R. STAHL LS Miniature Circuit Breaker 8530/1-MCB-STA103-C32-000-3
Article No. 272181
Key Features
- Trennerfunktion according to EN 60947-2
- Energy Limiting Class 3
- Easy replacement or expansion of your system due to modular design
- Simple mounting by snapping onto top-hat rails in Ex e enclosures
- Fixed thermal and magnetic trip units
- Ergonomically shaped operating lever ensures safe switching on and off
- Protection against re-switching during maintenance using padlocks (accessory)
Product Overview
The 8530 series miniature circuit breakers from R. STAHL offer good current limitation for short circuits and high switching capacity of 10, 15, or 25 kA. This means less stress on the lines and higher selectivity to upstream fuses. The modules are designed modularly and are available in 1- to 4-pole versions for rated currents from 0.5–63 A. The maximum installation capacity is 4.5 modules (TE).
Technical Data
Explosion Protection
Parameter | Value |
---|---|
Area of Application (Zones) | 1, 2 |
Area of Application (Zones) Note | Usable in Zone 21 / 22 with protection by enclosure Ex tb / tc |
IECEx Certificate Gas | IECEx FMG 19.0029U |
IECEx Gas Explosion Protection | Ex db eb IIC Gb |
ATEX Certificate Gas | FM19ATEX0191U |
ATEX Gas Explosion Protection | II 2 G Ex db eb IIC Gb |
Certifications | ATEX (FM), Brazil (ULB), IECEx (FM), People's Republic of China (CQST) |
Declarations of Conformity | Conformity certification (ATEX), People's Republic of China (CCC) |
Electrical Data
Parameter | Value |
---|---|
Rated Operating Voltage AC | 230/400 V |
Rated Operating Current | 32 A |
Frequency | 50/60 Hz |
Rated Short-Circuit Breaking Capacity | 10 kA |
Electrical Endurance | 10⁴ |
Mechanical Endurance | 2 x 10⁴ |
1. Auxiliary Function | - |
Rated Voltage 1. Auxiliary Function AC | - |
Max. Rated Current 1. Auxiliary Function | - |
2. Auxiliary Function | - |
Max. Voltage 2. Auxiliary Function DC | - |
Trip Characteristic | C |
Number of Poles | 3-pole |
Environmental Conditions
Parameter | Value |
---|---|
Ambient Temperature | -40 °C ... 70 °C |
Ambient Temperature | -40 °F ... 158 °F |
Ambient Temperature Note | Deviating ambient temperatures are available upon request based on current certificates. |
Mechanical Data
Parameter | Value |
---|---|
Protection Type (IP) (IEC 60529) | IP2X |
Housing Material | Thermoplast |
Conductor Cross-Section min. | 1.5 mm² |
Conductor Cross-Section max. | 25 mm² |
Conductor Cross-Section AWG min. | 16 AWG |
Conductor Cross-Section AWG max. | 4 AWG |
Conductor Cross-Section 2 min. | 1.5 mm² |
Conductor Cross-Section 2 max. | 10 mm² |
Conductor Cross-Section 2 AWG min. | 16 AWG |
Conductor Cross-Section 2 AWG max. | 8 AWG |
Tightening Torque min. | 2 N·m |
Tightening Torque max. | 3 N·m |
Conductor Cross-Section Note | 2-conductor connection (upper and lower chamber simultaneously): max. 16 / 10 mm² for upper and lower chamber (a maximum cross-section difference between the upper and lower chamber may be clamped.) Permitted combinations of conductor cross-sections can be found in the operating manual. |
Dimensions
Parameter | Value |
---|---|
Width | 83 mm (3.27 in) |
Length | 165 mm (6.5 in) |
Installation Depth | 138.3 mm (5.44 in) |
Weight | 1.4 kg (3.087 lb) |
Mounting / Installation
Parameter | Value |
---|---|
Tightening Torque | 2–3 N·m (17.7 ... 26.6 lbf·in) |
Tightening Torque Auxiliary Contact | 0.4–0.6 Nm (3.5 ... 5.3 lbf·in) |
Diagrams
Trip Characteristic C
Graph showing tripping time in seconds/minutes versus multiples of rated current (I/In). The curve indicates the tripping behavior for AC and DC, with a limit characteristic from a cold state.
Dimensional Drawing
Illustrations showing the dimensions of the 8530/1 miniature circuit breaker in millimeters and inches. Includes views of the 3-pole unit without auxiliary contacts and the overall dimensions.
Accessories
Lockable Device
A lock-out / tag-out shear for individually locking the component using up to 4 cylinder locks.
- Article No.: 227232
Mounting Set
A mounting set for attaching the component to the mounting plate without a top-hat rail.
- Article No.: 276618
Cylinder Lock
For locking (shackle Ø 3)
- Article No.: 107115
Subject to technical changes, changes in dimensions, weights, constructions, and delivery possibilities. Illustrations are non-binding.