Componentes para la técnica de sistemas

Disyuntor

Model: 8530/1-MCB-STA103N-C6-000-4

Article Number: 293853

Product Description

The R. STAHL 8530 series circuit breakers offer excellent short-circuit current limitation and high breaking capacity (10, 15, or 25 kA). This reduces stress on electrical lines and provides high selectivity with upstream fuses. The modules feature a modular design, are available in 1 to 4-pole versions, and support nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.

Key Features:

Technical Data

Explosion Protection

Applications (zones)1, 2
Applications (zones) NoteCan be used in zones 21/22 with enclosure protection Ex tb/tc
IECEX gas certificationIECEX FMG 19.0029U
IECEx gas explosion protectionEx db eb IIC Gb
ATEX gas certificationFM19ATEX0191U
ATEX gas explosion protectionII 2 G Ex db eb IIC Gb
CertificationsATEX (FM), Brazil (ULB), China (CQST), IECEX (FM)
Certificate of conformityCertificate of conformity (ATEX)

Electrical Data

Rated operating voltage AC230/400 V
Rated operating current6 A
Frequency50/60 Hz
Rated switching capacity10 kA
Electrical endurance2 x 10⁴
Mechanical endurance2 x 10⁴
1st auxiliary functionnone
Voltage 1st auxiliary function AC-
Maximum current 1st auxiliary function-
2nd auxiliary functionnone
Maximum voltage 2nd auxiliary function DCC
Tripping characteristicC
Number of poles3 pole + N

Environmental Conditions

Ambient temperature-40 °C ... 70 °C
Ambient temperature-40 °F ... 158 °F
Ambient temperature NoteDivergent ambient temperatures based on valid certificates upon request

Mechanical Data

Degree of protection (IP) (IEC 60529)IP2X
Enclosure materialThermoplastic
Connection terminal cross-section minimum1.5 mm²
Connection terminal cross-section maximum25 mm²
Connection terminal AWG minimum16 AWG
Connection terminal AWG maximum4 AWG
Connection terminal 2 cross-section minimum1.5 mm²
Connection terminal 2 cross-section maximum10 mm²
Connection terminal 2 AWG minimum16 AWG
Connection terminal 2 AWG maximum8 AWG
Tightening torque minimum2 N·m
Tightening torque maximum3 N·m
Connection terminal Note2 conductor connections (upper and lower chamber simultaneously): max. upper and lower chamber 16 / 10 mm² (only a difference in cross-section between the upper and lower chamber can be connected). Permitted conductor cross-section combinations are shown in the user instructions.
Width110 mm
Mounting width in inches4.33 in
Length165 mm
Length in inches6.5 in
Installation depth138.3 mm
Installation depth in inches5.44 in
Weight1.8 kg
Weight3.969 lb

Mounting / Installation

Tightening torque2-3 N·m
Tightening torque lbf in17.7 ... 26.6 lbf-in
Tightening torque auxiliary contact0.4–0.6 N·m
Tightening torque auxiliary contact lbf in3.5 ... 5.3 lbf in

Technical Diagrams

Technical diagrams - Subject to change.

Tripping time curves - Subject to change.

Measurement diagram (all dimensions in [inches]) - Subject to change.

Accessories

Cylinder lock

DescriptionCylinder lock for blocking (stirrup Ø 3)Article Number: 107115

Quadruple immobilization device

DescriptionLocking/tagging pliers for individual component locking using up to 4 cylinder locks.Article Number: 227232

Fixing kit

DescriptionA set of fixings for mounting the component on the mounting plate without a top-hat rail.Article Number: 276618

R. STAHL reserves the right to modify technical data, dimensions, weights, constructions, and delivery options.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta103n-c6-000-4-293853-es-es-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA103N-C6-000-4 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C6-000-4 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C6-000-4 Miniature Circuit Breaker - Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C6-000-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-B16-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-B16-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 21/22 hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103N-C25-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C25-000-4 circuit breaker, including explosion protection data, electrical characteristics, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C20-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C20-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for use in hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103N-C10-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C10-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for use in hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103N-B32-000-4 Circuit Breaker: Technical Specifications and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA103N-B32-000-4 circuit breaker, including electrical data, environmental conditions, mechanical data, and explosion protection.
Preview R. STAHL 8530/1-MCB-STA103N-C32-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C32-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.