R. STAHL Circuit Breaker 8530/1-MCB-STA103-C50-000-3
Article Number: 272183
Product Description
The R. STAHL 8530 series circuit breakers offer excellent current limitation in case of short circuits and high breaking capacity (10, 15, or 25 kA). This results in reduced stress on electrical lines and improved selectivity with respect to upstream fuses. The modules feature a modular design, available in 1 to 4 pole configurations, with nominal currents from 0.5–63 A. The maximum mounting width is 4.5 division units.
Key Features:
- Separator function according to EN 60947-2
- Energy limitation class 3
- Simple replacement or expansion of installations due to modular design
- Easy mounting via DIN rail snap-on in Ex e enclosures
- Thermally and magnetically tripped, with fixed settings
- Ergonomic operating lever for secure connection and disconnection
- Protection against re-closing during maintenance using padlocks (Accessories)
Technical Data
Explosion Protection
Parameter | Value |
---|---|
Applications (zones) | 1, 2 |
Applications (zones) Note | Can be used in zones 21/22 with protection by Ex tb/tc enclosure |
IECEX gas approval | IECEX FMG 19.0029U |
IECEx protection against gas explosion | Ex db eb IIC Gb |
ATEX gas approval | FM19ATEX0191U |
ATEX protection against gas explosion | II 2 G Ex db eb IIC Gb |
Certifications | ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM) |
Certificate of conformity | Certificate of conformity (ATEX), China (CCC) |
Electrical Data
Parameter | Value |
---|---|
Rated operating voltage AC | 230/400 V |
Rated operating current | 50 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 104 |
Mechanical service life | 2 x 104 |
1st auxiliary function | none |
1st auxiliary function voltage AC | - |
Max. current 1st auxiliary function | - |
2nd auxiliary function | none |
Max. voltage 2nd auxiliary function DC | - |
Tripping characteristic | C |
Number of poles | 3-pole |
Mechanical Data
Parameter | Value |
---|---|
Ambient temperature | -40 °C ... 70 °C |
Storage temperature | -40 °C ... 70 °C |
Ambient temperature (Fahrenheit) | -40 °F ... 158 °F |
Storage temperature (Fahrenheit) | -40°F ... +158°F |
Ambient temperature Note | Divergent ambient temperatures based on valid certificates upon request |
Degree of protection (IP) (IEC 60529) | IP2X |
Enclosure material | Thermoplastic |
Connection terminal minimum cross-section | 1.5 mm² |
Connection terminal maximum cross-section | 25 mm² |
Connection terminal AWG min. | 16 AWG |
Connection terminal AWG max. | 4 AWG |
Connection terminal 2 minimum cross-section | 1.5 mm² |
Connection terminal 2 maximum cross-section | 10 mm² |
Connection terminal 2 AWG min. | 16 AWG |
Connection terminal 2 AWG max. | 8 AWG |
Tightening torque minimum | 2 N·m |
Tightening torque maximum | 3 N·m |
Connection terminal Note | 2 conductor connections (upper and lower chamber simultaneously): lower and upper chamber max. 16 / 10 mm² (only one cross-section difference can be connected between the upper and lower chamber.) Permitted connection cross-section combinations are listed in the user manual. |
Width | 83 mm |
Width mounting in inches | 3.27 in |
Length | 165 mm |
Length in inches | 6.5 in |
Installation depth | 138.3 mm |
Installation depth in inches | 5.44 in |
Weight | 1.4 kg |
Weight (lb) | 3.087 lb |
Mounting / Installation | |
Tightening torque | 2-3 N·m |
Tightening torque lbf in | 17.7 ... 26.6 lbf-in |
Auxiliary contact tightening torque | 0.4–0.6 N·m |
Auxiliary contact tightening torque lbf in | 3.5 ... 5.3 lbf in |
Technical Diagrams
Tripping Characteristic Curve: The document includes a graph illustrating the tripping characteristic curve 'C' for the circuit breaker, showing the relationship between multiples of the rated current (I/In) and tripping time in seconds for both AC and DC applications.
Dimensional Drawings: Detailed drawings show the dimensions of the circuit breaker, including width, height, depth, and mounting details, with measurements provided in both millimeters and inches.
Accessories
Accessory | Description | Article Number |
---|---|---|
Cylinder lock | For locking (shackle Ø 3) | 107115 |
Quadruple locking device | Locking/tagging pliers for individual component locking using up to 4 cylinder locks. | 227232 |
Fixing kit | A fixing kit for mounting the component on the mounting plate without a top hat rail. | 276618 |
R. STAHL reserves the right to modify technical data, dimensions, weights, constructions, and delivery options.
Contact Information:
R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG