Image shows the V33D030S6-5P VRF 4-Way Cassette indoor unit, a compact, square-shaped unit designed for ceiling installation, featuring a grille on the front panel.
- Compatible with R-32 VRF air, water, and mini-VRF systems.
- The indoor unit shall feature Calm air mode. When activated in cooling mode, the unit will close its louver and will disperse air into the space through thousands of micro-holes on the front of the indoor unit, preventing cold air drafts on occupants.
- The indoor unit shall have an integral condensate pump with maximum 30-3/8" lift from bottom of the unit (21-5/8" from drain outlet) with check valve and float switch to disable unit in the event of condensate overflow.
- The indoor unit fascia panel shall have a built-in Wi-Fi adapter as standard to allow control and monitoring using the Samsung SmartThings app.
- Knock out for outside air capability.
Construction
- Insulated, HIPS chassis and fascia panel certified to UL94 V0.
- High-voltage terminal block temperature sensor to disable unit in the event of power connection overheating.
Refrigerant System
- The heat exchanger shall be mechanically bonded aluminum fin to copper tube.
- The indoor unit shall include an R32 alarm output plug for simple notification or interlock of third-party equipment upon R32 leak detection (VSTAT10P-1 accessory required).
Indoor Fan
- Indoor fan is a single turbo type.
- Three fan speed settings and auto settings.
- Electro-static, washable filter as standard (included with fascia panel).
- Fascia panel shall have LED indicator lights, infrared receiver, and (4) motorized louvers with independent control (32°-65° louver control range).
Controls
- Control wiring shall be 2 X 16 AWG.
- The unit shall be operated via a wired remote controller model VSTAT04P-1, purchased separately.
- Dual set temperature support when connected to supported controllers.
- Wired or wireless controllers must be purchased separately.
External Heat Control
- External heat control functionality allows for configuration of fan operation during auxiliary heat operation, defrost, and emergency heat (VSTAT10P-1 accessory required).
- External heat control configuration settings include outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).
- Emergency heat functionality allows the system to continue controlling the external heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).
- External heat control functionality allows for configuration of fan operation during auxiliary heat operation, defrost, and emergency heat.
- Emergency heat functionality allows the system to continue controlling the external heat source even when system errors prevent the heat pump from operating.
Convenience
- Emergency Temperature Output (ETO) function: when indoor unit is in error status or when room temperature exceeds a configurable temperature level, the system outputs a signal to an external source (e.g., backup system, building management system, alert device like status light, warning lamp, or buzzer).
Specifications
Category | Parameter | Value |
---|---|---|
Model | Indoor Unit Model Number | V33D030S6-5P |
Performance | Nominal Capacity Cooling (Btu/h) | 30,000 |
Nominal Capacity Heating (Btu/h) | 34,000 | |
Power | Voltage (Ø / V / Hz) | 1 / 208-230 / 60 |
Power | Operating Current (max.) Cooling (A) | 0.90 |
Operating Current (max.) Heating (A) | 0.90 | |
MCA (A) | 1.39 | |
Power | MOP (A) | 15 |
Evaporator Fan | Type | BLDC (1) With Turbo Type Fan (1) |
Output (Watts) | 97 | |
Airflow | Air Volume (L/M/H) Cooling (CFM) | 901 / 1,130 / 1,342 |
Air Volume (L/M/H) Heating (CFM) | 901 / 1,130 / 1,342 | |
Refrigerant | Type | R-32 |
A2L Leak Detection | Integral | |
Pipe Connections | High side (In.) | 3/8 |
Pipe Connections | Low side (In.) | 5/8 |
Condensate | (In.) | 1 1/4 in. OD, 1 in. ID |
Dimensions | W x H x D (In.) | 33 1/16 X 11 5/16 X 33 1/16 |
Weight (lbs.) | 49.20 | |
Sound Pressure Level | Low/Med./High (dB(A)) | 35 / 39 / 43.5 |
Safety | Certifications | UL 60335-2-40 |
Fascia Panel L x W x H (In.) | 37 3/8 X 37 3/8 X 7/8 | |
Fascia Panel | Weight (lbs.) | 13.9 |
Fascia Panel | Certifications | UL 60335-2-40 |
Accessories
Category | Description | Model Number |
---|---|---|
Fascia Panel | White | V1V33D01CPWW |
Black | V1V33D01CPBW | |
Wired controller | Advanced | VSTAT04P-1 |
Touchscreen | VSTAT02P-1 | |
Thermostat adapter | (for connection to standard 24VAC thermostats) | VSTAT09P-1 |
Wireless controller | VSTAT01P-1 | |
External temperature sensor | VCTRL11P-1 | |
External contact control interface module | VSTAT10P-1 | |
Motion Detect Sensor (MDS) | V1MDS01CS | |
CN83 Pigtail | (for 12VDC VENT output) | JV DB39-01263A CN83 Pigtail |
Dimensional Drawing
Dimensional drawing provides detailed measurements for the V33D030S6-5P VRF 4-Way Cassette indoor unit. It includes top, side, and bottom views, indicating dimensions for installation, pipe connections, and air intake. Key dimensions include overall width and depth of approximately 33-1/16 inches, and height of approximately 11-5/16 inches. The drawing also labels connection points for liquid and gas pipes, condensate drain, power/communication conduit, and fresh air intake.
No. | Description |
---|---|
1 | Liquid pipe connection (3/8) |
2 | Gas pipe connection (5/8) |
3 | Drain hose connection |
4 | Opening for power and communication wire conduit |
5 | Fresh air intake (Ø 4") |