R. STAHL 8530/1-MCB-STA103N-B16-000-4 Circuit Breaker
This document provides technical specifications for the R. STAHL 8530/1-MCB-STA103N-B16-000-4 circuit breaker, article number 293846.
Product Features
- Separator function according to EN 60947-2
- Energy limitation class 3
- Simple replacement or expansion of installations thanks to modular design
- Easy mounting via DIN rail in Ex e enclosures
- Fixed thermal and magnetic trip adjustment
- Ergonomic operating lever for safe connection and disconnection
- Protection against re-energization during maintenance with padlocks (accessories)
General Description
R. STAHL 8530 series circuit breakers offer good current limitation in case of short circuits and high breaking capacity (10, 15, or 25 kA). This results in reduced stress on electrical lines and high selectivity with respect to upstream fuses. The modules feature a modular structure, are available in 1 to 4-pole versions, and support nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.
Technical Data
Explosion Protection
Parameter | Value |
---|---|
Applications (zones) | 1, 2 |
Applications (zones) Note | Can be used in zones 21/22 with protection by Ex tb/tc enclosure |
IECEX gas certification | IECEx FMG 19.0029U |
IECEx Gas Explosion Protection | Ex db eb IIC Gb |
ATEX gas certification | FM19ATEX0191U |
ATEX Gas Explosion Protection | II 2 G Ex db eb IIC Gb |
Certifications | ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM) |
Certificate of Conformity | Certificate of Conformity (ATEX) |
Electrical Data
Parameter | Value |
---|---|
Rated operating voltage AC | 230/400 V |
Rated operating current | 16 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 10⁴ |
Mechanical service life | 2 x 10⁴ |
1st auxiliary function | None |
1st auxiliary function voltage AC | - |
1st auxiliary function current | - |
2nd auxiliary function | None |
Max. voltage 2nd aux. function DC | - |
Trip characteristic | B |
Number of poles | 3-pole + N |
Environmental Conditions
Parameter | Value |
---|---|
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature Note | Divergent ambient temperatures based on valid certificates upon request |
Mechanical Data
Parameter | Value |
---|---|
Degree of protection (IP) (IEC 60529) | IP2X |
Enclosure material | Thermoplastic |
Connection cross-section min. | 1.5 mm² |
Connection cross-section max. | 25 mm² |
Connection cross-section AWG min. | 16 AWG |
Connection cross-section AWG max. | 4 AWG |
Connection 2 cross-section min. | 1.5 mm² |
Connection 2 cross-section max. | 10 mm² |
Connection 2 AWG min. | 16 AWG |
Connection 2 AWG max. | 8 AWG |
Minimum tightening torque | 2 N·m |
Maximum tightening torque | 3 N·m |
Connection cross-section Note | 2 conductor connections (upper and lower chamber simultaneously): max. upper and lower chamber 16 / 10 mm² (only a difference in cross-section between the upper and lower chamber can be connected). Permitted connection cross-section combinations are listed in the user manual. |
Width | 110 mm |
Mounting width in inches | 4.33 in |
Length | 165 mm |
Length in inches | 6.5 in |
Installation depth | 138.3 mm |
Installation depth in inches | 5.44 in |
Weight | 1.8 kg |
Weight in pounds | 3.969 lb |
Mounting / Installation
Parameter | Value |
---|---|
Tightening torque | 2-3 N·m |
Tightening torque lbf·in | 17.7 ... 26.6 lbf·in |
Tightening torque auxiliary contact | 0.4–0.6 N·m |
Tightening torque auxiliary contact lbf·in | 3.5 ... 5.3 lbf·in |
Technical Diagrams
Characteristic Curve
A graph showing the trip characteristic curve (B) for AC and DC, illustrating the time in seconds and minutes versus current in multiples of the rated current.
Measurement Diagram
Diagrams showing the dimensions of the circuit breaker in millimeters and inches, including width, length, installation depth, and other key measurements. The diagrams indicate the unit is 8530/1, 4 division units.
Accessories
Cylinder Lock
Cylinder lock for blocking (stirrup Ø 3), article number 107115.
Locking Device
Tongs for locking/tagging for individual component locking using up to 4 cylinder locks, article number 227232.
Fixing Kit
A set of fixings for mounting the component on the mounting plate without a top-hat rail, article number 276618.
R. STAHL reserves the right to modify technical data, dimensions, weights, constructions, and delivery options.