Lennox V36D048S6-5P VRF 360 Cassette Indoor Unit

Submittal Data

Powered by SAMSUNG

Job Name: [Job Name Placeholder]

Purchaser: [Purchaser Placeholder]

Submitted to: [Submitted to Placeholder]

Unit designation: [Unit Designation Placeholder]

Location: [Location Placeholder]

Engineer: [Engineer Placeholder]

Reference: [Reference Placeholder]

Approval: [Approval Placeholder]

Construction: [Construction Placeholder]

Schedule #: [Schedule # Placeholder]

General Information

  • The system shall feature comfort humidity control. Utilizing an integral humidity sensor, the system optimizes the indoor unit coil temperature according to the dew point, maximizing energy savings while still providing space dehumidification and occupant comfort.
  • The indoor unit shall have an integral condensate pump with maximum 29" lift from bottom of the unit with check valve and float switch to disable unit in the event of condensate overflow.
  • The indoor unit fascia panel shall have a built-in Wi-Fi adapter as standard to allow control and monitoring using the Samsung SmartThings app.

Construction

  • Insulated, HIPS chassis and fascia panel certified to UL94 V0.
  • Includes a knock-out for outside air capability (booster fan connection).
  • All heat exchangers shall be mechanically boded aluminum fin to copper tube.

Refrigerant System

  • The system shall utilize low-GWP R-32 refrigerant.
  • Refrigerant flow shall be controlled by an electronic expansion valve at the indoor unit.
  • The indoor unit shall include an R32 alarm output plug for simple notification of R32 leak detection (VSTAT10P-1 accessory required).

Indoor Fan

  • Three fan speed settings and auto settings.
  • Washable filter as standard.
  • The indoor unit shall have LED indicator lights and an infrared receiver.
  • The indoor unit shall not have air louvers or blades allowing full airflow without restriction.
  • Air direction control shall be achieved by creating a low-pressure area near air outlet causing discharge air to change direction angle.
  • Fixed or auto-swing air direction shall be possible with local and central controller options (10° ~ 60° angle).
  • Independent air distribution control shall be possible with wireless or premium wired controller (three directions, 10° ~ 60° angle).

Controls

  • Control wiring shall be 2 X 16 AWG.
  • The unit shall be operated via a wireless or wired remote control with DDC-type signal (purchased separately).
  • Dual set temperature support when connected to supported controllers.
  • No additional interface modules/adapters are required when connecting to Samsung central control options.
  • Wired or wireless controllers must be purchased separately.

External Heat Control

  • External heat control functionality allows for configuration of fan operation during auxiliary heat operation, defrost, and emergency heat (VSTAT10P-1 accessory required).
  • External heat control configuration settings include outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).
  • Emergency heat functionality allows the system to continue controlling the external heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).

Convenience

  • Emergency Temperature Output (ETO) function: when indoor unit is in error status or when room temperature exceeds a configurable temperature level, the system outputs a signal to an external source (e.g., backup system, building management system, alert device like status light, warning lamp, or buzzer).

Specifications

SpecificationDetails
ModelV36D048S6-5P
Indoor Unit Model NumberV36D048S6-5P
Performance - Cooling (Btu/h)48,000
Performance - Heating (Btu/h)54,000
Voltage1/208-230/60
Operating Current (max.) - Cooling (A)0.75
Operating Current (max.) - Heating (A)0.75
Power - MCA (A)1.13
Power - MOP (A)15
Evaporator Fan - TypeBLDC (1) With Turbo Type Fan (1)
Evaporator Fan - Output (Watts)97
Airflow - Cooling (CFM)848/954/1,112
Airflow - Heating (CFM)848/954/1,112
Refrigerant - TypeR-32
Refrigerant - A2L Leak DetectionIntegral
Pipe Connections - Low side (In.)3/8
Pipe Connections - High side (In.)5/8
Condensate1 1/4 in. OD, 1 in. ID
Dimensions - W X H X D (In.)37 1/4 X 14 3/8 X 37 1/4
Dimensions - Weight (lbs.)50.70
Sound Pressure Level - Low/Med./High (dB(A))39/42/44
Safety - CertificationsUL 60335-2-40
Fascia Panel - Open Type (Round) - L X W X H (in.)41 3/8 X 3 3/8
Fascia Panel - Open Type (Round) - Weight (lbs.)8.85
Fascia Panel - Ceiling Type (Square) - L X W X H (in.)39 3/8 X 39 3/8 X 2 5/8
Fascia Panel - Ceiling Type (Square) - Weight (lbs.)6.62
Safety - CertificationsUL 60335-2-40

Accessories

Fascia Panel

  • Open Type (round, black) - V1V36D02CPBW
  • Open Type (round, white) - V1V36D02CPWW
  • Ceiling Type (square, black) - V1V36D01CPBW
  • Ceiling Type (square, white) - V1V36D01CPWW

