R. STAHL 8530/1-MCB-STA103N-B6-000-4 Line Protection Circuit Breaker
Article Number: 293843
Product Overview
The R. STAHL 8530 series line protection circuit breakers offer excellent current limitation for short circuits and high switching capacities of 10, 15, or 25 kA. They are designed for minimal line load and high selectivity to upstream fuses. These modular components are available in 1 to 4-pole versions with nominal currents from 0.5–63 A, supporting a maximum installation capacity of 4.5 modular units (MU).
Key features include:
- Disconnection function according to EN 60947-2
- Energy limitation class 3
- Easy replacement and system extension due to modular design
- Simple snap-on mounting on DIN rails in Ex e enclosures
- Fixed magneto-thermal trip units
- Ergonomic operating lever for safe switching on and off
- Padlock protection (accessories) prevents re-operation during maintenance
Technical Characteristics
Explosion Protection
Application Area (Zones) | Application Area (Zones) Note | Certificates | Explosion Protection Certificate |
---|---|---|---|
1, 2 | Usable in Zone 21 / 22 with Ex tb / tc enclosure protection | IECEx FMG 19.0029U | Ex db eb IIC Gb |
FM19ATEX0191U | II 2G Ex db eb IIC Gb | ||
ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM) | ATEX (FM) |
Electrical Characteristics
Characteristic | Value |
---|---|
Rated operational voltage AC | 230/400 V |
Rated service current | 6 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 104 |
Mechanical service life | 2 x 104 |
1st auxiliary function | None |
Voltage 1st auxiliary function AC | - |
Current max. 1st auxiliary function | - |
2nd auxiliary function | None |
Max. voltage 2nd auxiliary function DC | - |
Tripping characteristic | B |
Number of poles | 3 poles + N |
Ambient Conditions
Condition | Value |
---|---|
Ambient temperature | -40 °C ... 70 °C (-40 °F ... 158 °F) |
Ambient temperature Note | Ambient temperatures differing based on current certificates, on request |
Mechanical Characteristics
Characteristic | Value |
---|---|
Degree of protection (IP) (IEC 60529) | IP2X |
Housing material | Thermoplastic |
Minimum connection terminal size | 1.5 mm² |
Maximum connection terminal size | 25 mm² |
Minimum AWG connection terminal size | 16 AWG |
Maximum AWG connection terminal size | 4 AWG |
Minimum connection terminal size 2 | 1.5 mm² |
Maximum connection terminal size 2 | 10 mm² |
AWG connection terminal size 2 min. | 16 AWG |
AWG connection terminal size 2 max. | 8 AWG |
Minimum tightening torque | 2 N·m |
Maximum tightening torque | 3 N·m |
Connection terminal note | 2-conductor connection (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.) Permitted combination possibilities of connection terminals are indicated in the operating instructions. |
Width | 110 mm (4.33 in) |
Length | 165 mm (6.5 in) |
Mounting depth | 138.3 mm (5.44 in) |
Weight | 1.8 kg (3.969 lb) |
Mounting / Installation
Characteristic | Value |
---|---|
Tightening torque | 2–3 N·m (17.7 ... 26.6 lbf-in) |
Tightening torque auxiliary contact | 0.4–0.6 Nm (3.5 ... 5.3 lbf-in) |
Technical Drawings
Overall dimensions (all dimensions in mm [inches])
Circuit breaker dimensions:
- Width: 110 [4.33]
- Length: 165 [6.50]
- Height: 91.50 [3.60]
- Mounting depth: 138.30 [5.44]
- Total width including adjacent modules: 127.60 [5.02]
- Width of 4 modules: 8530/1; 4 division units
Tripping Characteristic Curve B:
A graph shows the tripping characteristic for Type B circuit breakers. The x-axis represents multiples of the rated current (I/In), ranging from 0.1 to 30. The y-axis represents time in seconds and minutes, ranging from 0.01 to 120. The curve illustrates the time it takes for the breaker to trip based on the current level, with a note indicating it's a limit curve from a cold state.
Accessories
Quadruple Locking Device
A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.
- Article Number: 227232
Fixing Kit
A fixing kit for attaching the component to a mounting plate without a DIN rail.
- Article Number: 276618
Cylinder Lock
For locking (shackle Ø 3)
- Article Number: 107115
Note: Technical specifications, dimensions, weights, construction types, and delivery possibilities are subject to change without notice. Figures are for illustrative purposes only.
Manufacturer: R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG | Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com