Lennox VUCD048S6-5P VRF Ceiling Mount
Submittal Data
Job Information
- Job Name:
- [Not Specified]
- Purchaser:
- [Not Specified]
- Submitted to:
- [Not Specified]
- Unit designation:
- [Not Specified]
- Location:
- [Not Specified]
- Engineer:
- [Not Specified]
- Reference:
- [Not Specified]
- Approval:
- [ ]
- Construction:
- [ ]
- Schedule #:
- [Not Specified]
General Information
- Compatible with R-32 VRF air, water, and mini systems.
- The indoor unit features integral Wi-Fi adapter ? as standard to allow control and monitoring using the Samsung SmartThings app.
Construction
- HIPS chassis certified to UL94 V0 with a galvanized steel base.
Refrigerant System
- The heat exchanger is mechanically bonded aluminum fin to copper tube.
- The indoor unit includes an R32 ? alarm output plug for simple notification or interlock of third-party equipment upon R32 leak detection (VSTAT10P-1 accessory required).
Indoor Fan
- Indoor fan is sirocco type.
- Fan supports three fan speeds and Auto setting.
- Washable filter included as standard.
Controls
- Control wiring is 2 X 16 AWG.
- The unit is operated via a wired remote controller model VSTAT04P-1, purchased separately.
- Dual set temperature support when connected to supported controllers.
- Wired or wireless controllers must be purchased separately.
External Heat Control
- External heat control functionality allows for configuration of fan operation during auxiliary heat operation, defrost, and emergency heat (VSTAT10P-1 accessory required).
- External heat control configuration settings include outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).
- Emergency heat functionality allows the system to continue controlling the external heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).
- External heat control functionality allows for configuration of fan operation during auxiliary heat operation, defrost, and emergency heat.
- Emergency heat functionality allows the system to continue controlling the external heat source even when system errors prevent the heat pump from operating.
Convenience
- Emergency Temperature Output (ETO) function: when the indoor unit is in error status or when room temperature exceeds a configurable temperature level, the system outputs a signal to an external source (e.g., backup system, building management system, alert device like status light, warning lamp, or buzzer).
Certifications
Ⓣ ETL LISTED
? AHRI CERTIFIED®
Unitary Small HP, AHRI Standard 210/240. Certification applies only when the complete system is listed with AHRI.
Lennox maintains a policy of ongoing development. Specifications are subject to change without notice.
Specifications
VUCD048S6-5P | |
---|---|
Model Indoor Unit Model Number |
VUCD048S6-5P |
Performance Nominal Capacity |
Cooling (Btu/h): 48,000 Heating (Btu/h): 54,000 |
Voltage: Ø/V/Hz: 1/208-230/60 | |
Power Operating Current (max.) |
Cooling (A): 1.45 Heating (A): 1.45 |
MCA: A: 3.30 | |
MOP: A: 15 | |
Evaporator Fan Type |
BLDC (1) With Sirocco Fan (3) |
Output: Watts: 244 | |
Airflow Air Volume (L/M/H) |
Cooling (CFM): 918 / 1,088 / 1,286 Heating (CFM): 918 / 1,088 / 1,286 |
Refrigerant Type |
R-32 ? |
A2L Leak Detection: Integral | |
Pipe Connections Refrigerant |
High side (In.): 3/8 Low side (In.): 5/8 |
Condensate | OD 1 1/4", ID 1" |
Dimensions W X H X D |
In.: 65 X 9 1/4 X 26 9/16 |
Weight | lbs.: 92.60 |
Sound Pressure Level Low/Med./High |
dB(A): 38 / 43 / 46 |
Safety Certifications |
UL 60335-2-40 |
Accessories
Accessory Type | Model Number |
---|---|
Wired controller (Advanced Touchscreen) | VSTAT04P-1 |
Wired controller (Touchscreen) | VSTAT02P-1 |
Thermostat adapter (for connection to standard 24VAC thermostats) | VSTAT09P-1 |
Wireless controller | VSTAT01P-1 |
External temperature sensor | VCTRL11P-1 |
External contact control interface module | VSTAT10P-1 |
CN83 Pigtail (for 12VDC VENT output) | JV DB39-01263A CN83 Pigtail |
Dimensional Drawing
Unit: Inches
The dimensional drawing provides a visual representation of the unit's physical dimensions and component locations. It includes multiple views (front, side, top, and detail views) showing measurements and connection points.
No. | Description |
---|---|
1 | Liquid pipe connection (3/8") |
2 | Gas pipe connection (5/8") |
3 | Condensate drain |
4 | Conduit hole |
5 | Knockout hole for upper piping |
6 | Knockout hole for rear piping |
7 | Knockout hole for drain pipe |
8 | Knockout hole for fresh air intake |
9 | Air filter |
10 | Air suction grille |
11 | Cover side |
12 | Knockout hole for side piping |
Key dimensions indicated in the drawing include:
- Overall Width: 65 inches
- Overall Height: 9 1/4 inches
- Overall Depth: 26 9/16 inches
- Pipe connection sizes are specified as 3/8" for liquid and 5/8" for gas.
- Condensate drain size is 1 1/4" OD / 1" ID.