Componentes para la técnica de sistemas - Disyuntor
Model: 8530/1-MCB-STA103-C32-000-3
Part Number: 272181
Product Overview
The R. STAHL 8530/1-MCB-STA103-C32-000-3 circuit breaker is designed for systems technology, offering good current limitation in case of short circuits and a high breaking capacity of 10, 15, or 25 kA. This reduces the load on electrical lines and provides high selectivity with upstream fuses. The modules feature a modular structure, available in 1 to 4 pole versions, with nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.
Key Features:
- Separator function according to EN 60947-2
- Energy limitation class 3
- Easy replacement or expansion of installations due to modular design
- Simple mounting by clipping onto the DIN mounting rail in Ex e enclosures
- Fixed thermal and magnetic trip adjustment
- Ergonomic operating lever for safe connection and disconnection
- Protection against reconnection during maintenance using padlocks (Accessories)
Technical Data
Explosion Protection
Applications (zones) | 1, 2 |
---|---|
Applications (zones) Note | Can be used in zones 21/22 with protection by Ex tb/tc enclosure |
IECEX gas certification | IECEX FMG 19.0029U |
IECEx gas explosion protection | Ex db eb IIC Gb |
ATEX gas certification | FM19ATEX0191U |
ATEX gas explosion protection | II 2 G Ex db eb IIC Gb |
Certifications | ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM) |
Certificate of conformity | Certificate of conformity (ATEX), China (CCC) |
Electrical Data
Rated operating voltage AC | 230/400 V |
---|---|
Rated operating current | 32 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 104 |
Mechanical service life | 2 x 104 |
1st auxiliary function | None |
1st auxiliary function voltage | - |
Max. current 1st auxiliary function | - |
2nd auxiliary function | None |
Max. voltage 2nd aux. function DC | - |
Trip characteristic | C |
Number of poles | 3-pole |
Environmental Conditions
Ambient temperature | -40 °C ... 70 °C |
---|---|
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature | -40°F ... +158°F |
Ambient temperature Note | Divergent ambient temperatures based on valid certificates upon request |
Mechanical Data
Degree of protection (IP) (IEC 60529) | IP2X |
---|---|
Enclosure material | Thermoplastic |
Connection terminal cross-section min. | 1.5 mm² |
Connection terminal cross-section max. | 25 mm² |
Connection terminal AWG min. | 16 AWG |
Connection terminal AWG max. | 4 AWG |
Connection terminal 2 min. | 1.5 mm² |
Connection terminal 2 max. | 10 mm² |
Connection terminal 2 AWG min. | 16 AWG |
Connection terminal 2 AWG max. | 8 AWG |
Tightening torque min. | 2 N·m |
Tightening torque max. | 3 N·m |
Connection terminal Note | 2 conductor connections (upper and lower chamber simultaneously): lower and upper chamber max. 16 / 10 mm² (only a maximum cross-section difference of the upper and lower chamber can be connected). Permitted connection cross-section combinations are listed in the user manual. |
Width | 83 mm |
Mounting width in inches | 3.27 in |
Length | 165 mm |
Length inches | 6.5 in |
Installation depth | 138.3 mm |
Installation depth inches | 5.44 in |
Weight | 1.4 kg |
Weight | 3.087 lb |
Mounting / Installation Tightening torque | 2-3 N·m |
Mounting / Installation Tightening torque lbf in | 17.7 ... 26.6 lbf-in |
Tightening torque auxiliary contact | 0.4–0.6 Nm |
Tightening torque auxiliary contact lbf in | 3.5 ... 5.3 lbf in |
Technical Diagrams
Technical diagrams - Subject to change without notice.
Trip Time vs. Multiple of Rated Current (I/In) for Characteristic C:
A graph showing the relationship between trip time (seconds) and the multiple of the rated current (I/In) for a Type C tripping characteristic. The graph displays curves for AC and DC, indicating the time it takes for the breaker to trip under various overcurrent conditions.
Measurement Diagram:
Schematic showing the dimensions of the circuit breaker. All dimensions are provided in millimeters with inch equivalents in brackets. Key dimensions include width, height, depth, and mounting dimensions.
3-pole unit with no auxiliary contact:
Illustration of the 3-pole circuit breaker unit without any auxiliary contacts.
Accessories
-
Cylinder lock
For locking (shackle Ø 3)
Part Number: 107115
-
Quadruple immobilization device
Locking/tagging tongs for individual component locking using up to 4 cylinder locks.
Part Number: 227232
-
Fixing kit
A set of fixings for mounting the component on the mounting plate without a top-hat rail.
Part Number: 276618
R. STAHL reserves the right to modify technical data, dimensions, weights, constructions, and delivery options.