Lennox Submittal Data
VOWD009S6-5P VRF 1-Way Cassette
Job Information
Job Name: [Not Specified]
Purchaser: [Not Specified]
Submitted to: [Not Specified]
Unit designation: [Not Specified]
Location: [Not Specified]
Engineer: [Not Specified]
Reference: [Not Specified]
Approval: [ ] Construction: [ ]
Schedule #: [Not Specified]
General Information
• Compatible with R-32 VRF air, water, and mini systems.
• The indoor unit features Calm Air Mode. When activated in cooling mode, the unit closes its louver and disperses air through thousands of micro-holes on the front, preventing cold air drafts on occupants.
• The indoor unit has an integral condensate pump with a maximum 26-5/16" lift from the bottom of the unit (21-5/16" from drain outlet), equipped with a check valve and float switch to disable the unit in case of condensate overflow.
• The indoor unit fascia panel includes a built-in Wi-Fi adapter as standard for control and monitoring via the Samsung SmartThings app.
Construction
• Insulated, HIPS chassis and fascia panel certified to UL94 V0.
• High-voltage terminal block temperature sensor to disable the unit in the event of power connection overheating.
Refrigerant System
• The heat exchanger is mechanically bonded aluminum fin to copper tube.
• The indoor unit includes an R32 alarm output plug for simple notification or interlock of third-party equipment upon R32 leak detection (VSTAT10P-1 accessory required).
Indoor Fan
• Three fan speed settings and auto settings.
• Electro-static, washable filter is standard, included with the fascia panel.
• Fascia panel features an LED display, infrared receiver, and motorized louvers.
Controls
• Control wiring is 2 x 16 AWG.
• The unit is operated via a wired remote controller model VSTAT04P-1, purchased separately.
• Dual set temperature support is available when connected to supported controllers.
• Wired or wireless controllers must be purchased separately.
External Heat Control
• External heat control functionality allows for configuration of fan operation during auxiliary heat operation, defrost, and emergency heat (VSTAT10P-1 accessory required).
• Configuration settings include outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).
• Emergency heat functionality allows the system to continue controlling the external heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).
Convenience
• Emergency Temperature Output (ETO) function: When the indoor unit is in an error status or when room temperature exceeds a configurable level, the system outputs a signal to an external source (e.g., backup system, building management system, alert device like status light, warning lamp, or buzzer).
Specifications
Specification | Details |
---|---|
Model | VOWD009S6-5P |
Indoor Unit Model Number | VOWD009S6-5P |
Nominal Capacity (Cooling) | 9,500 Btu/h |
Nominal Capacity (Heating) | 10,500 Btu/h |
Voltage | 1 / 208-230 / 60 Hz |
Operating Current (max.) Cooling | 0.23 A |
Operating Current (max.) Heating | 0.23 A |
MCA | 0.29 A |
MOP | 15 A |
Evaporator Fan Type | BLDC motor with cross-flow fan |
Evaporator Fan Output | 23 Watts |
Airflow Cooling (CFM) | 177/212/247 |
Airflow Heating (CFM) | 177/212/247 |
Air Volume (L/M/H) Type | R-32 |
Refrigerant Leak Detection | Integral |
Refrigerant Pipe Connections (High side) | 1/4 in. |
Refrigerant Pipe Connections (Low side) | 1/2 in. |
Condensate Pipe Connection | 1 1/4 in. OD, 1 in. ID |
Dimensions (W x H x D) | 38 3/16 X 5 5/16 X 16 1/8 In. |
Dimensions Weight | 21.40 lbs. |
Sound Pressure Level (Low/Med./High) | 24/28/32 dB(A) |
Safety Certifications | UL 60335-2-40 |
Fascia Panel (L x W x H) | 47 3/16 X 19 11/16 X 1 3/8 In. |
Fascia Panel Weight | 9.5 lbs. |
Fascia Panel Safety Certifications | UL 60335-2-40 |
Accessories
Accessory | Model Number | Selection |
---|---|---|
Fascia Panel | V1VOWD03CPWW | [ ] |
Wired controller | VSTAT04P-1 | [ ] |
Advanced Touchscreen | VSTAT02P-1 | [ ] |
Thermostat adapter (for connection to standard 24VAC thermostats) | VSTAT09P-1 | [ ] |
Wireless controller | VSTAT01P-1 | [ ] |
External temperature sensor | VCTRL11P-1 | [ ] |
External contact control interface module | VSTAT10P-1 | [ ] |
CN83 Pigtail (for 12VDC VENT output) | JV DB39-01263A CN83 Pigtail | [ ] |
Dimensional Drawing Description
The unit dimensions are provided in inches. Key features include:
- Liquid pipe connection (1/4 inch)
- Gas pipe connection (1/2 inch)
- Drain hose connection
- Opening for power and communication wire conduit
- Air outlet louver
- Air inlet grille
The drawing illustrates the overall unit size and mounting considerations, showing specific measurements for ceiling opening, suspension points, and overall unit depth and height.
Certifications and Affiliations
[ETL Listed] by Intertek.
[AHRI Certified] for Unitary Small HP, AHRI Standard 210/240. Certification applies only when the complete system is listed with AHRI.
Powered by Samsung.
Lennox maintains a policy of ongoing development. Specifications are subject to change without notice.