LENNOX V33D030S6-5P VRF 4-Way Cassette Indoor Unit Submittal Data

LENNOX V33D030S6-5P VRF 4-Way Cassette (3 x 3) Submittal Data

Powered by SAMSUNG

General Information

Image shows the V33D030S6-5P VRF 4-Way Cassette indoor unit, a compact, square-shaped unit designed for ceiling installation, featuring a grille on the front panel.

  • Compatible with R-32 VRF air, water, and mini-VRF systems.
  • The indoor unit shall feature Calm air mode. When activated in cooling mode, the unit will close its louver and will disperse air into the space through thousands of micro-holes on the front of the indoor unit, preventing cold air drafts on occupants.
  • The indoor unit shall have an integral condensate pump with maximum 30-3/8" lift from bottom of the unit (21-5/8" from drain outlet) with check valve and float switch to disable unit in the event of condensate overflow.
  • The indoor unit fascia panel shall have a built-in Wi-Fi adapter as standard to allow control and monitoring using the Samsung SmartThings app.
  • Knock out for outside air capability.

Construction

  • Insulated, HIPS chassis and fascia panel certified to UL94 V0.
  • High-voltage terminal block temperature sensor to disable unit in the event of power connection overheating.

Refrigerant System

  • The heat exchanger shall be mechanically bonded aluminum fin to copper tube.
  • The indoor unit shall include an R32 alarm output plug for simple notification or interlock of third-party equipment upon R32 leak detection (VSTAT10P-1 accessory required).

Indoor Fan

  • Indoor fan is a single turbo type.
  • Three fan speed settings and auto settings.
  • Electro-static, washable filter as standard (included with fascia panel).
  • Fascia panel shall have LED indicator lights, infrared receiver, and (4) motorized louvers with independent control (32°-65° louver control range).

Controls

  • Control wiring shall be 2 X 16 AWG.
  • The unit shall be operated via a wired remote controller model VSTAT04P-1, purchased separately.
  • Dual set temperature support when connected to supported controllers.
  • Wired or wireless controllers must be purchased separately.

External Heat Control

  • External heat control functionality allows for configuration of fan operation during auxiliary heat operation, defrost, and emergency heat (VSTAT10P-1 accessory required).
  • External heat control configuration settings include outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).
  • Emergency heat functionality allows the system to continue controlling the external heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).
  • External heat control functionality allows for configuration of fan operation during auxiliary heat operation, defrost, and emergency heat.
  • Emergency heat functionality allows the system to continue controlling the external heat source even when system errors prevent the heat pump from operating.

Convenience

  • Emergency Temperature Output (ETO) function: when indoor unit is in error status or when room temperature exceeds a configurable temperature level, the system outputs a signal to an external source (e.g., backup system, building management system, alert device like status light, warning lamp, or buzzer).

Specifications

CategoryParameterValue
ModelIndoor Unit Model NumberV33D030S6-5P
PerformanceNominal Capacity Cooling (Btu/h)30,000
Nominal Capacity Heating (Btu/h)34,000
PowerVoltage (Ø / V / Hz)1 / 208-230 / 60
PowerOperating Current (max.) Cooling (A)0.90
Operating Current (max.) Heating (A)0.90
MCA (A)1.39
PowerMOP (A)15
Evaporator FanTypeBLDC (1) With Turbo Type Fan (1)
Output (Watts)97
AirflowAir Volume (L/M/H) Cooling (CFM)901 / 1,130 / 1,342
Air Volume (L/M/H) Heating (CFM)901 / 1,130 / 1,342
RefrigerantTypeR-32
A2L Leak DetectionIntegral
Pipe ConnectionsHigh side (In.)3/8
Pipe ConnectionsLow side (In.)5/8
Condensate(In.)1 1/4 in. OD, 1 in. ID
DimensionsW x H x D (In.)33 1/16 X 11 5/16 X 33 1/16
Weight (lbs.)49.20
Sound Pressure LevelLow/Med./High (dB(A))35 / 39 / 43.5
SafetyCertificationsUL 60335-2-40
Fascia Panel L x W x H (In.)37 3/8 X 37 3/8 X 7/8
Fascia PanelWeight (lbs.)13.9
Fascia PanelCertificationsUL 60335-2-40

