Lennox V22D009S6-5P VRF 4-Way Cassette

Submittal Data

Powered by SAMSUNG

General Information

  • Compatible with R-32 VRF air, water, and mini-VRF systems.
  • Calm Air Mode: When activated in cooling mode, the unit closes its louvers and disperses air through thousands of micro-holes on the front, preventing cold air drafts on occupants.
  • Integral Condensate Pump: Features a pump with a maximum 29" lift from the bottom of the unit, including a check valve and float switch to disable the unit in case of condensate overflow.
  • Wi-Fi Connectivity: The fascia panel includes a built-in Wi-Fi adapter as standard, enabling control and monitoring via the Samsung SmartThings app.

Construction

  • Insulated HIPS chassis and fascia panel certified to UL94 V0.
  • Includes a knock-out for outside air capability (booster fan connection).

Refrigerant System

  • Heat exchanger: Mechanically bonded aluminum fin to copper tube.
  • Refrigerant flow: Controlled by an electronic expansion valve at the outdoor unit.
  • R32 Alarm Output: The indoor unit includes an R32 alarm output plug for simple notification or interlock of third-party equipment upon R32 leak detection (VSTAT10P-1 accessory required).

Indoor Fan

  • Fan Settings: Three fan speed settings and auto settings.
  • Filter: Washable filter as standard.
  • Fascia Panel Features: LED display, infrared receiver, and motorized louvers.
  • Calm Air Function: Closes the supply air outlet louver in cooling mode to gently disperse cool air without blowing directly onto occupants. This feature is optional and can be enabled using central or local control options.

Controls

  • Control Wiring: 2 x 16 AWG.
  • Operation: Via a wired remote controller model VSTAT04P-1 (purchased separately).
  • Temperature Support: Dual set temperature support when connected to supported controllers.
  • Controller Availability: Wired or wireless controllers must be purchased separately.

External Heat Control

  • Functionality: Allows configuration of fan operation during auxiliary heat, defrost, and emergency heat (VSTAT10P-1 accessory required).
  • Configuration Settings: Include outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).
  • Emergency Heat: Maintains control of the external heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).

Convenience

  • Emergency Temperature Output (ETO): When the indoor unit is in an error status or when room temperature exceeds a configurable level, the system outputs a signal to an external source (e.g., backup system, building management system, alert device like status light, warning lamp, or buzzer).

Specifications

SpecificationValue
ModelV22D009S6-5P
Indoor Unit Model NumberV22D009S6-5P
Nominal Capacity (Cooling)9,500 Btu/h
Nominal Capacity (Heating)10,500 Btu/h
Voltage1/208-230/60 Hz
Operating Current (max.) Cooling0.17 A
Operating Current (max.) Heating0.17 A
MCA0.24 A
MOP15 A
Evaporator Fan TypeBLDC (1) With Turbo Type Fan (1)
Evaporator Fan Output65 Watts
Airflow (Cooling CFM)265 / 300 / 353
Airflow (Heating CFM)265 / 300 / 353
Refrigerant TypeR-32
A2L Leak DetectionIntegral
Pipe Connections (High side)1/4 in.
Pipe Connections (Low side)1/2 in.
Condensate Connection1 1/4 in. OD, 1 in. ID
Dimensions (W x H x D)22 5/8 x 9 13/16 x 22 5/8 in.
Weight25.60 lbs.
Sound Pressure Level (Low/Med/High)26 / 30 / 33 dB(A)
Safety CertificationsUL 60335-2-40
Fascia Panel (L x W x H)24 3/8 x 24 3/8 x 2 3/8 in.
Fascia Panel Weight6.0 lbs.
Fascia Panel Safety CertificationsUL 60335-2-40

Accessories

Accessory TypeModel / Description
Fascia PanelV1V22D01CPWW
Wired controllerVSTAT04P-1, VSTAT02P-1, VSTAT09P-1, VSTAT01P-1, VCTRL11P-1, VSTAT10P-1
Advanced Touchscreen(Not specified)
Thermostat adapterFor connection to standard 24VAC thermostats
Wireless controller(Not specified)
External temperature sensor(Not specified)
External contact control interface module(Not specified)
Motion Detect Sensor (MDS)V1MDS02CS
CN83 Pigtail (for 12VDC VENT output)JV DB39-01263A CN83 Pigtail

Dimensional Drawing

The dimensional drawing provides detailed measurements for the V22D009S6-5P unit in inches.

