. Radiated spurious emissions according to EN 61000-6-4. |
Mechanical Data
Degree of protection (IP) | IP30 |
Degree of protection (IP) terminals | IP20 |
Fire resistance (UL 94) | V0 |
Enclosure material | Polyamide |
Junction dimension | 12.5 mm |
Width | 12.5 mm |
Mounting width in inches | 0.49 in |
Height | 114.5 mm |
Height in inches | 4.51 in |
Length | 116 mm |
Length in inches | 4.57 in |
Weight | 165 g (0.36 lb) |
Mounting / Installation
Mounting position | Vertical / Horizontal |
Connection type | Spring terminal |
Minimum rigid conductor cross-section | 0.2 mm² |
Maximum flexible conductor cross-section | 1.5 mm² |
Minimum flexible conductor cross-section | 0.2 mm² |
Maximum flexible conductor cross-section | 1.5 mm² |
AWG ambient temperature | 24 ... 16 |
Measurement Diagram (all dimensions in inches)
A diagram shows the dimensions of the unit. Key dimensions include:
- Height: 114.50 [4.51]
- Length: 116 [4.57]
- Width: 12.50 [0.49]
- Internal dimensions are also indicated.
The diagram references "i-spac series 9260, 9270, 9275, 9276, 9282 with spring terminal".
R. STAHL reserves the right to modify technical data, dimensions, weights, constructions, and delivery options.