Accessories

CategoryDescriptionModel Number
Fascia PanelWhiteV1V33D01CPWW
BlackV1V33D01CPBW
Wired controllerAdvancedVSTAT04P-1
TouchscreenVSTAT02P-1
Thermostat adapter(for connection to standard 24VAC thermostats)VSTAT09P-1
Wireless controllerVSTAT01P-1
External temperature sensorVCTRL11P-1
External contact control interface moduleVSTAT10P-1
Motion Detect Sensor (MDS)V1MDS01CS
CN83 Pigtail(for 12VDC VENT output)JV DB39-01263A CN83 Pigtail

Dimensional Drawing

Dimensional drawing provides detailed measurements for the V33D030S6-5P VRF 4-Way Cassette indoor unit. It includes top, side, and bottom views, indicating dimensions for installation, pipe connections, and air intake. Key dimensions include overall width and depth of approximately 33-1/16 inches, and height of approximately 11-5/16 inches. The drawing also labels connection points for liquid and gas pipes, condensate drain, power/communication conduit, and fresh air intake.

No.Description
1Liquid pipe connection (3/8)
2Gas pipe connection (5/8)
3Drain hose connection
4Opening for power and communication wire conduit
5Fresh air intake (Ø 4")

PDF preview unavailable. Download the PDF instead.

sbmtl V33D030S6-5P 2508 Adobe InDesign 20.4 (Windows) Adobe PDF Library 17.0

Related Documents

Preview Lennox V33D048S6-5P VRF 4-Way Cassette Submittal Data
Technical specifications and features for the Lennox V33D048S6-5P VRF 4-Way Cassette indoor unit, including performance data, construction details, accessories, and dimensional information.
Preview Lennox V36D048S6-5P VRF 360 Cassette Indoor Unit Submittal Data
Technical specifications, features, and dimensional data for the Lennox V36D048S6-5P VRF 360 Cassette indoor unit, including construction, refrigerant system, fan, controls, and accessories.
Preview Lennox VOWD009S6-5P VRF 1-Way Cassette Indoor Unit Submittal Data & Specifications
Detailed submittal data and technical specifications for the Lennox VOWD009S6-5P VRF 1-Way Cassette indoor unit, covering general information, construction, performance, airflow, controls, and available accessories.
Preview Lennox V22D005S6-5P VRF 4-Way Cassette Indoor Unit Submittal Data
Submittal data and specifications for the Lennox V22D005S6-5P VRF 4-Way Cassette (2x2) indoor unit, detailing its features, construction, performance, controls, and accessories.
Preview Lennox Samsung VOWD024S6-5P VRF 1-Way Cassette Submittal Data
Technical specifications and features for the Lennox Samsung VOWD024S6-5P VRF 1-Way Cassette indoor unit, including performance data, dimensions, and accessories.
Preview Lennox VUCD048S6-5P VRF Ceiling Mount Submittal Data and Specifications
Detailed submittal data, specifications, and dimensional drawings for the Lennox VUCD048S6-5P VRF Ceiling Mount unit, featuring R-32 refrigerant, integral Wi-Fi, and advanced controls.
Preview Lennox VWMD018S6-5P VRF Wall Mount Indoor Unit Specifications and Features
Detailed submittal data for the Lennox VWMD018S6-5P VRF Wall Mount Indoor Unit, including specifications, features, construction, controls, and accessories. Compatible with R-32 VRF systems.
Preview Lennox V22D009S6-5P VRF 4-Way Cassette: Submittal Data & Specifications
Detailed submittal data and specifications for the Lennox V22D009S6-5P VRF 4-Way Cassette indoor unit, featuring Calm air mode, R-32 refrigerant compatibility, and advanced control options.