General Information
- Compatible with R-32 VRF air, water, and mini systems.
- Calm Air Mode: When activated in cooling mode, the unit closes its louvers and disperses air through thousands of micro-holes on the front of the indoor unit, preventing cold air drafts on occupants.
- Condensate Pump: Integral pump with maximum 26-5/16" lift from the unit bottom (21-5/16" from drain outlet). Includes a check valve and float switch to disable the unit in case of condensate overflow.
- Wi-Fi Connectivity: The fascia panel includes a built-in Wi-Fi adapter as standard, enabling control and monitoring via the Samsung SmartThings app.
Construction
- Insulated HIPS chassis and fascia panel, certified to UL94 V0.
- High-voltage terminal block features a temperature sensor to disable the unit if power connection overheats.
Refrigerant System
- Heat exchanger: Mechanically bonded aluminum fin to copper tube.
- R32 alarm output plug: For simple notification or interlock of third-party equipment upon R32 leak detection (requires VSTAT10P-1 accessory).
Indoor Fan
- Three fan speed settings and an auto setting.
- Electro-static, washable filter included as standard with the fascia panel.
- Fascia panel features: LED display, infrared receiver, and motorized louvers.
Controls
- Control wiring: 2 x 16 AWG.
- Operation: Via wired remote controller model VSTAT04P-1 (purchased separately).
- Dual set temperature support when connected to supported controllers.
- Wired or wireless controllers must be purchased separately.
External Heat Control
- Allows configuration of fan operation during auxiliary heat, defrost, and emergency heat operations (requires VSTAT10P-1 accessory).
- Configuration settings include: outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (requires VSTAT10P-1 accessory).
- Emergency heat functionality: Enables the system to continue controlling the external heat source even when system errors prevent the heat pump from operating (requires VSTAT10P-1 accessory).
Convenience
- Emergency Temperature Output (ETO): When the indoor unit is in an error status or the room temperature exceeds a configurable level, the system outputs a signal to an external source (e.g., backup system, building management system, alert device like a status light, warning lamp, or buzzer).
Specifications
Model | Indoor Unit Model Number | VOWD024S6-5P |
Performance | Nominal Capacity Cooling (Btu/h) | 24,000 |
Nominal Capacity Heating (Btu/h) | 27,000 | |
Power | Voltage Ø/V/Hz | 1 / 208-230 / 60 |
Power | Operating Current (max.) Cooling (A) | 0.40 |
Operating Current (max.) Heating (A) | 0.40 | |
MCA (A) | 0.5 | |
Power | MOP (A) | 15 |
Evaporator Fan | Type | BLDC motor with cross-flow fan |
Output (Watts) | 54 | |
Airflow | Air Volume Cooling (CFM) | 494 / 547 / 600 |
Air Volume Heating (CFM) | 494 / 547 / 600 | |
Refrigerant | Type | R-32 |
Refrigerant | A2L Leak Detection | Integral |
Pipe Connections | High side (In.) | 3/8 |
Low side (In.) | 5/8 | |
Dimensions | Condensate (In.) W X H X D | 1 1/4 in. OD, 1 in. ID |
Unit (In.) W X H X D | 47 1/4 X 5 7/16 X 17 3/4 | |
Weight (lbs.) | 28.70 | |
Sound Pressure Level | Low/Med./High (dB(A)) | 37 / 40 / 43 |
Safety | Certifications | UL 60335-2-40 |
Fascia Panel (In.) L X W X H | 55 1/2 X 4.75 X 1 3/8 | |
Fascia Panel | Weight (lbs.) | 11.0 |
Safety | Certifications | UL 60335-2-40 |
Accessories
- Fascia Panel: V1VOWD05CPWW
- Wired controller (Advanced): VSTAT04P-1
- Wired controller (Touchscreen): VSTAT02P-1
- Thermostat adapter (for connection to standard 24VAC thermostats): VSTAT09P-1
- Wireless controller: VSTAT01P-1
- External temperature sensor: VCTRL11P-1
- External contact control interface module: VSTAT10P-1
- CN83 Pigtail (for 12VDC VENT output): JV DB39-01263A CN83 Pigtail
Dimensional Drawing Description
The dimensional drawing illustrates the Lennox Samsung VOWD024S6-5P VRF 1-Way Cassette unit. Key dimensions are provided in inches:
- Overall Unit Width: 47 1/4 inches
- Overall Unit Height: 5 7/16 inches
- Overall Unit Depth: 17 3/4 inches
- Fascia Panel Dimensions: 55 1/2 inches (Length) x 4.75 inches (Width) x 1 3/8 inches (Height)
- Ceiling Opening (approximate): 54 5/16 inches x 49 5/8 inches
- Suspension points are indicated.
Connection points are detailed:
- Liquid pipe connection: 3/8 inch
- Gas pipe connection: 5/8 inch
- Drain hose connection
- Opening for power and communication wire conduit
- Air outlet louver
- Air inlet grille
The drawing shows side, front, and top views of the unit, highlighting its cassette form factor and installation considerations.
Related Documents
![]() |
Lennox VMDD012S6-5P VRF Medium Static Ducted Submittal Data Submittal data for the Lennox VMDD012S6-5P VRF Medium Static Ducted indoor unit, detailing its specifications, features, accessories, and dimensions. Compatible with R-32 VRF systems and offers Wi-Fi connectivity via Samsung SmartThings app. |
![]() |
Lennox VOWD009S6-5P VRF 1-Way Cassette Indoor Unit Submittal Data & Specifications Detailed submittal data and technical specifications for the Lennox VOWD009S6-5P VRF 1-Way Cassette indoor unit, covering general information, construction, performance, airflow, controls, and available accessories. |
![]() |
Lennox VUCD048S6-5P VRF Ceiling Mount Submittal Data and Specifications Detailed submittal data, specifications, and dimensional drawings for the Lennox VUCD048S6-5P VRF Ceiling Mount unit, featuring R-32 refrigerant, integral Wi-Fi, and advanced controls. |
![]() |
Lennox V36D048S6-5P VRF 360 Cassette Submittal Data and Specifications Detailed submittal data and specifications for the Lennox V36D048S6-5P VRF 360 Cassette indoor unit, including features, construction, refrigerant system, fan, controls, external heat control, convenience functions, specifications, and accessories. |
![]() |
Lennox V22D005S6-5P VRF 4-Way Cassette Indoor Unit Submittal Data Submittal data and specifications for the Lennox V22D005S6-5P VRF 4-Way Cassette (2x2) indoor unit, detailing its features, construction, performance, controls, and accessories. |
![]() |
Lennox V33D048S6-5P VRF 4-Way Cassette Submittal Data Technical specifications and features for the Lennox V33D048S6-5P VRF 4-Way Cassette indoor unit, including performance data, construction details, accessories, and dimensional information. |
![]() |
Lennox V36D048S6-5P VRF 360 Cassette Indoor Unit Submittal Data Technical specifications, features, and dimensional data for the Lennox V36D048S6-5P VRF 360 Cassette indoor unit, including construction, refrigerant system, fan, controls, and accessories. |
![]() |
LENNOX V33D030S6-5P VRF 4-Way Cassette Indoor Unit Submittal Data Submittal data sheet for the LENNOX V33D030S6-5P VRF 4-Way Cassette indoor unit, detailing specifications, features, construction, and dimensions. Compatible with R-32 VRF systems. |