Lennox V22D009S6-5P VRF 4-Way Cassette
Submittal Data
Powered by SAMSUNG
General Information
- Compatible with R-32 VRF air, water, and mini-VRF systems.
- Calm Air Mode: When activated in cooling mode, the unit closes its louvers and disperses air through thousands of micro-holes on the front, preventing cold air drafts on occupants.
- Integral Condensate Pump: Features a pump with a maximum 29" lift from the bottom of the unit, including a check valve and float switch to disable the unit in case of condensate overflow.
- Wi-Fi Connectivity: The fascia panel includes a built-in Wi-Fi adapter as standard, enabling control and monitoring via the Samsung SmartThings app.
Construction
- Insulated HIPS chassis and fascia panel certified to UL94 V0.
- Includes a knock-out for outside air capability (booster fan connection).
Refrigerant System
- Heat exchanger: Mechanically bonded aluminum fin to copper tube.
- Refrigerant flow: Controlled by an electronic expansion valve at the outdoor unit.
- R32 Alarm Output: The indoor unit includes an R32 alarm output plug for simple notification or interlock of third-party equipment upon R32 leak detection (VSTAT10P-1 accessory required).
Indoor Fan
- Fan Settings: Three fan speed settings and auto settings.
- Filter: Washable filter as standard.
- Fascia Panel Features: LED display, infrared receiver, and motorized louvers.
- Calm Air Function: Closes the supply air outlet louver in cooling mode to gently disperse cool air without blowing directly onto occupants. This feature is optional and can be enabled using central or local control options.
Controls
- Control Wiring: 2 x 16 AWG.
- Operation: Via a wired remote controller model VSTAT04P-1 (purchased separately).
- Temperature Support: Dual set temperature support when connected to supported controllers.
- Controller Availability: Wired or wireless controllers must be purchased separately.
External Heat Control
- Functionality: Allows configuration of fan operation during auxiliary heat, defrost, and emergency heat (VSTAT10P-1 accessory required).
- Configuration Settings: Include outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).
- Emergency Heat: Maintains control of the external heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).
Convenience
- Emergency Temperature Output (ETO): When the indoor unit is in an error status or when room temperature exceeds a configurable level, the system outputs a signal to an external source (e.g., backup system, building management system, alert device like status light, warning lamp, or buzzer).
Specifications
Specification | Value |
---|---|
Model | V22D009S6-5P |
Indoor Unit Model Number | V22D009S6-5P |
Nominal Capacity (Cooling) | 9,500 Btu/h |
Nominal Capacity (Heating) | 10,500 Btu/h |
Voltage | 1/208-230/60 Hz |
Operating Current (max.) Cooling | 0.17 A |
Operating Current (max.) Heating | 0.17 A |
MCA | 0.24 A |
MOP | 15 A |
Evaporator Fan Type | BLDC (1) With Turbo Type Fan (1) |
Evaporator Fan Output | 65 Watts |
Airflow (Cooling CFM) | 265 / 300 / 353 |
Airflow (Heating CFM) | 265 / 300 / 353 |
Refrigerant Type | R-32 |
A2L Leak Detection | Integral |
Pipe Connections (High side) | 1/4 in. |
Pipe Connections (Low side) | 1/2 in. |
Condensate Connection | 1 1/4 in. OD, 1 in. ID |
Dimensions (W x H x D) | 22 5/8 x 9 13/16 x 22 5/8 in. |
Weight | 25.60 lbs. |
Sound Pressure Level (Low/Med/High) | 26 / 30 / 33 dB(A) |
Safety Certifications | UL 60335-2-40 |
Fascia Panel (L x W x H) | 24 3/8 x 24 3/8 x 2 3/8 in. |
Fascia Panel Weight | 6.0 lbs. |
Fascia Panel Safety Certifications | UL 60335-2-40 |
Accessories
Accessory Type | Model / Description |
---|---|
Fascia Panel | V1V22D01CPWW |
Wired controller | VSTAT04P-1, VSTAT02P-1, VSTAT09P-1, VSTAT01P-1, VCTRL11P-1, VSTAT10P-1 |
Advanced Touchscreen | (Not specified) |
Thermostat adapter | For connection to standard 24VAC thermostats |
Wireless controller | (Not specified) |
External temperature sensor | (Not specified) |
External contact control interface module | (Not specified) |
Motion Detect Sensor (MDS) | V1MDS02CS |
CN83 Pigtail (for 12VDC VENT output) | JV DB39-01263A CN83 Pigtail |
Dimensional Drawing
The dimensional drawing provides detailed measurements for the V22D009S6-5P unit in inches.
Overall Unit Dimensions: Width: 22 5/8 in., Height: 9 13/16 in., Depth: 22 5/8 in.
Ceiling Opening: The required ceiling opening is approximately 22 5/8 in. x 22 5/8 in.
Suspension: Suspension points are indicated with a range of 22 13/16 to 23 1/16 inches.
Connections:
- Liquid pipe connection (No. 1): 1/4 inch.
- Gas pipe connection (No. 2): 1/2 inch.
- Drain connection (No. 3): 1 1/4 inch OD, 1 inch ID. The maximum drain lift is 29 inches from the unit bottom, or 21 5/16 inches from the drain connection itself.
- Opening for power and communication wire conduit (No. 4).
Airflow Components:
- Air inlet grille (No. 5) is located on the bottom.
- Supply air outlet louver (No. 6) is on the front face.
- Fresh air intake (No. 7) is a 4-inch diameter opening.
Fascia Panel Dimensions: 24 3/8 in. x 24 3/8 in. with a thickness of 2 3/8 in.
Certifications
- ETL Listed
- AHRI Certified® Unitary Small HP (AHRI Standard 210/240)