R. STAHL Circuit Breaker 8530/1-MCB-STA103-C63-000-3
Article No. 267213
Product Description
The R. STAHL 8530 series circuit breakers offer excellent current limitation in case of short circuits and high breaking capacities of 10, 15, or 25 kA. This results in reduced stress on electrical lines and high selectivity with respect to upstream fuses. The modules are designed with a modular structure, available in 1 to 4 pole versions and for nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.
Key Features:
- Disconnecting function according to EN 60947-2
- Energy limiting class 3
- Simple replacement or expansion of installations due to modular design
- Easy mounting via DIN rail clip in Ex e enclosures
- Fixed thermal and magnetic trip adjustment
- Ergonomic operating lever for safe connection and disconnection
- Protection against reconnection during maintenance using padlocks (Accessories)
Technical Data
Explosion Protection
Applications (zones) | 1, 2 |
---|---|
Applications (zones) Note | Can be used in zones 21/22 with protection by Ex tb/tc enclosure |
IECEX gas certification | IECEX FMG 19.0029U |
IECEx gas explosion protection | Ex db eb IIC Gb |
ATEX gas certification | FM19ATEX0191U |
ATEX gas explosion protection | II 2 G Ex db eb IIC Gb |
Certifications | ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM) |
Certificate of conformity | Certificate of conformity (ATEX), China (CCC) |
Electrical Data
Rated operating voltage AC | 230/400 V |
---|---|
Rated operating current | 63 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 104 |
Mechanical service life | 2 x 104 |
1st auxiliary function | none |
1st auxiliary function voltage AC | - |
Max. current 1st auxiliary function | - |
2nd auxiliary function | none |
Max. voltage 2nd auxiliary function DC | - |
Trip characteristic | C |
Number of poles | 3-pole |
Environmental Conditions
Ambient temperature | -40 °C ... 70 °C |
---|---|
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature Note | Divergent ambient temperatures based on valid certificates upon request |
Mechanical Data
Degree of protection (IP) (IEC 60529) | IP2X |
---|---|
Enclosure material | Thermoplastic |
Connection terminal cross-section min. | 1.5 mm² |
Connection terminal cross-section max. | 25 mm² |
Connection terminal AWG min. | 16 AWG |
Connection terminal AWG max. | 4 AWG |
Connection 2 cross-section min. | 1.5 mm² |
Connection 2 cross-section max. | 10 mm² |
Connection 2 AWG min. | 16 AWG |
Connection 2 AWG max. | 8 AWG |
Tightening torque min. | 2 N·m |
Tightening torque max. | 3 N·m |
Connection terminal Note | 2 conductor connections (upper and lower chamber simultaneously): Lower and upper chamber max. 16 / 10 mm² (only a maximum cross-section difference between the upper and lower chamber can be wired). Permitted connection cross-section combinations are shown in the user instructions. |
Width | 83 mm (3.27 in) |
Length | 165 mm (6.5 in) |
Mounting depth | 138.3 mm (5.44 in) |
Weight | 1.4 kg (3.087 lb) |
Mounting / Installation
Tightening torque | 2-3 N·m (17.7 ... 26.6 lbf-in) |
---|---|
Tightening torque auxiliary contact | 0.4–0.6 Nm (3.5 ... 5.3 lbf in) |
Technical Diagrams
Trip Characteristic Curve: The document includes a technical diagram illustrating the trip characteristic curve for the circuit breaker, showing the relationship between time of trip and multiple of rated current (I/In) for both AC and DC circuits, with a 'C' trip characteristic.
Dimensional Drawings: Schematics showing the dimensions of the circuit breaker are provided, including width, height, and mounting dimensions, with measurements in both millimeters and inches.
Accessories
-
?
Cylinder lock for blocking (Ø 3mm shackle)
Article No.: 107115 -
?
Quadruple immobilization device: Locking and labeling pliers for individual component locking using up to 4 cylinder locks.
Article No.: 227232 -
?
Fixing kit: A set of fixings for mounting the component on the mounting plate without a top-hat rail.
Article No.: 276618