R. STAHL Circuit Breaker 8530/1-MCB-STA103N-C20-000-4

Article Number: 293857

Product Overview

The R. STAHL 8530 series circuit breakers offer excellent current limitation in case of short circuits and high breaking capacities of 10, 15, or 25 kA. This results in reduced stress on electrical lines and improved selectivity with upstream fuses. The modules feature a modular design, available in 1 to 4 pole configurations, with nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.

Key Features:

  • Circuit breaker function according to EN 60947-2
  • Energy limitation class 3
  • Easy replacement or expansion of installations due to modular design
  • Simple mounting via DIN rail snap-on in Ex e enclosures
  • Fixed thermal and magnetic tripping adjustment
  • Ergonomic operating lever for secure connection and disconnection
  • Protection against re-energization during maintenance using padlocks (Accessories)

Technical Data

Explosion Protection

Parameter Value
Applications (zones) 1, 2
Applications (zones) Note Can be used in zones 21/22 with protection by enclosure Ex tb/tc
IECEX gas certification IECEX FMG 19.0029U
IECEx gas explosion protection Ex db eb IIC Gb
ATEX gas certification FM19ATEX0191U
ATEX gas explosion protection II 2 G Ex db eb IIC Gb
Certifications ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM)
Certificate of conformity Certificate of conformity (ATEX)

Electrical Data

Parameter Value
Rated operating voltage AC 230/400 V
Rated operating current 20 A
Frequency 50/60 Hz
Rated switching capacity 10 kA
Electrical service life 2 x 10⁴
Mechanical service life 2 x 10⁵
1st auxiliary function none
1st auxiliary function voltage AC -
Max. current 1st auxiliary function -
2nd auxiliary function none
Max. voltage 2nd auxiliary function DC -
Tripping characteristic C
Number of poles 3 pole + N

Environmental Conditions

Parameter Value
Ambient temperature -40 °C ... 70 °C
Ambient temperature -40 °C ... 70 °C
Ambient temperature -40 °F ... 158 °F
Ambient temperature -40°F ... +158°F
Ambient temperature Note Divergent ambient temperatures based on valid certificates upon request

Mechanical Data

Parameter Value
Degree of protection (IP) (IEC 60529) IP2X
Enclosure material Thermoplastic
Connection terminal cross-section min. 1.5 mm²
Connection terminal cross-section max. 25 mm²
Connection terminal AWG min. 16 AWG
Connection terminal AWG max. 4 AWG
Connection terminal 2 cross-section min. 1.5 mm²
Connection terminal 2 cross-section max. 10 mm²
Connection terminal 2 AWG min. 16 AWG
Connection terminal 2 AWG max. 8 AWG
Tightening torque min. 2 N·m
Tightening torque max. 3 N·m
Connection terminal Note 2 conductor connections (upper and lower chamber simultaneously): lower and upper chamber max. 16 / 10 mm² (a cross-sectional difference between the upper and lower chamber of max. one size can be connected). Permitted connection cross-section combinations are listed in the user manual.
Width 110 mm
Mounting width in inches 4.33 in
Length 165 mm
Length in inches 6.5 in
Mounting depth 138.3 mm
Mounting depth in inches 5.44 in
Weight 1.8 kg
Weight 3.969 lb

Mounting / Installation

Parameter Value
Tightening torque 2-3 N·m
Tightening torque lbf in 17.7 ... 26.6 lbf-in
Auxiliary contact tightening torque 0.4–0.6 Nm
Auxiliary contact tightening torque lbf in 3.5 ... 5.3 lbf in

Technical Diagrams

Tripping Characteristic Curve C

Shows the tripping behavior of the circuit breaker for different multiples of the rated current (In) under AC and DC conditions.

Measurement Diagram

Provides dimensional information for the circuit breaker, including width, length, and mounting depth, with measurements in both millimeters and inches.

3-pole + N, without auxiliary contact

Illustrates the pole configuration of the circuit breaker.

Accessories

Accessory Description Article Number
Cylinder lock For locking (shackle Ø 3) 107115
Quadruple immobilization device Locking/labeling pliers for individual component locking using up to 4 cylinder locks. 227232
Fixing kit A fixing kit for mounting the component on the mounting plate without a top hat rail. 276618

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta103n-c20-000-4-293857-es-es-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA103N-C20-000-4 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103N-C20-000-4 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for use in hazardous locations.
Preview R. STAHL 8530 Series Miniature Circuit Breaker (MCB) - Technical Data and Specifications
Detailed technical specifications for the R. STAHL 8530 series miniature circuit breaker (MCB), model 8530/1-MCB-STA103N-C20-000-4. Includes information on explosion protection, electrical data, mechanical data, ambient conditions, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-B16-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-B16-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 21/22 hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103N-C6-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C6-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C25-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C25-000-4 circuit breaker, including explosion protection data, electrical characteristics, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C10-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C10-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for use in hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103N-C20-000-4 Line Protection Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103N-C20-000-4 line protection circuit breaker, including features, electrical characteristics, mechanical specifications, and accessories. Suitable for Zone 1, 2, 21, and 22 hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103N-B32-000-4 Circuit Breaker: Technical Specifications and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA103N-B32-000-4 circuit breaker, including electrical data, environmental conditions, mechanical data, and explosion protection.