R. STAHL 8530/1-MCB-STA103N-B6-000-4 Circuit Breaker
Article Number: 293843
Key Features
- Circuit breaker according to EN 60947-2
- Energy limiting class 3
- Easy replacement or expansion of installations thanks to modular design
- Simple mounting via DIN mounting rail in Ex e enclosures
- Thermally and magnetically tripped, fixed setting
- Ergonomic operating lever for safe connection and disconnection
- Protection against re-energization during maintenance with padlocks (Accessories)
Product Overview
R. STAHL 8530 series circuit breakers offer excellent current limitation in short-circuit situations and high breaking capacities of 10, 15, or 25 kA. This results in reduced stress on electrical lines and high selectivity with upstream fuses. The modules feature a modular design, available in 1 to 4-pole versions, with nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.
Technical Data
Explosion Protection
Applications (zones) | Applications (zones) Note | IECEX gas approval | IECEx Gas Explosion Protection | ATEX gas approval | ATEX Gas Explosion Protection |
---|---|---|---|---|---|
1, 2 | Can be used in zones 21/22 with Ex tb/tc enclosure protection | IECEX FMG 19.0029U | Ex db eb IIC Gb | FM19ATEX0191U | II 2 G Ex db eb IIC Gb |
Certifications
- Certifications: ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM)
- Certificate of conformity (ATEX)
Electrical Data
Rated operational voltage AC | Rated operational current | Frequency | Rated switching capacity | Electrical service life | Mechanical service life | 1st Auxiliary function | Voltage 1st Auxiliary function AC | Max. current 1st Auxiliary function | 2nd Auxiliary function | Max. voltage 2nd Auxiliary function DC | Trip characteristic | Number of poles |
---|---|---|---|---|---|---|---|---|---|---|---|---|
230/400 V | 6 A | 50/60 Hz | 10 kA | 2 x 10⁴ | 2 x 10⁴ | none | - | - | none | - | B | 3-pole + N |
Environmental Conditions
Ambient temperature | Ambient temperature | Ambient temperature | Ambient temperature | Ambient temperature Note |
---|---|---|---|---|
-40 °C ... 70 °C | -40 °C ... 70 °C | -40 °F ... 158 °F | -40°F ... +158°F | Divergent ambient temperatures based on current valid certificates upon request |
Mechanical Data
Degree of protection (IP) (IEC 60529) | Enclosure material | Minimum connection cross-section | Maximum connection cross-section | Minimum AWG connection cross-section | Maximum AWG connection cross-section | Minimum connection cross-section 2 | Maximum connection cross-section 2 | Minimum AWG connection cross-section 2 | Maximum AWG connection cross-section 2 | Minimum tightening torque | Maximum tightening torque | Connection cross-section Note |
---|---|---|---|---|---|---|---|---|---|---|---|---|
IP2X | Thermoplastic | 1.5 mm² | 25 mm² | 16 AWG | 4 AWG | 1.5 mm² | 10 mm² | 16 AWG | 8 AWG | 2 N·m | 3 N·m | 2 connections (upper and lower chamber simultaneously): max. upper chamber 16 / lower chamber 10 mm² (only a difference in cross-section between upper and lower chamber can be connected) |
Allowed connection cross-section combinations are in the user manual.
Width | Width mounting in inches | Length | Length in inches | Installation depth | Installation depth in inches | Weight | Weight in lbs |
---|---|---|---|---|---|---|---|
110 mm | 4.33 in | 165 mm | 6.5 in | 138.3 mm | 5.44 in | 1.8 kg | 3.969 lb |
Mounting / Installation
Tightening torque | Tightening torque lbf in | Auxiliary contact tightening torque | Auxiliary contact tightening torque lbf in |
---|---|---|---|
2-3 N·m | 17.7 ... 26.6 lbf-in | 0.4–0.6 N·m | 3.5 ... 5.3 lbf in |
Technical Drawings
Technical drawings - Subject to change without notice.
Diagram 1: Trip time curve for Type B characteristic (AC/DC)
Description of Diagram 1: A graph showing the trip time in seconds and minutes against the current in multiples of the rated current. It illustrates the tripping behavior of the circuit breaker under different current loads, with curves for AC and DC.
Diagram 2: Measurement scheme (all dimensions in [inches])
Description of Diagram 2: A technical drawing showing the dimensions of the circuit breaker, including width, length, installation depth, and mounting details. Dimensions are provided in both millimeters and inches.
Diagram 3: 8530/1; 4 division units
Description of Diagram 3: A visual representation of the circuit breaker's physical layout and its modularity, indicating it occupies 4 division units.
Accessories
Item | Description | Article Number |
---|---|---|
? Cylinder lock | For locking (Ø 3 mm shackle) | 107115 |
Quadruple immobilisation device | Locking/tagging tongs for individual component locking using up to 4 cylinder locks. | 227232 |
Fixing kit | A fixing kit for mounting the component on the mounting plate without a top-hat rail. | 276618 |
R. STAHL reserves the right to modify technical data, dimensions, weights, constructions, and delivery options.
Contact R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG for more information.