Componentes para la técnica de sistemas

Disyuntor

Model: 8530/1-MCB-STA103N-C10-000-4

Article No.: 293854

Key Features

R. STAHL 8530A Series Circuit Breakers: Offer excellent current limitation in case of short circuits and high breaking capacity (10, 15, or 25 kA). This results in reduced load on electrical lines and high selectivity with respect to upstream fuses. The modules feature a modular structure, available in 1 to 4-pole versions for nominal currents from 0.5–63 A. Maximum mounting capacity is 4.5 division units.

Technical Data

Explosion Protection

Applications (zones) 1, 2
Applications (zones) Note Can be used in zones 21/22 with protection by Ex tb/tc enclosure
IECEX gas certification IECEX FMG 19.0029U
IECEx Gas Explosion Protection Ex db eb IIC Gb
ATEX gas certification FM19ATEX0191U
ATEX Gas Explosion Protection II 2 G Ex db eb IIC Gb
Certifications ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM)
Certificate of conformity Certificate of conformity (ATEX)

Electrical Data

Rated operating voltage AC 230/400 V
Rated operating current 10 A
Frequency 50/60 Hz
Rated switching capacity 10 kA
Electrical service life 2 x 10⁴
Mechanical service life 2 x 10⁴
1st auxiliary function none
Voltage 1st auxiliary function AC -
Max. current 1st auxiliary function -
2nd auxiliary function none
Max. voltage 2nd auxiliary function DC -
Trip characteristic C
Number of poles 3-pole + N

Environmental Conditions

Ambient temperature -40 °C ... 70 °C
Ambient temperature -40 °C ... 70 °C
Ambient temperature -40 °F ... 158 °F
Ambient temperature -40°F ... +158°F
Ambient temperature Note Divergent ambient temperatures based on valid certificates upon request

Mechanical Data

Degree of protection (IP) (IEC 60529) IP2X
Enclosure material Thermoplastic
Connection terminal cross-section min. 1.5 mm²
Connection terminal cross-section max. 25 mm²
Connection terminal AWG min. 16 AWG
Connection terminal AWG max. 4 AWG
Connection terminal 2 cross-section min. 1.5 mm²
Connection terminal 2 cross-section max. 10 mm²
Connection terminal 2 AWG min. 16 AWG
Connection terminal 2 AWG max. 8 AWG
Tightening torque min. 2 N·m
Tightening torque max. 3 N·m
Connection terminal Note 2 conductor connections (upper and lower chamber simultaneously): lower and upper chamber max. 16 / 10 mm² (only one cross-sectional difference between upper and lower chamber can be connected). Permitted connection terminal cross-section combinations are listed in the user manual.
Width 110 mm
Mounting width in inches 4.33 in
Length 165 mm
Length in inches 6.5 in
Installation depth 138.3 mm
Installation depth in inches 5.44 in
Weight 1.8 kg
Weight 3.969 lb

Mounting / Installation

Tightening torque 2-3 N·m
Tightening torque lbf·in 17.7 ... 26.6 lbf·in
Tightening torque auxiliary contact 0.4–0.6 N·m
Tightening torque auxiliary contact lbf·in 3.5 ... 5.3 lbf·in

Technical Diagrams

Trip Curve: The document includes a technical diagram illustrating the trip characteristic curve for the circuit breaker, showing the relationship between multiples of the rated current (I/In) and time (seconds/minutes) for both AC and DC applications, with a specific focus on trip characteristic C.

Dimensional Drawing: A measurement diagram is provided, showing the overall dimensions of the 8530/1; 4 division units circuit breaker. Key dimensions include width (110 mm / 4.33 in), length (165 mm / 6.50 in), installation depth (138.3 mm / 5.44 in), and height details.

Accessories

Cylinder Lock

Description Cylinder lock (stirrup Ø 3) for blocking (individual component blocking using up to 4 cylinder locks) Article No. 107115

Fixing Kit

Description Fixing kit for mounting the component on the mounting plate without a top hat rail Article No. 276618

R. STAHL Schaltgeräte GmbH reserves the right to modify technical data, dimensions, weights, constructions, and delivery options.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta103n-c10-000-4-293854-es-es-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA103N-C10-000-4 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C10-000-4 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C10-000-4 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103N-C10-000-4 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for use in hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103N-C10-000-4 Miniature Circuit Breaker - Technical Data and Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA103N-C10-000-4 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for system solutions in hazardous environments.
Preview R. STAHL 8530/1-MCB-STA103N-B16-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-B16-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Zone 21/22 hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103N-C6-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C6-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C25-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C25-000-4 circuit breaker, including explosion protection data, electrical characteristics, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA103N-C20-000-4 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA103N-C20-000-4 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for use in hazardous areas.
Preview R. STAHL 8530/1-MCB-STA103N-B32-000-4 Circuit Breaker: Technical Specifications and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA103N-B32-000-4 circuit breaker, including electrical data, environmental conditions, mechanical data, and explosion protection.