Overall Unit Dimensions: Width: 22 5/8 in., Height: 9 13/16 in., Depth: 22 5/8 in.

Ceiling Opening: The required ceiling opening is approximately 22 5/8 in. x 22 5/8 in.

Suspension: Suspension points are indicated with a range of 22 13/16 to 23 1/16 inches.

Connections:

  • Liquid pipe connection (No. 1): 1/4 inch.
  • Gas pipe connection (No. 2): 1/2 inch.
  • Drain connection (No. 3): 1 1/4 inch OD, 1 inch ID. The maximum drain lift is 29 inches from the unit bottom, or 21 5/16 inches from the drain connection itself.
  • Opening for power and communication wire conduit (No. 4).

Airflow Components:

  • Air inlet grille (No. 5) is located on the bottom.
  • Supply air outlet louver (No. 6) is on the front face.
  • Fresh air intake (No. 7) is a 4-inch diameter opening.

Fascia Panel Dimensions: 24 3/8 in. x 24 3/8 in. with a thickness of 2 3/8 in.

Certifications

  • ETL Listed
  • AHRI Certified® Unitary Small HP (AHRI Standard 210/240)

PDF preview unavailable. Download the PDF instead.

sbmtl v22d009s6-5p 2508 Adobe InDesign 20.4 (Windows) Adobe PDF Library 17.0

Related Documents

Preview Lennox V22D005S6-5P VRF 4-Way Cassette Indoor Unit Submittal Data
Submittal data and specifications for the Lennox V22D005S6-5P VRF 4-Way Cassette (2x2) indoor unit, detailing its features, construction, performance, controls, and accessories.
Preview Lennox V36D048S6-5P VRF 360 Cassette Indoor Unit Submittal Data
Technical specifications, features, and dimensional data for the Lennox V36D048S6-5P VRF 360 Cassette indoor unit, including construction, refrigerant system, fan, controls, and accessories.
Preview Lennox VOWD009S6-5P VRF 1-Way Cassette Indoor Unit Submittal Data & Specifications
Detailed submittal data and technical specifications for the Lennox VOWD009S6-5P VRF 1-Way Cassette indoor unit, covering general information, construction, performance, airflow, controls, and available accessories.
Preview LENNOX V33D030S6-5P VRF 4-Way Cassette Indoor Unit Submittal Data
Submittal data sheet for the LENNOX V33D030S6-5P VRF 4-Way Cassette indoor unit, detailing specifications, features, construction, and dimensions. Compatible with R-32 VRF systems.
Preview Lennox V33D048S6-5P VRF 4-Way Cassette Submittal Data
Technical specifications and features for the Lennox V33D048S6-5P VRF 4-Way Cassette indoor unit, including performance data, construction details, accessories, and dimensional information.
Preview Lennox V22D020S6-5P VRF 4-Way Cassette Indoor Unit Submittal Data
Submittal data for the Lennox V22D020S6-5P VRF 4-Way Cassette indoor unit, detailing specifications, features, construction, and dimensional information for HVAC applications.
Preview Lennox VUCD048S6-5P VRF Ceiling Mount Submittal Data and Specifications
Detailed submittal data, specifications, and dimensional drawings for the Lennox VUCD048S6-5P VRF Ceiling Mount unit, featuring R-32 refrigerant, integral Wi-Fi, and advanced controls.
Preview Lennox V36D048S6-5P VRF 360 Cassette Submittal Data and Specifications
Detailed submittal data and specifications for the Lennox V36D048S6-5P VRF 360 Cassette indoor unit, including features, construction, refrigerant system, fan, controls, external heat control, convenience functions, specifications, and accessories.