Controllers & Modules

  • Advanced - VSTAT04P-1
  • Touchscreen - VSTAT02P-1
  • Thermostat adapter (for connection to standard 24VAC thermostats) - VSTAT09P-1
  • Wireless controller - VSTAT01P-1
  • External temperature sensor - VCTRL11P-1
  • External contact control interface module - VSTAT10P-1
  • Motion detect sensor (MDS, white, compatible with square panel only) - V1MDS03CS
  • CN83 Pigtail (for 12VDC VENT output) - JV DB39-01263A CN83 Pigtail

Dimensional Drawing - Ceiling Type Fascia Panel

Unit: Inches

This section provides dimensional drawings for the unit with a Ceiling Type Fascia Panel.

Diagram Description:

  • Top View: Shows the square panel dimensions and mounting points.
  • Side View: Illustrates the unit's depth and how it integrates with the ceiling.
  • Front View: Details the air outlet and inlet grilles, fascia panel, and connection points.
  • Back View: Shows the rear of the unit with connection points and mounting details.

Labeled Components:

No.Description
1Liquid pipe connection (1/4)
2Gas pipe connection (1/2)
3Drain pipe connection
4Opening for power and communication wire conduit
5Air outlet opening
6Air inlet grille
7Suction inlet for booster fan
8Fascia panel
9Drain hose
10Fresh air intake
11Display
12Wireless signal receiver

Dimensional Drawing - Open Type Fascia Panel

Unit: Inches

This section provides dimensional drawings for the unit with an Open Type Fascia Panel.

Diagram Description:

  • Top View: Shows the round panel dimensions and mounting points.
  • Side View: Illustrates the unit's depth and how it integrates with the ceiling.
  • Front View: Details the air outlet and inlet grilles, fascia panel, and connection points.
  • Back View: Shows the rear of the unit with connection points and mounting details.

Labeled Components:

No.Description
1Liquid pipe connection (1/4)
2Gas pipe connection (1/2)
3Drain pipe connection
4Opening for power and communication wire conduit
5Air outlet opening
6Air inlet grille
7Suction inlet for booster fan
8Fascia panel
9Drain hose
10Fresh air intake
11Display
12Wireless signal receiver

PDF preview unavailable. Download the PDF instead.

sbmtl v36d048s6-5p 2509 Adobe InDesign 20.4 (Windows) Adobe PDF Library 17.0

Related Documents

Preview LENNOX V33D030S6-5P VRF 4-Way Cassette Indoor Unit Submittal Data
Submittal data sheet for the LENNOX V33D030S6-5P VRF 4-Way Cassette indoor unit, detailing specifications, features, construction, and dimensions. Compatible with R-32 VRF systems.
Preview Lennox V33D048S6-5P VRF 4-Way Cassette Submittal Data
Technical specifications and features for the Lennox V33D048S6-5P VRF 4-Way Cassette indoor unit, including performance data, construction details, accessories, and dimensional information.
Preview Lennox VOWD009S6-5P VRF 1-Way Cassette Indoor Unit Submittal Data & Specifications
Detailed submittal data and technical specifications for the Lennox VOWD009S6-5P VRF 1-Way Cassette indoor unit, covering general information, construction, performance, airflow, controls, and available accessories.
Preview Lennox V22D005S6-5P VRF 4-Way Cassette Indoor Unit Submittal Data
Submittal data and specifications for the Lennox V22D005S6-5P VRF 4-Way Cassette (2x2) indoor unit, detailing its features, construction, performance, controls, and accessories.
Preview Lennox VUCD048S6-5P VRF Ceiling Mount Submittal Data and Specifications
Detailed submittal data, specifications, and dimensional drawings for the Lennox VUCD048S6-5P VRF Ceiling Mount unit, featuring R-32 refrigerant, integral Wi-Fi, and advanced controls.
Preview Lennox V36D048S6-5P VRF 360 Cassette Submittal Data and Specifications
Detailed submittal data and specifications for the Lennox V36D048S6-5P VRF 360 Cassette indoor unit, including features, construction, refrigerant system, fan, controls, external heat control, convenience functions, specifications, and accessories.
Preview Lennox VWMD018S6-5P VRF Wall Mount Indoor Unit Specifications and Features
Detailed submittal data for the Lennox VWMD018S6-5P VRF Wall Mount Indoor Unit, including specifications, features, construction, controls, and accessories. Compatible with R-32 VRF systems.
Preview Lennox V22D009S6-5P VRF 4-Way Cassette: Submittal Data & Specifications
Detailed submittal data and specifications for the Lennox V22D009S6-5P VRF 4-Way Cassette indoor unit, featuring Calm air mode, R-32 refrigerant compatibility, and advanced control options.